Type MC Armored Cables
- UL Listed as MC.
- Single conductors are dual rated THHN/THWN-2, meeting 90 °C in Wet and Dry Locations.
- All Singles meet the VW-1 flame test.
Product Description
Type MC-HCF-AIA
Features
UL Listed as MC.
Single conductors are dual rated THHN/THWN-2, meeting 90 °C in Wet and Dry Locations.
All Singles meet the VW-1 flame test.
Insulation is rated Gas and Oil resistant II.
Cables is rated for CT use. RoHS-2 Compliant.
Listed for use in UL 1, 2 and 3 Hour Through Penetration
Firestop Systems C-AJ-310,
C-AJ-3111, C-AJ-3112, W-L-3077, W-L-3078.
For ease of pulling and
installation, the cable is reverse wound on reel. For coils, pull
from inside end to ensure ease of installation.
Application
For installations requiring
redundant, dedicated or isolated grounding paths.
Health Care Facilities: For branch
Per NEC 300.22(C), in
1
2
3
4
5
environmental air-handling spaces.
Class I Div. 2, Class II Div. 2, and Class III Div. 1 hazardous locations, in accordance with NEC.
2. Insulation Circuit & Ground:
Flame retardant thermoplastic polyvinyl chloride (PVC) and nylon covering.
Conductor’s and Ground ID:
Requires use of UL Listed MC-HCF-AIA fittings.
Bui lding Wire
Standards
UL 1569 Metal Clad cables.
UL 83 Thermoplastic-Insulated Wires and Cables.
UL 1685 Vertical-Tray Fire-
Propagation and Smoke-Release Test for Electrical and Optical- Fiber Cables.
|
480Y / 277V |
|||||||
|
# Cdr. |
Color Code |
Ground |
Al Bond |
||||
|
2 |
BN |
GY |
GN |
Bare |
|||
|
2 |
OE |
GY |
GN |
Bare |
|||
|
2 |
YW |
GY |
GN |
Bare |
|||
|
2 |
PE |
GY |
GN |
Bare |
|||
|
3 |
BN |
OE |
GY |
GN |
Bare |
||
|
3 |
OE |
YW |
GY |
GN |
Bare |
||
|
3 |
BN |
YW |
GY |
GN |
Bare |
||
|
3 |
YW |
PE |
GY |
GN |
Bare |
||
BN |
PE |
GY |
GN |
Bare |
|||
Federal Specification A-A-59544 (formerly J-C-30B).
ICEA S-95-658/NEMA WC70 (as applicable)
Specifications
Maximum operating voltage:
- 600 volts
- circuit wiring in patient care
- areas of hospitals, medical
centers, nursing homes, dental offices, clinics, outpatient
facilities and other health care facilities in accordance with
NEC articles 517, 330 and 300.4 as applicable. (Note: Use in
hazardous anesthetizing areas is not permitted.)
For places of assemblies and
theaters per NEC articles 518 and
520, respectively.
In cable tray and approved raceways.
Maximum conductor operation temperatures:
3. Assembly: All insulated
conductors, phases and
grounding, are individually
wrapped in a binder tape and twisted together.
4. Bare aluminum grounding/
bonding conductor: It is located outside the individually wrapped assembly of other conductors and in contact with the
interlocked aluminum armor.
5. Armor: Easy to identify green color aluminum interlocked
armor. It is applied over the
assembly of conductors, tape and in contact with aluminum grounding/bonding conductor.
• 90 °C Dry
Engineering Information
1. Conductor: Soft annealed uncoated copper solid wire
per ASTM B3, or soft annealed uncoated copper Class B or C concentric stranding or unilay (19 wires) per ASTM B8, or
combination unilay per ASTM B787.
Sizes: 14 AWG up to 10 AWG.
Number of Conductors: 2 to 3.
In dry locations and embedded in plaster finish on brick or other masonry, except in damp or wet locations.
Type MC/RG & MC/RG-HCF-AIA Al Bonding Wire in Contact with Armor, 90 °C
Technical Data
600 V Copper PVC/Nylon, Green Insulated Ground, Aluminum Bonding Wire in Contact with Armor, 90 °C
Conductor |
Grounding Wire |
Nominal O.D. |
Mass |
||
SizeAWG / # Conductors |
ConductorColor |
Insulated Ground(Green) |
SolidAluminumBonding Ground |
||
in |
lb/kft |
||||
|
Solid Copper Conductors with Solid Aluminum Bonding Ground Conductor 120/208 V |
|||||
|
14-2 |
BK/WE |
14 |
12 |
0.542 |
111 |
|
14-3 |
BK/WE/RD |
14 |
12 |
0.552 |
130 |
|
12-2 |
BK/WE |
12 |
10 |
0.563 |
140 |
|
12-2 |
RD/WE |
12 |
10 |
0.563 |
140 |
|
12-2 |
BE/WE |
12 |
10 |
0.563 |
140 |
|
12-3 |
BK/WE/RD |
12 |
10 |
0.590 |
155 |
|
10-2 |
BK/WE |
10 |
8 |
0.645 |
181 |
|
10-2 |
RD/WE |
10 |
8 |
0.645 |
181 |
|
10-2 |
BE/WE |
10 |
8 |
0.645 |
181 |
|
10-3 |
BK/WE/RD |
10 |
8 |
0.685 |
218 |
|
Stranded Copper Conductors with Solid Aluminum Bonding Ground Conductor, 120/208 V |
|||||
|
12-2 |
BK/WE |
12 |
10 |
0.585 |
147 |
|
12-2 |
RD/WE |
12 |
10 |
0.585 |
147 |
|
12-2 |
BE/WE |
12 |
10 |
0.585 |
147 |
|
12-3 |
BK/WE/RD |
12 |
10 |
0.621 |
176 |
|
10-2 |
RD/WE |
10 |
8 |
0.687 |
206 |
|
10-3 |
RD/WE/RD |
10 |
8 |
0.728 |
251 |
|
Multiple Neutrals: Solid copper conductors with solid aluminum bonding ground conductors |
|||||
|
12-2 12-2 |
BK/RD WE-BK/WE-RD |
12 |
10 |
0.563 |
140 |
|
12-3 12-3 |
BK/WE/RD WE-BK/WE-RD/WE-BE |
12 |
10 |
0.590 |
155 |
|
10-2 10-2 |
BK/RD WE-BK/WE-RD |
10 |
8 |
0.645 |
181 |
|
10-3 10-3 |
BK/WE/RD WE-BK/WE-RD/WE-BE |
10 |
8 |
0.685 |
218 |
|
Multiple Neutrals: Stranded Copper Conductors with Solid Aluminum Bonding Ground Conductor |
|||||
|
12-2 12-2 |
BK/RD WE-BK/WE-RD |
12 |
10 |
0.585 |
147 |
The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors, and accessories should be verified using the actual dimensions of the product. Other sizes are available upon request.
Capacities: Refer to the beginning of the section.
Color Abbreviations |
|||||||
Black |
White |
Brown |
Orange |
Yellow |
Purple |
Grey |
Green |
BK |
WE |
BN |
OE |
YW |
PE |
GY |
GN |
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
UD TRIPLEXTRI-RATED 600V
HNQZ’s tri-rated Type RHH/RHW-2 or USE-2 is primarily used for
TFFN TEWN
TFFN/TEWN PVC Insulated , Nylon Jacketed
Secondary Underground Distribution Aluminium Cable
Single conductors are UL Listed as Type USE-2.
Data Center – MC Feeder XHHWXHHW-2 AL 8000
MC Feeder, XHHW-2 Aluminum
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions