Medium Voltage Cables to BS 6622BS 7835
Medium Voltage Cables to BS 6622/BS 7835
- Standards: BS 6622/BS · BS7835 · BS6622
Product Description
Medium Voltage Cables to BS 6622/BS 7835
British Standard BS7835 specifies requirements for single-core and three-core armoured cables with thermosetting insulation – 3.8/6.6kV up to 19/33kV. They are designed to produce low levels of smoke and corrosive gases on exposure to fire compared to the cables specified in British Standard BS6622.
Medium Voltage Cables to BS 6622/BS 7835 Application
They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
Medium Voltage Cables to BS 6622/BS 7835 Construction
| Conductor | Stranded copper (Class 2), aluminium stranded (Class 2) or solid (class 1) |
| Insulation | Cross-linked Polyethylene (XLPE) Type GP8 or cross-linked Ethylene Propylene Rubber (EPR) Type GP7 |
| Insulation screen | Extruded semi-conductive layer of cross-linkable polymer or combination of semi-conductive layer and semi-conductive tape |
| Screen | Metallic screening layer of copper wire or copper tape |
| Bedding | Low Smoke Zero Halogen (LSZH) compound |
| Armour | Metallic armour of aluminium or aluminium alloy for single-core cables and galvanised steel wire for three-core cables |
| Outersheath | Thermoplastic LSZH oversheath, Polyvinyl Chloride (PVC) compound or medium density Polyethylene (MDPE) |
Medium Voltage Cables to BS 6622/BS 7835 Nominal /Operating /Test Voltages
| Rated Voltage Uo/U | Operating Voltage (Um) | Testing Voltage (rms) |
| 3.8/6.6KV | 7.2KV | 15KV |
| 6.35/11KV | 12KV | 25.5KV |
| 8.7/15KV | 17.5KV | 35KV |
| 12.7/22KV | 24KV | 51KV |
| 19/33KV | 36KV | 76KV |
Medium Voltage Cables to BS 6622/BS 7835 Single Core 3.8/6.6KV (Um=7.2KV)
Dimensional Data
| Nom. Cross-Section Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||||||
| Nom. Insulation Thickness | Copper Wire Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Copper Tape Screen Area | Nom. Bedding Thickness | Nom. Armour Wire Diameter | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |||
| CU | AL | ||||||||||||
| CU | AL | ||||||||||||
| mm^2 | mm | mm^2 | mm | mm | kg/km | mm^2 | mm | mm | mm | mm | kg/km | ||
| 25 | 2.5 | 16 | 1.5 | 20.3 | 750 | 580 | 3.4 | 1.2 | 1.6 | 1.8 | 26.3 | 1150 | 1000 |
| 35 | 2.5 | 16 | 1.6 | 21.3 | 870 | 650 | 3.6 | 1.2 | 1.6 | 1.8 | 27.3 | 1250 | 1050 |
| 50 | 2.5 | 16 | 1.6 | 22.4 | 1090 | 770 | 3.9 | 1.2 | 1.6 | 1.8 | 28.4 | 1500 | 1190 |
| 70 | 2.5 | 16 | 1.7 | 24.2 | 1310 | 870 | 4.3 | 1.2 | 1.6 | 1.8 | 30.0 | 1740 | 1300 |
| 95 | 2.5 | 16 | 1.7 | 25.8 | 1560 | 960 | 4.7 | 1.2 | 1.6 | 1.9 | 31.8 | 2030 | 1430 |
| 120 | 2.5 | 16 | 1.8 | 27.4 | 1830 | 1070 | 5.0 | 1.2 | 1.6 | 1.9 | 33.2 | 2310 | 1550 |
| 150 | 2.5 | 25 | 1.8 | 29.1 | 2130 | 1190 | 5.3 | 1.2 | 1.6 | 2.0 | 35.1 | 2660 | 1720 |
| 185 | 2.5 | 25 | 1.9 | 30.8 | 2490 | 1320 | 5.8 | 1.2 | 2.0 | 2.0 | 37.4 | 3120 | 1950 |
| 240 | 2.6 | 25 | 1.9 | 33.5 | 3040 | 1520 | 6.3 | 1.2 | 2.0 | 2.1 | 40.3 | 3740 | 2200 |
| 300 | 2.8 | 25 | 2.0 | 36.1 | 3650 | 1770 | 7.0 | 1.2 | 2.0 | 2.2 | 42.9 | 4400 | 2520 |
| 400 | 3.0 | 35 | 2.2 | 40.6 | 4680 | 2170 | 7.7 | 1.2 | 2.0 | 2.3 | 47.2 | 5490 | 2960 |
| 500 | 3.2 | 35 | 2.3 | 43.6 | 5670 | 2570 | 8.5 | 1.3 | 2.5 | 2.5 | 51.6 | 6760 | 3660 |
| 630 | 3.2 | 35 | 2.4 | 48.8 | 6980 | 2990 | 9.5 | 1.4 | 2.5 | 2.6 | 57.0 | 8200 | 4160 |
Medium Voltage Cables to BS 6622/BS 7835 Three Core 3.8/6.6KV (Um=7.2KV)
Dimensional Data
| Nom. Cross-Section Area | Unarmoured Cables | Steel Wire Armoured Cables | |||||||||||
| Nom. Insulation Thickness | Copper Wire Screen Area | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Copper Tape Screen Area | Nom. Bedding Thickness | Nom. Armour Wire Diameter | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |||
| CU | AL | ||||||||||||
| CU | AL | ||||||||||||
| mm^2 | mm | mm^2 | mm | mm | kg/km | mm^2 | mm | mm | mm | mm | kg/km | ||
| 25 | 2.5 | 16 | 2.1 | 37.7 | 2205 | 1740 | 3.4 | 1.2 | 2.0 | 2.2 | 44.5 | 3890 | 3465 |
| 35 | 2.5 | 16 | 2.3 | 41.2 | 2690 | 2010 | 3.6 | 1.2 | 2.5 | 2.3 | 46.8 | 4420 | 3730 |
| 50 | 2.5 | 16 | 2.5 | 44.9 | 3340 | 2350 | 3.8 | 1.3 | 2.5 | 2.5 | 51.5 | 5640 | 4690 |
| 70 | 2.5 | 16 | 2.6 | 48.0 | 4050 | 2730 | 4.3 | 1.3 | 2.5 | 2.6 | 55.0 | 6570 | 5240 |
| 95 | 2.5 | 16 | 2.7 | 51.7 | 5000 | 3180 | 4.7 | 1.4 | 2.5 | 2.7 | 58.9 | 7760 | 5890 |
| 120 | 2.5 | 16 | 2.8 | 54.7 | 5890 | 3590 | 5.0 | 1.5 | 2.5 | 2.8 | 62.1 | 8810 | 6510 |
| 150 | 2.5 | 25 | 2.9 | 58.4 | 6960 | 4160 | 5.3 | 1.5 | 2.5 | 2.9 | 65.8 | 10110 | 7310 |
| 185 | 2.5 | 25 | 3.0 | 61.9 | 8160 | 4650 | 5.8 | 1.6 | 2.5 | 3.0 | 69.5 | 11520 | 7960 |
| 240 | 2.6 | 25 | 3.2 | 68.1 | 10210 | 5530 | 6.3 | 1.7 | 2.5 | 3.2 | 75.9 | 13920 | 9140 |
| 300 | 2.8 | 25 | 3.5 | 73.6 | 12380 | 6670 | 7.0 | 1.8 | 3.15 | 3.5 | 83.1 | 17400 | 11620 |
| 400 | 3.0 | 35 | 3.7 | 83.8 | 16190 | 8430 | 7.7 | 2.0 | 3.15 | 3.7 | 93.0 | 21900 | 13980 |
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
Primary UD
† Ampacities are based on the following: Copper: Three shielded single insulated Copper conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835). Aluminum: Three shielded single insulated Aluminum conductors in…
LV — Power Cables Rated Voltage of 1.8 3V and below
LV cable: cable voltage level up to 1.8/3kV
Low Voltage Power Cables
Low Voltage(450/750v 0.6/1KV) Single-Multi-Core PVC/XLPE Insulated Power and Control Cables
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions