One-stop Solution for Wire & Cable · Since 1969
THHW THWN
Building Wire

THHW THWN

THHN/THWN-2 Copper, PVC Insulated

  • THHN/THWN-2 Marking apply only to sizes 8 AWG up to 1000 kcmil.
  • Use of lubrication is not
  • mandatory to install THHN/ THWN-2 conductors in the

Product Description

THHN/THWN-2 Copper, PVC Insulated

Nylon Jacket, 600 V

A

Features

THHN/THWN-2 Marking apply only to sizes 8 AWG up to 1000 kcmil.

Use of lubrication is not

mandatory to install THHN/ THWN-2 conductors in the

raceways or cable trays.

PVC insulation offers exceptional electrical, physical and flame-

retardant properties.

All sizes are UL/cUL Listed as MTW (Not Solid), AWM,

T90 Nylon, and TWN75.

All sizes meet VW-1 and FT1 Vertical Flame Test.

All colors in sizes 1/0 and larger are UL listed and marked CT USE in accordance with NEC meeting UL 1685 vertical-tray flame test and also marked FT4 meeting

IEEE 1202 vertical-tray test both at 70,000 BTU/Hr.

All colors in sizes 8 AWG and larger are rated SR for Sunlight Resistance exposure.

All sizes and colors are GRII for Gasoline and Oil resistance.

RoHS compliance in sizes 14 AWG to 10 AWG.

BIG Sequential Footage Marking for easy identification, in sizes 1/0 AWG and larger, every 1 ft.

1

2

3

Colored insulation and a nylon jacket are color-coded (sizes 8 AWG and larger) for visual identification of conductors in electrical installations.

Engineering Information

1. Conductors: Solid uncoated

copper conductors per ASTM B3.

Stranded uncoated copper conductors per ASTM B3, B8 and B787.

On request, Class I for conductor size 250 kcmil to 1000 kcmil per per ASTM B172 and ASTM B174.

2. Insulation: Polyvinyl Chloride (PVC) per UL 83 and UL 1063.

3. Jacket (color coded): Low

friction tough polyamide, Nylon, per UL 83 and UL 1063.

Installation Performance A significant reduction (25% – 30%) in the pulling force is achieved

for THHN/THWN-2 when

compared to the pulling forced required for Standard THHN/

THWN-2 without any lubricant. Further, this reduction is

  • comparable to the reduction
  • achieved when the Standard
  • THHN/THWN-2 conductors
  • are pulled using a lubricant in
  • identical installation. These
  • results demonstrate that it is

feasible to install the THHN/ THWN-2 conductors without the use of a lubricant in an NFPA

70 (NEC ) compliant installation.

Application

HNQZ Wire and Cable

THHN/THWN-2 conductors in all colors are suitable for use in general-purpose wiring in

Bu i ld ing Wire

accordance with the

requirements of NFPA 70 (NEC ). Type THHN/THWN-2 conductors are approved for use at a

maximum voltage of 600 volts and a maximum conductor

temperature of 90 °C in wet or dry locations and 75 °C when exposed to gasoline and oil.

Also rated AWM for 105 °C dry and 80 °C in oil.

Specifications

UL Standard 83 (THHN/THWN-2)

UL Standard 758 (AWM) UL Standard 1063 (MTW)

CSA Standard C22.2 No. 75 (T90

Nylon/TWN75.

ASTM B3, B8, and B787.

ICEA S-95-658/NEMA WC70.

Federal Specification A-A-59544.

ANSI/NFPA 70 National Electric Code (NEC ).

Test Methods: UL 1581, UL 2556, and UL 1685 as applicable

pulling force for THHN/THWN-2

500 – 500 – 500 – 1/o THHN/THWN-2 conductors in 3″ EMT conduits with four 90 o Bends

conduit fill: 30. 8%

THHN/THWN-2 Copper, PVC Insulated, Nylon Jacket, 600 V

THHN/THWN-2 600 V, Copper Conductors

The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors, and accessories should be verified using the actual dimensions of the product.

* Allowable capacities shown are for general use as specified by the National Electrical Code Sections 310.15 and 240.4(D). In addition, also refer to Section 110.14 for requirements for markings on the equipment and the permitted ampacities for the conductors.

** For made-to-order items: Minimum runs, pricing, and lead times are subject to the plant’s production schedule.

*** Size 8 solid in green color is available as a stock item.

PRINT LEGENDS Sizes:

STRANDED CONDUCTOR SIZES 8–1 AWG (IN ALL COLORS):

HNQZ WIRE & CABLE E102470 S (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II SIZE AWG (SIZE mm²) CU 600 V VW-1 SR OR C(UL) TYPE T90 NYLON OR TWN75 FT1.

CONDUCTOR SIZES: 1/0 AWG – 1000 kcmil (IN ALL COLORS):

HNQZ WIRE & CABLE E102470 S (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II SIZE AWG (SIZE mm²) CU 600 V VW-1 SR FOR CT USE FT4 OR C(UL) TYPE T90 NYLON OR TWN75 FT1.

PRINT LEGEND: 8 AWG SOLID (IN ALL COLORS)

HNQZ WIRE & CABLE E95989 S (UL) THHN OR THWN-2 OR AWM OR GR II (SIZE) AWG (SIZE mm²) CU 600 V VW-1 SR OR C(UL) TYPE T90 NYLON OR TWN75 FT1

PRINT LEGENDS: 14–10 AWG:

SOLID:

HNQZ WIRE & CABLE E95989 S (UL) THHN OR THWN-2 OR AWM OR GR II (SIZE) AWG (SIZE mm²) CU 600 V VW-1 OR C(UL) TYPE T90 NYLON OR TWN75 FT1 RoHS

STRANDED:

HNQZ WIRE & CABLE E102470 S (UL) MTW OR THHN OR THWN-2 ORAWM OR GR II (SIZE) AWG (SIZE mm²) CU 600 VW-1 OR C(UL) TYPE T90 NYLON OR TWN75 FT1 RoHS

THHN/THWN-2 Copper, PVC Insulated, Nylon Jacket, 600 V

Technical Data continued

THHN/THWN-2 600 V, Copper Conductors Flexible Stranding

Size

Strand

Size

(AWG)

Number

of strands

(Stranding

Class I)

Nominal Thickness

Nominal

Diameter

Nominal

Mass

Min Bending

Radius

Ampacity

AWG or

kcmil

mm2

PVC (in)

Nylon (in)

in

lb/kft

in

60 °C*

75 °C*

90 °C*

90 °C**

2

33.60

24

161

0.040

0.006

0.411

237

1.64

95

115

130

190

1

42.40

24

210

0.050

0.007

0.478

312

1.91

110

130

150

220

1/0

53.50

24

266

0.050

0.007

0.524

392

2.10

125

150

170

260

2/0

67.40

24

342

0.050

0.007

0.579

496

2.32

145

175

195

300

3/0

85.00

24

418

0.050

0.007

0.628

600

2.51

165

200

225

350

4/0

107.00

24

532

0.050

0.007

0.694

755

2.78

195

230

260

405

250

127.00

24

637

0.060

0.008

0.770

919

3.08

215

255

290

455

300

152.00

24

735

0.060

0.008

0.817

1053

3.27

240

285

320

500

350

177.00

24

882

0.060

0.008

0.882

1253

3.53

260

310

350

570

400

203.00

24

980

0.060

0.008

0.923

1387

3.69

280

335

380

615

500

253.00

24

1225

0.060

0.008

1.015

1719

5.08

320

380

430

700

600

304.00

24

1470

0.070

0.009

1.121

2072

5.61

355

420

475

780

750

380.00

24

1862

0.070

0.009

1.242

2625

6.21

400

475

535

885

The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors, and accessories should be verified using the actual dimensions of the product.

* Allowable capacities shown are for general use as specified by the National Electrical Code Sections 310.15(B)(16) of the NEC, 2017 Edition for insulated conductors rated

Up to and including 2000 volts, 60ºC Through 90ºC (140ºF Through 194ºF) Not more than three current-carrying conductors in a raceway, cable, or earth (directly buried), based on an ambient temperature of 30ºC (86ºF) and 240.4(D). In addition, also refer to Section 110.14 for requirements for markings on the equipment and the permitted ampacities for the conductors.

** Allowable Ampacities are based on Table 310.15(B)(17) of the NEC, 2017 Edition of Single-Insulated Conductors Rated Up to and Including 2000 Volts in Free Air, Based on an Ambient Temperature of 30ºC (86ºF)

PRINT LEGENDS Sizes:

CONDUCTOR SIZES 250 kcmil – 750 kcmil (IN ALL COLORS):

HNQZ WIRE & CABLE E315239 (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II SIZE AWG (SIZE mm²) (STRANDS Class I) CU 600 V VW-1 SR FOR CT USE FT4 OR C(UL) TYPE T90 NYLON OR TWN75 FT1.

Applicable Standards

UL 1685ASTM B3ASTM B172ASTM B174UL 83UL 1063ICEA S-95-658/NEMAUL 1581

Certificate Display

ISO 9001 Quality Management System
ISO 9001 Certificate (2025–2028)
ISO 9001 Certificate (NOA)
CE — Verification of Conformity
RoHS Compliance Attestation (EU)
Low Voltage Directive Attestation (EU)

Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.

Factory Tour

Why Choose Us

50+ years of experience Trusted manufacturing expertise since 1969
International standards IEC, ASTM, BS, CSA and other global standards
Strict quality control Comprehensive testing throughout production
Large production capacity Reliable supply for utility and EPC projects
Fast global delivery Efficient manufacturing and worldwide shipping
Technical support Expert assistance from inquiry to project completion

Packing & Shipping

  • Wooden, steel or steel-wood drums; drum length to customer requirement
  • Drum marking per customer / utility specification
  • Both drum ends sealed and protected for sea freight
Get in touch

Ready for Your Next Cable Project?

Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.

  • Emailinfo@qzcablegroup.com
  • WhatsApp / WeChat+86 173 3570 4553
  • Contact personChloe · Export Department
  • Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China

    The more specific the standard and size, the faster we can quote.
    Inquiry WhatsApp Email