LT & HT POWER CABLE DIN VDE 0276
LV & MV Power Cables

LT & HT POWER CABLE DIN VDE 0276

LT & HT POWER CABLE DIN VDE 0276

  • Standards: IEC 60228 · IEC 60502-1 · IEC 60502 · BS 6346 · IEC 60502-2

Product Description

LT & HT POWER CABLE DIN VDE 0276

LOW VOLTAGE POWER CABLES WITH (PVC, PE and XLPE, HFFR) INSULATION

NYY, NAYY, NYBY, NAYBY, NYCY, NAYCY, NYCWY, NAYCWY, NYRY, NAYRY, NY2Y, NAY2Y (E-AY2Y), N2XY, NA2XY; N2X2Y, NA2X2Y, N2XYRY, NA2XYRY, 2XSY, NA2XSY, N2XS2Y, NA2XS2Y, N2XSEY, NA2XSEY, N2XSE2Y, NA2XSE2Y

NYY, NAYY

Power cable with PVC insulation and PVC sheath

Rated Voltage: U0/U – 0.6/1 kV

Standard: DIN VDE 0276/HD603 type 3G-2-power; DIN VDE 0276/HD627 type 4H1 – signal

Application

NYY, NAYY is used in power plants industrial and switching installations in secondary distribution networks and other These cables are preferentially used in outdoor applications for indoor installations in the open air underground and in water where mechanical damage is not anticipated. 

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228 Conductor:

solid or multi-strand Cu or Al wires

class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Core temperature, max: 70oC in operation
Max. short circuit temperature: 160 oC , not more than 5 sec Insulation: PVC type DIV4 acc. VDE0207
Rated voltage – U0 /U (Umax): 0.6/1(1.2) kV Core identification: according to VDE 0293
Test voltage: AC – 4 kV; 50 Hz Signal-command copper core:

Additional, cross section 2,5mm2,

red coloured (black coloured 1,5mm2 on request)

Temperature Range  

Cores assembly:

cores stranded concentrically

(cores stranded in concentric layers, for signal)

Fixed installation: -30°C to +70°C
Flexible Installation: -5°C to +50°C Inner sheath: rubber filling compound or tape
Bending radius, min.   Sheath: PVC type DMV5 acc. VDE 0207
single core: 15xDcable Color of sheath: black
multi core: 12xDcable  
Specific insulation resistance at 70°C: min, 1010 Ωx cm

Max. permessible tensile stress with cable grip:

For Cu conducor = 50 N/mm2
For Al conducor = 30 N/mm2
Construction data: NYY U0/U – 0.6/1kV
Number of cores x Nominal  Cross Section

Shape

Overall  Diameter (Approx.) Copper weight  (Approx.) Total  Weight  (Approx.) Packing: Cable coil or  Drum
No x mm²   max.mm kg/km kg/km m or N°/m
1×4 RE 8,0 38,0 104,0 100
1×6 RE 9,0 58,0 128,0 100
1×10 RE 10,0 96,0 176,0 100
1×16 RE 11,0 154,0 239,0 9/1000
1×25 RM 13,0 240,0 380,0 9/1000
1×35 RM 14,0 336,0 477,0 10/1000
1×50 RM 15,0 480,0 650,0 10/1000
1×70 RM 17,0 672,0 864,0 12/1000
1×95 RM 19,0 912,0 1132,0 12/1000
1×120 RM 21,0 1150,0 1405,0 14/1000
1×150 RM 22,0 1440,0 1710,0 14/1000
1×185 RM 24,0 1776,0 2086,0 14/1000
1×240 RM 27,0 2304,0 2669,0 16/1000
1×300 RM 30,0 2880,0 3305,0 16/1000
1×400 RM 34,0 3840,0 4337,0 18/1000
3×1.5 RE 12,0 43,0 223,0 9/1000
3×2.5 RE 13,0 72,0 272,0 9/1000
3×4 RE 15,0 115,0 373,0 10/1000
3×6 RE 16,0 173,0 466,0 12/1000
3×10 RE 18,0 288,0 629,0 12/1000
3×16 RE 20,0 461,0 850,0 12/1000
3×25/16 RM /RM 25,0 874,0 1595,0 14/1000
3×35/16 SM /RM 27,0 1162,0 1718,0 16/1000
3×50/25 SM /RM 30,5 1680,0 2383,0 14/500
3×70/35 SM /SM 33,0 2352,0 3196,0 14/500
3×95/50 SM /SM 38,0 3216,0 4271,0 16/500
3×120/70 SM /SM 41,0 4128,0 5281,0 16/500
3×150/70 SM /SM 45,5 4992,0 6408,0 18/500
3×185/95 SM /SM 50,0 6240,0 7909,0 20/500
3×240/120 SM /SM 57,0 8064,0 10162,0 22/500
4×1.5 RE 13,0 58,0 256,0 9/1000
4×2.5 RE 14,0 96,0 316,0 10/1000
4×4 RE 15,0 154,0 439,0 10/1000
4×6 RE 17,0 230,0 547,0 12/1000
4×10 RE 19,0 384,0 743,0 12/1000
4×16 RE 22,0 614,0 1039,0 14/1000
4×25 RM 26,5 960,0 1620,0 16/1000
4×35 SM 27,0 1344,0 1916,0 16/1000
4×50 SM 31,0 1920,0 2639,0 14/500
4×70 SM 35,0 2688,0 3576,0 14/500
4×95 SM 40,0 3648,0 4746,0 16/500
4×120 SM 43,0 4608,0 5813,0 16/500
4×150 SM 48,0 5760,0 7263,0 18/500
4×185 SM 53,0 7104,0 8905,0 20/500
4×240 SM 60,0 9210,0 11430,0 24/500
5×1.5 RE 14,0 72,0 292,0 10/1000
5×2.5 RE 15,0 120,0 363,0 10/1000
5×4 RE 17,0 192,0 510,0 12/1000
5×6 RE 18,5 288,0 640,0 12/1000
5×10 RE 21,0 480,0 899,0 14/1000
5×16 RE 23,0 768,0 1240,0 14/1000
5×25 RM 30,0 1200,0 1957,0 16/1000
7×1.5 RE 15,0 101,0 350,0 10/1000
10×1.5 RE 17.5 144,0 476,0 12/1000
12×1.5 RE 18,0 173,0 523,0 12/1000
14×1.5 RE 18,7 202,0 578,0 12/1000
19×1.5 RE 20,5 274,0 716,0 14/1000
           
24×1.5 R E 23,5 346,0 885,0 14/1000
30×1.5 R E 25,0 432,0 1045,0 14/1000
40×1.5 R E 27,0 576,0 1310,0 16/1000
7×2.5 R E 16,0 168,0 445,0 12/1000
10×2.5 R E 19,0 240,0 610,0 12/1000
12×2.5 R E 19,5 288,0 680,0 12/1000
14×2.5 R E 20,5 336,0 755,0 14/1000
19×2.5 R E 22,5 456,0 950,0 14/1000
24×2.5 R E 26,0 576,0 1173,0 16/1000
30×2.5 R E 27,2 720,0 1398,0 16/1000
40×2.5 R E 30,0 960,0 1778,0 16/1000
Construction data : NAYY  U0/U- 0. 6/ 1k V

Number of cores x No. m ina l

Cross Section

Sh a p e

Overall Diameter (A p p r o x.) Al. weigh t (A p p r o x.)

To ta l Weight

(A p p r o x.)

Pa c kin g: Cable Coil o r Drum
N o x mm²   ma x. mm kg / km kg / km m o r N ° / m
4x 25+1. 5 R M +R E 27, 5 290, 0 1081, 0 12/ 500
4x 35+1. 5 R M +R E 30, 0 406, 0 1293, 5 14/ 500
4x 50+1. 5 S M +R E 31, 0 580, 0 1340, 0 14/ 500
4x 70+1. 5 S M +R E 35, 0 812, 0 1755, 0 16/ 500
4x 95+1. 5 S M +R E 40, 0 1102, 0 2262, 0 16/ 500
4x 120+1. 5 S M +R E 43, 0 1392, 0 2702, 0 16/ 500
4x 150+1. 5 S M +R E 48, 0 1740, 0 3370, 5 18/ 500
4x 185+1. 5 S M +R E 53, 0 2146, 0 4086, 5 20/ 500
4x 240+1. 5 S M +R E 59, 0 2784, 0 5142, 0 22/ 500

NYBY, NAYBY

Power Cable PVC insulated and armoured with two steel tapes

Rated Voltage: U0/U – 0.6/1 kV Standard: IEC 60502-1(DIN VDE 0271)

Application

NYBY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other. These cables are also used as control cables for transmission of measured values control and regulation pulses. These cables are preferentially used for underground application as well as for interior installation in room and cable ducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection an protection against accidental contact is required if damaged. 

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228 Conductor: solid or multi-strand Cu or Al wires
Core temperature, max: 70oC in operation class 1, 2 or 5 acc. VDE 0295(IEC 60228)
Max. short circuit temperature: 160 oC , not more than 5 sec Insulation: PVC acc. to IEC 60502
Rated voltage – U0 /U (Umax): 0.6/1 (1.2) kV Core identification: single core-black, multiple core
Test voltage: AC – 3.5 kV; 50 Hz according to VDE 0293 (HD 308)
Temperature Range   Cores assembly: cores stranded concentrically
Fixed installation: -30°C to +70°C (cores stranded in concentric layers, for signal)
Flexible Installation: -5°C to +50°C Inner sheath: PVC filling compound
Bending radius, min.   Armour:  
single core: 15xDcable for multi-core cable: two steel tapes
multi core: 12xDcable for single-core cable: two Aluminium tapes
Specific insulation resistance at 70°C: min. 1010Ώxcm Sheat: PVC type ST1 acc. IEC 60502

Max. permissible tensile stress with cable grip:

P = D2 · 3 N/mm2

D = Cable diameter (mm)

Color: black
Construction data: NYBY, NA YBY U 0/U – 0.6/1k V

Num ber of cores x Nom inal

Cross S ection

Shape

Overall Diam eter (Approx.) Copper w eight (Approx.)

Total Weight

(Approx.)

Packing: Cable coil or Drum
No x mm²   max.mm kg/km kg/km m or N°/m
NY BY
2  x 1.5 RE 12,4 29,0 270,0 9/1000
2  x 2.5 RE 13,1 48,0 315,0 9/1000
2  x 4 RE 14,9 77,0 390,0 10/1000
2  x 6 RE 15,9 116,0 465,0 12/1000
2×10 RE 17,5 192,0 590,0 12/1000
2×16 RM 19,4 308,0 790,0 12/1000
2×25 RM 24,4 480,0 1215,0 14/1000
 
3  x 1.5 RE 13,0 43,0 280,0 9/1000
3  x 2.5 RE 14,0 72,0 340,0 10/1000
3  x 4 RE 16,0 115,0 440,0 12/1000
3  x 6 RE 17,0 173,0 540,0 12/1000
3  x 10 RE 19,0 288,0 710,0 12/1000
3  x 16 RM 21,0 461,0 970,0 12/1000
 
3×25/16 RM/RE 28,0 874,0 1740,0 12/500
3×35/16 RM/RE 32,0 1162,0 2340,0 14/500
3×50/25 S M/RM 33,0 1680,0 2765,0 14/500
3×70/35 S M/S M 36,0 2352,0 3590,0 14/500
3×95/50 S M/S M 41,0 3216,0 4700,0 16/500
3×120/70 S M/S M 43,0 4128,0 5720,0 16/500
3×150/70 S M/S M 49,0 4992,0 6880,0 18/500
3×185/95 S M/S M 53,0 6240,0 8440,0 20/500
3×240/120 S M/S M 60,0 8064,0 10880,0 22/500
 
4×1.5 RE 14,0 58,0 313,0 10/1000
4×2.5 RE 15,0 96,0 380,0 10/1000
4×4 RE 17,0 154,0 520,0 12/1000
4×6 RE 18,0 230,0 640,0 12/1000
4×10 RE 20,0 384,0 860,0 14/1000
4×16 RM 22,0 614,0 1170,0 14/1000
4×25 RM 28,0 960,0 1810,0 12/500
4×35 RM 32,0 1344,0 2630,0 14/500
4×50 S M 33,0 1920,0 2940,0 14/500
4×70 S M 37,0 2688,0 3860,0 16/500
4×95 S M 42,0 3648,0 5100,0 16/500
4×120 S M 44,0 4608,0 6150,0 16/500
4×150 S M 49,0 5760,0 7510,0 18/500
4×185 S M 53,0 7104,0 9170,0 20/500
 
5×1.5 RE 14,5 72,0 360,0 10/1000
5×2.5 RE 15,5 120,0 436,0 10/1000
5×4 RE 18,0 192,0 600,0 12/1000
5×6 RE 20,0 288,0 750,0 12/1000
NA YBY

Number of cores x Nominal

Cross Section

Shape

Overall Diameter (Approx.) Al weight (Approx.) Total Weight (Approx.) Packing: Cable coil or Drum
No x mm²   max.mm kg/km kg/km m or N°/m
4×25+1.5 RM+RE 28,5 290,0 1233,0 16/1000
4×35+1.5 RM+RE 31,0 406,0 1730,0 18/1000
4×50+1.5 SM+RE 33,0 580,0 1940,0 18/1000
4×70+1.5 SM+RE 37,0 812,0 2310,0 20/1000
4×95+1.5 SM+RE 42,0 1102,0 2970,0 16/500
4×120+1.5 SM+RE 46,0 1392,0 3600,0 18/500
4×150+1.5 SM+RE 50,0 1740,0 4230,0 18/500
4×185+1.5 SM+RE 55,0 2146,0 5010,0 20/500
4×240+1.5 SM+RE 61,0 2784,0 6250,0 24/500

NYCY, NAYCY

Power Cable with concentric copper conductor

Rated Voltage: U0/U – 0.6/1 kV Standard:DIN VDE 0276/HD603 – power ; DIN VDE 0276/HD627 type 4H1 – signal

Application

NYCY, NAYCY is used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other. These cables are preferentially used for underground application as well as for interior installation in room and cable ducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection and protection against accidental contact is required if damaged. 

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228 Conductor:

solid or multi-strand Cu or Al wires

class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Core temperature, max: 70oC in operation
Max. short circuit temperature: 160 oC , not more than 5 sec Insulation: PVC type DIV4 acc. VDE0207
Rated voltage – U0 /U (Umax): 0.6/1(1.2) kV Core identification: according to VDE 0293 (HD 308)
Test voltage: AC – 4 kV; 50 Hz

Cores assembly

cores stranded concentrically

(cores stranded in concentric layers, for signal)

Temperature Range  
Fixed installation: -30°C to +70°C Inner sheath: rubber filling compaund
Flexible Installation: -5°C to +50°C
Concentric copper conductor:

helicoidally copper wires and one

copper tape around inner covering

Bending radius, min. 12xDcable
Specific insulation resistance at 70°C: min, 1010 Ωx cm
Sheat: PVC type DMV5 acc. VDE 0207, black color
max Permessible tensile stress with cable grip:

For Cu conductor = 50 N/mm2

For Al conductor = 30 N/mm2

Construction data: NYCY U0/U – 0.6/1kV

Number of cores x Nominal

Cross Section

Shape

Overall Diameter (Approx.) Copper weight (Approx.) Total Weight (Approx.) Packing: Cable coil or Drum
No x mm²   max.mm kg/km kg/km m or N°/m
2 x 1.5/1.5 RE 14 60,0 245,0 10/1000
2 x 2.5/2.5 RE 14 85,0 285,0 10/1000
2 x 4/4 RE 16,0 125,0 360,0 12/1000
3×1.5/1.5 RE 14,0 80,0 280,0 10/1000
3×2.5/2.5 RE 15,0 109,0 316 10/1000
3×4/4 RE 17,0 155,0 423,0 12/1000
3×6/6 RE 18,0 240,0 530,0 12/1000
3×10/10 RE 20,0 384,0 730,0 12/1000
3×16/16 RE 22,0 610,0 970,0 14/1000
3×25/16 RM 25,0 870,0 1340,0 14/1000
3×35/35 SM 27,0 1340,0 1820,0 16/1000
3×50/50 SM 31,0 1980,0 2490,0 12/500
3×70/70 SM 35,0 2680,0 3350,0 16/500
3×95/95 SM 40,0 3650,0 4490,0 16/500
3×120/120 SM 43,0 4610,0 5500,0 16/500
3×150/150 SM 48,0 5750,0 6950,0 18/500
4×1.5/1.5 RE 15,0 94,0 302,0 10/1000
4×2.5/2.5 RE 16,0 133,0 360,0 12/1000
4×4/4 RE 18,0 195,0 485,0 12/1000
4×6/6 RE 19,0 299,0 616,0 12/1000
4×10/10 RE 21,0 480,0 850,0 14/1000
4×16/16 RE 23,0 766,0 1160,0 14/1000
4×25/16 RM 28,0 1112,0 1630,0 16/1000
4×35/16 SM 30,0 1515,0 2080,0 16/1000
4×50/25 SM 34,0 2156,0 2775,0 14/500
4×70/35 SM 38,0 3070,0 3910,0 16/500
4×95/50 SM 43,0 4200,0 5180,0 16/500
4×120/70 SM 48,0 5275,0 6400,0 18/500
4×150/70 SM 53,0 6690,0 8075,0 20/500
4×185/95 SM 58,0 8030,0 9710,0 22/500
5×1.5/2.5 RE 16,0 109,0 344,0 12/1000
5×2.5/2.5 RE 17,0 158,0 412,0 12/1000
5×4/4 RE 19,0 259,0 560,0 12/1000
5×6/6 RE 20,0 355,0 690,0 12/1000
5×10/10 RE 23,0 575,0 965,0 14/1000
5×16/16 RE 25,0 940,0 1355,0 14/1000
7×1.5/2.5 RE 17,0 141,0 395,0 12/1000
8×1.5/2.5 RE 17,0 155,0 440,0 12/1000
10×1.5/2.5 RE 20,0 188,0 510,0 12/1000
12×1.5/2.5 RE 20,0 223,0 585,0 12/1000
14×1.5/2.5 RE 21,0 253,0 640,0 14/1000
19×1.5/4 RE 23,0 325,0 780,0 14/1000
24×1.5/6 RE 26,0 407,0 950,0 16/1000
30×1.5/6 RE 27,0 494,0 1105,0 16/1000
7×2.5/2.5 RE 18,0 209,0 490,0 12/1000
8×2.5/4 RE 19,0 233,0 550,0 12/1000
10×2.5/4 RE 21,0 291,0 670,0 14/1000
12×2.5/4 RE 22,0 339,0 730,0 14/1000
14×2.5/6 RE 23,0 397,0 825,0 14/1000
19×2.5/6 RE 25,0 516,0 1000,0 14/1000
24×2.5/10 RE 28,0 673,0 1270,0 16/1000
30×2.5/10 RE 30,0 820,0 1495,0 16/1000

NYCWY, NAYCWY

Power Cable with concentric copper conductor

Rated Voltage: U0/U – 0.6/1 kV Standard:DIN VDE 0276/HD603 type 3G-1 – power ; DIN VDE 0276/HD627 – signal

Application

Power cables for energy supply, preferably used for underground laying, especially in subscriber networks, power station as well as control impulses and test data. Overall, where increased electrical and also mechanical protection are required. These cables are installed in open air, in underground, in water, indoors and in cable ducts. The corrugated concentric conductor (CW) is allowed to use as neutral, protective or earth conductor. Simultaneously, this also is permitted to apply as a screen for example earthed-connected protection against contact. Due to the typical construction of corrugated concentric conductors (Ceander), are possible to obtain many more cable joints, without cutting any conductor. In that way the operating reliability is guaranteed. 

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228 Conductor:

solid or multi-strand Cu or Al wires

class 1, 2 or 5 acc. VDE 0295(IEC 60228)

Core temperature, max: 70oC in operation
Max. short circuit temperature: 160 oC , not more than 5 sec Insulation: PVC type DIV4 acc. VDE0207
Core identification: according to VDE 0293 (HD 308)
Rated voltage – U0 /U (Umax): 0.6/1(1.2) kV
Cores assembly:

cores stranded concentrically

(cores stranded in concentric layers, for signal)

Test voltage: AC – 4 kV; 50 Hz
Temperature Range   Inner sheath: rubber filling compaund
Fixed installation: -30°C to +70°C

Concentric copper conductor:

Waveconal outer conductor – copper wires

and contrahelical copper tape (reverse lay copper tape)

Flexible Installation: -5°C to +50°C
Bending radius, min. 12xDcable Sheath: PVC type DMV5 acc. VDE 0207
pecific insulation resistance at 70°C: min, 1010 Ωx cm Color: black

ssible tensile stress with cable grip:

For Cu conductor = 50 N/mm2

For Al conductor = 30 N/mm2

 
Construction data: NYCWY U0/U – 0.6/1kV

Number of cores x Nominal

Cross Section

Shape

Overall Diameter

(Approx.)

Copper

weight (Approx.)

Total Weight (Approx.) Packing: Cable coil or Drum
No x mm²   max.mm kg/km kg/km m or N°/m
3×10/10 RE 20 394,0 775,0 12/1000
3×16/16 RE 22,0 630,0 1066,0 14/1000
3×25/16 RM 26,0 895,0 1584,0 16/1000
3×35/16 SM 28 1190,0 1710,0 16/1000
3×50/25 SM 30,0 1722,0 2368,0 14/500
3×70/35 SM 33,0 2411,0 3174 14/500
3×95/50 SM 38,0 3296,0 4256,0 16/500
3×120/70 SM 41,0 4231,0 5314,0 16/500
3×150/70 SM 45,0 5117,0 6344,0 18/500
3×185/95 SM 50,0 6396,0 8054,0 20/500
3×240/120 SM 56,0 8265,0 10274,0 22/500
 
4×10/10 RE 21,0 492,0 897,0 14/1000
4×16/16 RE 24,0 787,0 1250,0 14/1000
4×25/16 RM 28,0 1141,0 1822,0 16/1000
4×35/16 SM 29,0 1535,0 2140,0 16/1000
4×50/25 SM 33,0 2214,0 3031,0 14/500
4×70/35 SM 38,0 3100,0 4056,0 16/500
4×95/50 SM 43,0 4231,0 5364,0 16/500
4×120/70 SM 46,0 5412,0 6748,0 18/500
4×150/70 SM 51,0 6592,0 8159,0 20/500
4×185/95 SM 57,0 8216,0 10198,0 22/500

NYRY, NAYRY

Power Cable PVC insulation armored with steel wire armour

Rated Voltage: U0/U – 0.6/1 kV Standard: IEC 60502-1; DIN VDE 0271 (acc. to BS 6346)

Application

These cables are used in power plants, industrial and switching installations, for street lighting, domestic power supply connections, in secondary distribution networks and other.These cables are preferentially used for underground application as well as for interior installation in room and cableducts and for outdoor and applications, for indoor installations, in the open air, underground and in wet ambient where greater mechanical protection an protection against accidental contact is required if damaged. 

Construct io n d a t a : N Y R Y U 0/ U –  0. 6/ 1k V

Nu m b e r of c o r e s x Nom in a l

C r os s S e c t ion

Sha p e

Ov e r a ll

D iam et er ( A p p r o x . )

C o ppe r w e ight (A p p r o x . )

To ta l W e ig h t

( A ppr o x .)

Pa c kin g: C a ble c o il or D r u m
N o x mm²   ma x . mm kg / km kg / km m o r N °/ m
NY R ( A L) Y – a r m ou r w it h a lu m in iu m r oou n d w ir e s
1x 10 R E 14,4 96,0 326,0 1 0/ 1000
1x 16 R E 15,4 154,0 402,0 1 0/ 1000
1x 25 R M 17,2 240,0 541,0 1 2/ 1000
1x 35 R M 18,3 336,0 658,0 1 2/ 1000
1x 50 R M 20,5 480,0 841,0 1 2/ 1000
1x 70 R M 22,5 672,0 1070,0 1 4/ 1000
1x 95 R M 24,5 912,0 1365,0 1 4/ 1000
1x 120 R M 26,5 1152,0 1 662,0 16/ 1000
1x 150 R M 28,5 1440,0 1 967,0 16/ 1000
1x 185 R M 31,0 1776,0 2 406,0 18/ 1000
1x 240 R M 34,0 2304,0 3 071,0 18/ 1000
1x 300 R M 38,0 2880,0 3 781,0 16/ 500
1x 400 R M 42,0 3840,0 4 764,0 16/ 500
1x 500 R M 46,5 4800,0 5 968,0 18/ 500
1x 630 R M 51,0 6048,0 7 538,0 20/ 500
N Y R Y – a r m o u r w it h g a lv a n iz e d s t e ll w ir e s
2x 1.5 R E 1 4,0 2 8,8 3 47,0 10/ 1000
2x 2.5 R E 1 5,0 4 8,0 4 03,0 10/ 1000
2x 4.0 R E 1 6,9 7 6,8 5 16,0 12/ 1000
2x 6.0 R E 1 8,8 115,2 701,0 1 2/ 1000
2x 10 R E 21,0 192,0 874,0 1 4/ 1000
2x 16 R E 23,0 308,0 1082,0 1 4/ 1000
2x 25 R M 27,0 480,0 1565,0 1 6/ 1000
2x 35 R M 29,0 672,0 1893,0 1 6/ 1000
2x 50 R M 32,5 960,0 2293,0 1 8/ 1000
2x 70 R M 37,0 1344,0 3 150,0 16/ 500
2x 95 R M 42,0 1824,0 4 037,0 16/ 500
2x 120 R M 45,0 2304,0 4 725,0 18/ 500
2x 150 R M 50,5 2880,0 6 041,0 20/ 500
2x 185 R M 55,5 3552,0 7 253,0 22/ 500
NYRY – a r m o u r w it h g a lv a n iz e d s t e ll w ir e s
3x 1.5 R E 1 4,5 4 3,2 3 82,0 10/ 1000
3x 2.5 R E 1 5,5 7 2,0 4 48,0 10/ 1000
3x 4.0 R E 1 8,4 115,2 678,0 1 2/ 1000
3x 6.0 R E 1 9,6 172,8 783,0 1 2/ 1000
3x 10 R E 22,0 288,0 1006,0 1 4/ 1000
3x 16 R E 24,0 462,0 1276,0 1 4/ 1000
3x 25 R M 28,0 720,0 1863,0 1 6/ 1000
3x 35 R M 30,5 1008,0 2 279,0 14/ 500
3x 50 S M 33,5 1440,0 2 644,0 14/ 500
3x 70 S M 38,5 2016,0 3 664,0 16/ 500
3x 95 S M 42,5 2736,0 4 661,0 16/ 500
3x 120 S M 45,5 3456,0 5 478,0 18/ 500
3x 150 S M 51,5 4320,0 7 040,0 20/ 500
3x 185 S M 56,5 5328,0 8 457,0 22/ 500
3x 240 S M 62,5 6912,0 10579,0 24/ 500
3x 300 S M 68,0 8640,0 12683,0 24/ 500
NYRY- a r m o u r w it h g a lv a n iz e d s t e ll w ir e s
4x 1.5 R E 1 5,4 5 7,6 4 25,0 10/ 1000
4x 2.5 R E 1 6,5 9 6,0 5 09,0 12/ 1000
4x 4.0 R E 1 9,6 153,6 767,0 1 2/ 1000
4x 6.0 R E 2 1,0 230,4 904,0 1 4/ 1000
4x 10 R E 23,5 384,0 1179,0 1 4/ 1000
4x 16 R E 27,0 616,0 1657,0 1 6/ 1000
4x 25 R M 30,5 960,0 2236,0 1 6/ 1000
4x 35 R M 33,5 1344,0 2 768,0 14/ 500
4x 50 S M 40,0 1920,0 3639,0 16/ 500
4x 70 S M 43,0 2688,0 4592,0 16/ 500
4x 95 S M 50,0 3648,0 6338,0 20/ 500
4x 120 S M 54,0 4608,0 7547,0 20/ 500
4x 150 S M 60,5 5760,0 9073,0 24/ 500
4x 185 S M 65,0 7104,0 10835,0 24/ 500
4x 240 S M 72,0 9216,0 13543,0 24/ 450
4x 300 S M 78,0 11520,0 16333,0 24/ 400

NY2Y, NAY2Y

Power Cable PVC insulation and PE sheath Rated Voltage: U0/U – 0.6/1 kV

Standard:DIN VDE 0276/HD603; IEC 60502-1

Application

Power cable suitable for laying in air, soil, water, concrete, in enclosed locations, cable ducts, in Power Plants, Industrial Applications, City Power Grids where mechanical damages are not expected and cables are not exposed to excessive pulling. 

Construction data: NAY2Y U0/U – 0.6/1kV
Nominal Cross Section

Shape

Overall Diameter (Approx.) Al weight (Approx.) Total Weight (Approx.) Packing: Cable coil or Drum
No x mm²   max.mm kg/km kg/km m or N°/m
with signal wire – 2.5 mm2.
4×16+2,5 RM+RE 23,0 186,0 665,0 14/1000
4×25+2,5 RM+RE 27,0 290,0 1325,0 16/1000
4×35+2,5 RM+RE 29,0 406,0 1164,0 16/1000
4×50+2,5 SM+RE 32,0 580,0 1290,0 18/1000
4×70+2,5 SM+RE 36,0 812,0 1740,0 16/500
4×95+2,5 SM+RE 40,0 1102,0 2220 16/500
4×120+2,5 SM+RE 44,0 1392,0 2700,0 18/500
4×150+2,5 SM+RE 49,0 1740,0 3315,0 20/500
4×185+2,5 SM+RE 54,0 2146,0 3960,0 20/500
4×240+2,5 SM+RE 61,0 2784,0 5065,0 24/500
without signal wire
4×16 RM 23,0 186,0 645,0 14/1000
4×25 RM 27,0 290,0 1295,0 16/1000
4×35 RM 29,0 406,0 1132,0 16/1000
4×50 SM 32,0 580,0 1270,0 18/1000
4×70 SM 36,0 812,0 1720,0 16/500
4×95 SM 40,0 1102,0 2190,0 16/500
4×120 SM 44,0 1392,0 2665,0 18/500
4×150 SM 49,0 1740,0 3295,0 20/500
4×185 SM 54,0 2146,0 3930,0 20/500
4×240 SM 61,0 2784,0 5035,0 24/500

N2XY, NA2XY, N2X2Y, NA2X2Y

Power cable with XLPE insulation and PVC or PE sheath

Rated Voltage: U0/U – 0.6/1 kV Standard: VDE 0276/HD603 tip 5G-2; IEC 60502-1

Application

The power cables with insulation of cross-linked polyethylene (XLPE) are designed for distribution and supply of consumers with nominal voltage 0.6/1 kV and frequency 50 Hz in industrial installations and urban networks. They are suitable for fixed indoor assembly in cable ducts and conduits, over shelves and grilles, directly underground in ditch and outdoor under shelters providing the conditions determined for the type of cable. 

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228

Conductor:

solid or multi-strand Cu or Al wires

class 1, 2 or (5) acc. VDE 0295 (IEC 60228)

Core temperature, max: 90oC in operation
Max. short circuit temperature: 250 oC , not more than 5 sec Insulation: XLPE type DIX3 acc. to VDE 0276-603/5G
Rated voltage U0 /U(Umax): 0.6/1(1.2) kV Core identification: according to VDE 0293 (HD 308)
Test voltage: AC – 4 kV (3.5kV by IEC); 50 Hz

Signal-command copper core:

Additional, cross section 2,5mm2,

red coloured (black coloured 1,5mm2 on request)

Temperature range:  
flexing: -5°C to +50°C
stationary: -30°C to +90°C

Cores assembly:

cores stranded concentrically

(cores stranded in concentric layers, for signal)

Bending radius, min.  
for single-core: 15xDcable Wrapping: paper tape
for multi-core: 12xDcable Inner covering: rubber filling compound
Specific insulation resistance at 90°C: min, 1014 Ωx cm

Sheath:

PVC type DMV6 acc. to VDE 0276-603/sec.1 or

PE HDPE mass, type DMP2 acc. DIN VDE 0276/HD603

Max. permessible tensile stress with cable grip:

For Cu conducor = 50 N/mm2 For Al conducor = 30 N/mm2
Color of sheath: black
Construction  data: N2XY U 0 / U – 0 . 6 / 1 k V

N u m b e r  o f  c o r e s  x  N o m in a l

C r o s s S e c t io n

S h a p e

O v e r a l l D ia m e t e r (A p p r o x . )

C o p p e r ( o r A  l) w e ig h t

(A p p r o x . )

T o t a l  W e ig h t

( A p p r o x . )

P a c k in g : C a b le c o i l o r D r u m
N o x m m ²   m a x . m m k g / k m k g / k m m o r N ° / m
1 x 4 R E 6 , 5 3 8 , 0 7 4 , 0 1 0 0
1 x 6 R E 7 , 0 5 8 , 0 9 6 , 0 1 0 0
1 x 1 0 R E 8 , 0 9 6 , 0 1 4 2 , 0 1 0 0
1 x 1 6 R E 9 , 0 1 5 4 , 0 2 0 5 , 0 8 / 1 0 0 0
1 x 2 5 R M 1 1 , 0 2 4 0 , 0 3 0 2 , 0 9 / 1 0 0 0
1 x 3 5 R M 1 2 , 0 3 3 6 , 0 4 0 0 9 / 1 0 0 0
1 x 5 0 R M 1 3 , 0 4 8 0 , 0 5 2 6 , 0 9 / 1 0 0 0
1 x 7 0 R M 1 6 , 0 6 7 2 , 0 7 5 0 , 0 1 2 / 1 0 0 0
1 x 9 5 R M 1 7 , 0 9 1 2 , 0 1 0 0 0 , 0 1 2 / 1 0 0 0
1 x 1 2 0 R M 1 8 , 5 1 1 5 0 , 0 1 2 4 0 , 0 1 2 / 1 0 0 0
1 x 1 5 0 R M 2 1 , 0 1 4 4 0 , 0 1 5 5 0 , 0 1 4 / 1 0 0 0
1 x 1 8 5 R M 2 3 , 0 1 7 7 6 , 0 1 8 9 0 , 0 1 4 / 1 0 0 0
1 x 2 4 0 R M 2 6 , 0 2 3 0 4 , 0 2 4 3 0 , 0 1 6 / 1 0 0 0
1 x 3 0 0 R M 2 8 , 0 2 8 8 0 , 0 3 0 1 5 , 0 1 6 / 1 0 0 0
 
3 x 1 . 5 R E 1 0 , 0 4 3 , 0 1 4 2 , 0 8 / 1 0 0 0
3 x 2 . 5 R E 1 1 , 0 7 2 , 0 1 8 3 , 0 9 / 1 0 0 0
3 x 4 R E 1 2 , 0 1 1 5 , 0 2 4 2 , 0 9 / 1 0 0 0
3 x 6 R E 1 3 , 0 1 7 3 , 0 3 2 0 , 0 9 / 1 0 0 0
3 x 1 0 R E 1 5 , 0 2 8 8 , 0 4 8 0 , 0 1 0 / 1 0 0 0
3 x 1 6 R E 1 7 , 0 4 6 1 , 0 7 0 0 , 0 1 2 / 1 0 0 0
 
3 x 2 5 / 1 6 R M / R M 2 1 , 0 8 7 4 , 0 1 2 3 0 , 0 1 4 / 1 0 0 0
3 x 3 5 / 1 6 S M / R M 2 6 , 0 1 1 6 2 , 0 1 4 5 0 , 0 1 6 / 1 0 0 0
3 x 5 0 / 2 5 S M / R M 2 9 1 6 8 0 , 0 1 9 5 5 , 0 1 4 / 5 0 0
3 x 7 0 / 3 5 S M / S M 3 1 , 0 2 3 5 2 , 0 2 7 2 0 , 0 1 4 / 5 0 0
3 x 9 5 / 5 0 S M / S M 3 7 , 0 3 2 1 6 , 0 3 7 5 6 , 0 1 6 / 5 0 0
 
4 x 1 . 5 R E 1 1 , 0 5 8 , 0 1 6 5 , 0 9 / 1 0 0 0
4 x 2 . 5 R E 1 2 , 0 9 6 , 0 2 1 6 , 0 9 / 1 0 0 0
4 x 4 R E 1 3 , 0 1 5 4 , 0 2 9 0 , 0 9 / 1 0 0 0
4 x 6 R E 1 4 , 0 2 3 0 , 0 3 8 5 , 0 1 0 / 1 0 0 0
4 x 1 0 R E 1 6 , 0 3 8 4 , 0 5 9 0 , 0 1 2 / 1 0 0 0
4 x 1 6 R E 1 9 , 0 6 1 4 , 0 8 6 4 , 0 1 2 / 1 0 0 0
4 x 2 5 R M 2 2 9 6 0 , 0 1 2 9 3 , 0 1 4 / 1 0 0 0
4 x 3 5 S M 2 7 , 0 1 3 4 4 , 0 1 7 5 0 , 0 1 6 / 1 0 0 0
4 x 5 0 S M 3 0 , 0 1 9 2 0 , 0 2 3 0 0 , 0 1 4 / 5 0 0
4 x 7 0 S M 3 4 , 0 2 6 8 8 , 0 3 2 8 0 , 0 1 4 / 5 0 0
4 x 9 5 S M 3 8 , 0 3 6 4 8 , 0 4 3 0 0 , 0 1 6 / 5 0 0
4 x 1 2 0 S M 4 3 , 0 4 6 0 8 , 0 5 4 1 6 , 0 1 6 / 5 0 0
4 x 1 5 0 S M 4 7 , 0 5 7 6 0 , 0 6 7 0 0 , 0 1 8 / 5 0 0
4 x 1 8 5 S M 5 2 , 0 7 1 0 4 , 0 8 2 0 0 , 0 2 0 / 5 0 0
4 x 2 4 0 S M 5 8 , 0 9 2 1 0 , 0 1 0 5 6 0 , 0 2 2 / 5 0 0
 
5 x 1 . 5 R E 1 2 , 0 7 2 , 0 1 9 3 , 0 9 / 1 0 0 0
5 x 2 . 5 R E 1 2 , 5 1 2 0 , 0 2 5 2 , 0 9 / 1 0 0 0
5 x 4 R E 1 4 , 0 1 9 2 , 0 3 4 0 , 0 1 0 / 1 0 0 0
5 x 6 R E 1 5 , 0 2 8 8 , 0 4 6 0 , 0 1 0 / 1 0 0 0
5 x 1 0 R E 1 8 , 0 4 8 0 , 0 8 4 0 , 0 1 2 / 1 0 0 0
5 x 1 6 R E 2 1 , 0 7 6 8 , 0 1 0 4 0 , 0 1 4 / 1 0 0 0
5 x 2 5 R M 2 5 , 0 1 2 0 0 , 0 1 5 6 0 , 0 1 4 / 1 0 0 0
Construction  data:NA2XY 0.6/1 KV
4 x 1 6 + 1 . 5 R E + R E 2   1   , 0 1   8   6   , 0 5   9   6   , 0 1 4 / 1 0 0 0   
4 x 2 5 + 1 . 5 R M + R E 2  4    2   9   0   , 0 8   2   0   , 0 1 4 / 1 0 0 0   
4 x 3 5 + 1 . 5 R M + R E 2   7   , 0 4   0   6   , 0 1 0 3 3 , 0 1 6 / 1 0 0 0   
4 x 5 0 + 1 . 5 S M + R E 3   0   , 0 5   8   0   , 0 1 1 3 7 , 0 1 4 / 5 0 0   
4 x 7 0 + 1 . 5 S M + R E 3   5   , 0 8   1   2   , 0 1 5 6 8 , 0 1 6 / 5 0 0   
4 x 9 5 + 1 . 5 S M + R E 3   9   , 0 1 1 0 2 , 0 1 9 4 6 , 0 1 6 / 5 0 0   
4 x 1 2 0 + 1 . 5 S M + R E 4   3   , 0 1 3 9 2 , 0 2   4   3  6    1 6 / 5 0 0   
4 x 1 5 0 + 1 . 5 S M + R E 4   7   , 0 1 7 4 0 , 0 2 9 7 3 , 0 1 8 / 5 0 0   
4 x 1 8 5 + 1 . 5 S M + R E 5   2   , 0 2 1 4 6 , 0 3 5 9 2 , 0 2 0 / 5 0 0   
4 x 2 4 0 + 1 . 5 S M + R E 5   8   , 0 2 7 8 4 , 0 4 5 7 3 , 0 2 2 / 5 0 0   
4   x   1  6    R   E 2   1   , 0 1   8   6   , 0 5   7   0   , 0 1 4 / 1 0 0 0   
4   x   2  5    R   M 2  4    2   9   0   , 0 7   9   4   , 0 1 4 / 1 0 0 0   
4   x   3  5    S  M 2   7   , 0 4   0   6   , 0 8   7   4   , 0 1 6 / 1 0 0 0   
4   x   5  0    S  M 3   0   , 0 5   8   0   , 0 1 1 1 0 , 0 1 4 / 5 0 0   
4   x   7  0    S  M 3   5   , 0 8   1   2   , 0 1 5 4 0 , 0 1 6 / 5 0 0   
4   x   9  5    S  M 3   9   , 0 1 1 0 2 , 0 1 9 2 0 , 0 1 6 / 5 0 0   
4 x 1 2 0    S  M 4   3   , 0 1 3 9 2 , 0 2 4 1 0 , 0 1 6 / 5 0 0   
4 x 1 5 0    S  M 4   7   , 0 1 7 4 0 , 0 2 9 4 6 , 0 1 8 / 5 0 0   
4 x 1 8 5    S  M 5   2   , 0 2 1 4 6 , 0 3 5 6 5 , 0 2 0 / 5 0 0   
4 x 2 4 0    S  M 5   8   , 0 2 7 8 4 , 0 4 5 4 5 , 0 2 2 / 5 0 0   

N2XYRY, NA2XYRY Power cable with XLPE insulation, steel wire armor, PVC sheath

C o ns t r uc t i o n  d a t a :  N 2X Y R Y U 0/ U  –  0. 6/ 1k V
Nu m b e r o f c o r e s x  No m in a l C r os s S e c t ion Sha p e

O v e r a ll

D iam et er ( A p p r o x . )

C o ppe r w e ight ( A ppr o x . )

To t a l

W e ig ht ( A ppr o x . )

Pa c k in g: C a ble c o il o r D r u m
N o  x  mm²   ma x . mm k g / k m k g / k m m  o r N ° / m
N 2 X Y R ( A L ) Y – a r m o ur w it h a lum inium r o o und w ir e s
1x 50 R M 17, 5 480, 0 742, 0 12/ 1000
1x 70 R M 19, 0 672, 0 975, 0 12/ 1000
1x 95 R M 21, 0 912, 0 1277, 0 14/ 1000
1x 120 R M 23, 0 1152, 0 1547, 0 14/ 1000
1x 150 R M 24, 5 1440, 0 1860, 0 14/ 1000
1x 185 R M 26, 2 1776, 0 2268, 0 16/ 1000
1x 240 R M 30, 0 2304, 0 2952, 0 16/ 1000
1x 300 R M 32, 3 2880, 0 3434, 0 18/ 1000
1x 400 R M 37, 0 3840, 0 4738, 0 20/ 1000
N 2 X Y R Y –   a r m o u r w it h  g a lv a n iz e d  s t e ll w ir e s
2x 1. 5 R E 13, 0 28, 8 397, 0 9/ 1000
2x 2. 5 R E 14, 0 48, 0 455, 0 10/ 1000
2x 4. 0 R E 14, 5 76, 8 524, 0 10/ 1000
2x 6. 0 R E 17, 5 115, 2 715, 0 12/ 1000
2x 10 R E 18, 5 192, 0 869, 0 12/ 1000
2x 16 R E 20, 5 307, 0 1102, 0 12/ 1000
2x 25 R M 24, 5 480, 0 1637, 0 14/ 1000
N 2 X Y R Y –   a r m o u r w it h  g a lv a n iz e d  s t e ll w ir e s
3x 1. 5 R E 13, 5 43, 2 429, 0 10/ 1000
3x 2. 5 R E 14, 5 72, 0 498, 0 10/ 1000
3x 4. 0 R E 15, 5 115, 2 583, 0 10/ 1000
3x 6. 0 R E 18, 0 172, 8 800, 0 12/ 1000
3x 10 R E 19, 5 288, 0 996, 0 12/ 1000
3x 16 R E 21, 5 460, 0 1287, 0 14/ 1000
3x 25 R M 25, 5 720, 0 1918, 0 14/ 1000
3x 35 R M 30, 0 1008, 0 2602, 0 14/ 500
3x 50 S M 31, 0 1440, 0 2771, 0 14/ 500
3x 70 S M 35, 0 2016, 0 3826, 0 16/ 500
3x 95 S M 38, 5 2736, 0 4849, 0 16/ 500
3x 120 S M 42, 5 3456, 0 6158, 0 16/ 500
3x 150 S M 47, 0 4320, 0 7356, 0 18/ 500
3x 185 S M 51, 5 5328, 0 8914, 0 20/ 500
3x 240 S M 57, 0 6912, 0 11082, 0 22/ 500
3x 300 S M 62, 5 11520, 0 13366, 0 24/ 500
N 2 X Y R Y –   a r m o u r w it h  g a lv a n iz e d  s t e ll w ir e s
3x 25+ 16 R M / R M 26, 5 873, 0 2135, 0 16/ 1000
3x 35+ 16 R M / R M 31, 0 1161, 0 2793, 0 14/ 500
3x 50+ 25 S M / R M 35, 5 1680, 0 3492, 0 16/ 500
3x 70+ 35 S M / S M 38, 5 2352, 0 4414, 0 16/ 500
3x 95+ 50 S M / S M 44, 0 3216, 0 6063, 0 18/ 500
3x 120+ 70 S M / S M 48, 0 4128, 0 7298, 0 18/ 500
3x 150+ 70 S M / S M 53, 0 4992, 0 8586, 0 22/ 500
3x 185+ 95 S M / S M 58, 0 6240, 0 10409, 0 24/ 500
3x 240+ 120 S M / S M 65, 5 8064, 0 12960, 0 24/ 500
3x 300+ 150 S M / S M 71, 5 12960, 0 15497, 0 24/ 450
N 2 X Y R Y –   a r m o u r w it h  g a lv a n iz e d  s t e ll w ir e s
4x 1. 5 R E 14, 0 57, 6 466, 0 10/ 1000
4x 2. 5 R E 15, 0 96, 0 556, 0 10/ 1000
4x 4. 0 R E 16, 0 153, 6 657, 0 12/ 1000
4x 6. 0 R E 19, 0 230, 4 906, 0 12/ 1000
4x 10 R E 21, 0 384, 0 1160, 0 14/ 1000
4x 16 R E 23, 5 614, 0 1669, 0 14/ 1000
4x 25 R M 27, 5 960, 0 2289, 0 16/ 1000
4x 35 R M 33, 0 1344, 0 3153, 0 14/ 500
4x 50 S M 35, 5 1920, 0 3725, 0 16/ 500
4x 70 S M 38, 5 2688, 0 4759, 0 16/ 500
4x 95 S M 44, 0 3648, 0 6550, 0 18/ 500
4x 120 S M 48, 0 4608, 0 7817, 0 18/ 500
4x 150 S M 53, 0 5760, 0 9386, 0 20/ 500
4x 185 S M 58, 0 7104, 0 11342, 0 22/ 500
4x 240 S M 65, 5 9216, 0 14230, 0 24/ 500
4x 300 S M 74, 0 11520, 0 18205, 0 24/ 450

2XSY, NA2XSY, N2XS2Y, NA2XS2Y

Cu or Al single-core cables with insulation XLPE and PVC or PE sheath

Rated Voltage: U0/U – 3.6/6; 6/10; 8.7/15; 12/20; 18/30; 20/35; 20.8/36kV; Standard:VDE 0276/HD620.S2; IEC 60502-2

Application

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes.

Technical Data: Cable Structure:
Conductor resistance at 20oC: according to VDE 0295 and IEC 60228 class 2

Conductor:

Cu or Al stranded compacted,

according to IEC 60228 and VDE 0295 class 2

Core temperature, max: 90 °C in continuous operation
Max. short circuit temperature: 250 oC , not more than 5 sec
Inner semi-conductive layer: semi-conductive XLPE compound around conductor
Overload temperature: 130oC /100h per year max.

Highest system voltage, Umax

3.6/6 kV = max. 7.2 kV 6/10 kV = max. 12 kV 8.7/15 kV = max. 17.5 kV 12/20 kV = max. 24 kV 18/30 kV = max. 36 kV 20/35 kV = max. 42kV 20.8/36 kV = max. 42 kV Insulation: XLPE compoundDIX8 as per DIN VDE 0276-620 part 1.
Outer semi-conductive layer: semi-conductive XLPE compound around insulation
Warapping: Semi-conductive tape helicoidally wrapped
Metal screen:

Cu wires concentrically laid and one

contact of Cu tape with min. thickness of 0.1mm.

Optional metal screen: overlapping one or two Cu tapes

Test voltage = 3.5Uo(IEC60502-2); 3.5Uo(VDE 0276/HD620)

AC (50Hz) – 5 min

3.6/6 kV = 12.6 kV

6/10 kV = 21kV

8.7/15 kV = 30.45 kV

12/20 kV =  42 kV

18/30 kV =  63 kV

20/35 kV = 70kV

20.8/36 kV = 72.8 kV

PE Sheath:

PE compound type ST7 according to IEC 60502-2

type DMP 2 according to VDE 0276, black color

PVC Sheath: PVC mass type DMV6, red (or black) coloured
 
Available constructions:
Single Al core: 1x(25 – 630)mm2
Single Cu core: 1x(25 – 500)mm2
Level of partial discharge at 2*Uo: no more than 2pC Standard Cross section of metallic screen for conductor sizes:  
Bending radius, min 15xDcable from 25mm2 to 120 mm2 16mm2
Temperature of laying: no less than – 5 oC
from 150mm2 to 300mm2 25mm2
Dielectric factor of losses, 50 Hz: at 20°C, (0.8-3)x10-4
Spec.volume insulation resistance at 20°C, min 1015 Ωx cm from 400mm2 to 630mm2 35mm2
Intensity of electric field: max. 6.9-5.3 kV/mm

Standard shape of conductor

RM – class 2 conductor acc. to IEC 60228 and VDE 0295

On Request:

Tests:

according to IEC 60502-2 or

DIN VDE 0276-620

Force of strain in laying, N max.

Al cores – 30*S Cu cores – 50*S

where: S is cross section of cores in mm2

Construction data: N2XSY, NA2XSY
Number of cores x Nominal Cross Section Nominal insulation thickness Nominal sheath thickness Overall Diameter (Approx.) Copper weight (Approx.) Al weight (Approx.) Total Weight (Approx.) Packing: Cable coil or Drum
No x mm² mm mm max.mm kg/km kg/km kg/km m or N°/m
N2XSY 6/10kV
1x25RM/16 3.4 2.5 22.4 408 – 800 14/1000
1x35RM/16 3.4 2.5 24.4 518 – 960 14/1000
1x50RM/16 3.4 2.5 25 662 – 1160 14/1000
1x70RM/16 3.4 2.5 27 854 – 1360 16/1000
1x95RM/16 3.4 2.5 28.2 1094 – 1600 16/1000
1x120RM/16 3.4 2.5 29.5 1334 – 1870 16/1000
1x150RM/25 3.4 2.5 31.1 1723 – 2270 16/1000
1x185RM/25 3.4 2.5 32.6 2059 – 2640 18/1000
1x240RM/25 3.4 2.5 35.4 2587 – 3210 20/1000
1x300RM/25 3.4 2.5 37.1 3163 – 3800 20/1000
NA2XSY 6/10kV
1x35RM/16 3.4 2.5 24.4 182 101 700 14/1000
1x50RM/16 3.4 2.5 25 182 145 780 16/1000
1x70RM/16 3.4 2.5 27 182 203 890 16/1000
1x95RM/16 3.4 2.5 28.2 182 276 990 18/1000
1x120RM/16 3.4 2.5 29.5 182 348 1100 9/1000
1x150RM/25 3.4 2.5 31.1 283 435 1300 9/1000
1x185RM/25 3.4 2.5 32.6 283 537 1440 10/1000
1x240RM/25 3.4 2.5 35.4 283 696 1680 12/1000
1x300RM/25 3.4 2.5 37.1 283 870 1890 12/1000
N2XSY 12/20kV
1x35RM/16 5.5 2.5 27.8 518 – 1100 16/1000
1x50RM/16 5.5 2.5 29.3 662 – 1290 16/1000
1x70RM/16 5.5 2.5 31.2 854 – 1540 18/1000
1x95RM/16 5.5 2.5 32.5 1094 – 1810 18/1000
1x120RM/16 5.5 2.5 33.7 1334 – 2080 18/1000
1x150RM/25 5.5 2.5 35.4 1723 – 2500 20/1000
1x185RM/25 5.5 2.5 37 2059 – 2870 20/1000
1x240RM/25 5.5 2.5 40 2587 – 3470 20/1000
1x300RM/25 5.5 2.5 41.3 3163 – 4080 22/1000
NA2XSY 12/20kV
1x35RM/16 5.5 2.5 27.8 182 101 880 16/1000
1x50RM/16 5.5 2.5 29.3 182 145 970 16/1000
1x70RM/16 5.5 2.5 31.2 182 203 1090 18/1000
1x95RM/16 5.5 2.5 32.5 182 276 1200 18/1000
1x120RM/16 5.5 2.5 33.7 182 348 1310 18/1000
1x150RM/25 5.5 2.5 35.4 283 435 1530 20/1000
1x185RM/25 5.5 2.5 37 283 537 1680 20/1000
1x240RM/25 5.5 2.5 40 283 696 1920 20/1000
1x300RM/25 5.5 2.5 41.3 283 870 2150 22/1000
N2XSY 20/35kV
1x35RM/16 9.0 2.5 34.8 518 – 1460 20/1000
1x50RM/16 9.0 2.5 36.4 662 – 1660 20/1000
1x70RM/16 9.0 2.5 38.2 854 – 1930 20/1000
1x95RM/16 9.0 2.5 39.5 1094 – 2220 22/1000
1x120RM/16 9.0 2.5 40.7 1334 – 2500 22/1000
1x150RM/25 9.0 2.5 42.4 1723 – 2930 24/1000
1x185RM/25 9.0 2.5 43.9 2059 – 3310 24/1000
1x240RM/25 9.0 2.5 46.7 2587 – 3950 18/500
1x300RM/25 9.0 2.5 48.3 3163 – 4580 20/500
NA2XSY 20/35kV
1x35RM/16 9.0 2.5 34.8 182 101 1230 20/1000
1x50RM/16 9.0 2.5 36.4 182 145 1340 20/1000
1x70RM/16 9.0 2.5 38.2 182 203 1480 20/1000
1x95RM/16 9.0 2.5 39.5 182 276 1610 22/1000
1x120RM/16 9.0 2.5 40.7 182 348 1730 22/1000

N2XSEY, NA2XSEY, N2XSE2Y, NA2XSE2Y

Cu or Al triple-core cables with insulation XLPE and PVC or PE sheath Rated Voltage: U0/U – 3.6/6; 6/10; 8.7/15; 12/20; 18/30; 20/35; 20.8/36kV;

Standard:VDE 0276/HD620.S2; IEC 60502-2 

C onstruction da ta : N 2XSEY , NA 2XSEY
Number of cores x Nominal Cross S ection Nom inal insulation thickness Nom inal sheath thickness

Overall

Diam eter (Approx.)

Cu w eight (Approx.) Al w eight (Approx.)

Total

W eight (Approx.)

Packing: Cable coil or Drum
No x mm² mm mm max.mm kg/km kg/km kg/km m or N°/m
N2X S EY 6/10kV
3x50RM /16 3.4 2.5 48 1774 – 3650 24/1000
3x70RM /16 3.4 2.7 53 2380 – 4640 20/500
3x95RM /16 3.4 2.8 57 3132 – 5580 22/500
3x120RM /16 3.4 2.9 60 3877 – 6540 24/500
3x150RM /25 3.4 3.0 63 4768 – 7720 24/500
3x185RM /25 3.4 3.2 67 5808 – 9040 24/500
3x240RM /25 3.4 3.4 74 7424 – 11290 22/250
3x300RM /25 3.4 3.4 77 9203 – 13340 24/250
NA 2X S EY 6/10kV
3x50RM /16 3.4 2.5 48 297 435 2680 24/1000
3x70RM /16 3.4 2.7 53 330 609 3270 20/500
3x95RM /16 3.4 2.8 57 357 827 3730 22/500
3x120RM /16 3.4 2.9 60 378 1044 4200 24/500
3x150RM /25 3.4 3.0 63 406 1305 4840 24/500
3x185RM /25 3.4 3.2 67 428 1610 5440 24/500
3x240RM /25 3.4 3.4 74 474 2038 6550 22/250
3x300RM /25 3.4 3.4 77 502 2610 7500 24/250

Applicable Standards

IEC 60228IEC 60502-1IEC 60502BS 6346IEC 60502-2

Certificate Display

ISO 9001 Quality Management System
ISO 9001 Certificate (2025–2028)
ISO 9001 Certificate (NOA)
CE — Verification of Conformity
RoHS Compliance Attestation (EU)
Low Voltage Directive Attestation (EU)

Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.

Factory Tour

Why Choose Us

50+ years of experience Trusted manufacturing expertise since 1969
International standards IEC, ASTM, BS, CSA and other global standards
Strict quality control Comprehensive testing throughout production
Large production capacity Reliable supply for utility and EPC projects
Fast global delivery Efficient manufacturing and worldwide shipping
Technical support Expert assistance from inquiry to project completion

Packing & Shipping

  • Wooden, steel or steel-wood drums; drum length to customer requirement
  • Drum marking per customer / utility specification
  • Both drum ends sealed and protected for sea freight
Get in touch

Ready for Your Next Cable Project?

Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.

  • Emailinfo@qzcablegroup.com
  • WhatsApp / WeChat+86 173 3570 4553
  • Contact personChloe · Export Department
  • Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China

    The more specific the standard and size, the faster we can quote.
    Inquiry WhatsApp Email