Primary UD
LV & MV Power Cables

Primary UD

† Ampacities are based on the following: Copper: Three shielded single insulated Copper conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835). Aluminum: Three shielded single insulated Aluminum conductors in…

  • Low tension stripping compounds. RUS U-1 (15 kV & 25 kV). True triple extrusion system and closed handling raw materials system…

Product Description

Ampacity – Primary UD Cables – Copper and Aluminum

Primary UD TR-XLPE / LLDPE, Concentric Neutral

Primary UD EPR / LLDPE, Concentric Neutral

Primary UD TR-XLPE / PVC, Concentric Neutral

Primary UD EPR / PVC, Concentric Neutral

Primary UD PILC Replacement, EPR/PE

Primary UD TR-XLPE Insulated, Concentric Neutral

Primary UD EPR Insulated, Concentric Neutral

Ampacity – Primary UD Cables – Copper and Aluminum

Ampacity 100% and 133% Insulation Levels

Size AWG or kcmil Copper Aluminum
5 – 15 kV 25 – 46 kV 5 –15 kV 25 – 46 kV
1/3 Neutral Full Neutral 1/3 Neutral Full Neutral 1/3 Neutral Full Neutral 1/3 Neutral Full Neutral
amp amp amp amp
2 160 160 – – 125 125 – –
1 187 185 189 188 146 145 147 147
1/0 212 210 214 212 166 165 167 167
2/0 241 238 248 245 189 188 194 193
3/0 273 268 281 276 214 213 220 218
4/0 309 300 317 309 244 241 250 247
250 336 – 344 – 266 – 273 –
350 398 – 407 – 320 – 326 –
500 476 – 476 – 394 – 392 –
750 547 – 555 – 476 – 486 –
1000 620 – 625 – 550 – 556 –
1/6 Neutral Full Neutral 1/6 Neutral Full Neutral 1/6 Neutral Full Neutral 1/6 Neutral Full Neutral
1000 658 – 658 – 580 – 573 –

† Ampacities are based on the following:
Copper: Three shielded single insulated Copper conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835).
Aluminum: Three shielded single insulated Aluminum conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835).

Primary UD TR-XLPE / LLDPE, Concentric Neutral

Features

Low tension stripping compounds.
RUS U-1 (15 kV & 25 kV).
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
On request, sealed conductor with strand filled compound passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
When requested, strand filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.
On request, dual sealed cable (strand filled on conductor + WSP on neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.
On request, can be UL Listed as MV90 for use in accordance with Article 328 of the NEC.
On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.

Specifications

Maximum operating voltage:

• 5 kV – 46 kV, 100 and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

ParameterSpecification
1. ConductorSoft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On requeststrand filled.
Sizes8 AWG – 1000 kcmil.
On requestlarger sizes.
2. Conductor ShieldSemi conducting cross-linked polyethylene (XLPE).
On requestsuper-clean and super-smooth materials.
  1. Insulation: Thermoset tree-retardant crosslinked polyethylene (TR-XLPE).

4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).

5. Concentric Neutral: Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced.

Full or 1/3 Neutral.

ParameterSpecification
On request optionsalternate neutral constructions, Water Swellable Powder (WSP), and ripcords.
6. JacketExtruded to fill (Encapsulated) Black sunlight resistant linear low density polyethylene (LLDPE), with three Red Stripes.
On requestsemiconducting PE or Black HDPE.

Configuration Options:

On request, Triplex or Paralleled configurations.

5 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft AWG mil in lb/m.ft
Copper 100% Insulation Level (90 mil)
2 7 0.50 6 14 50 0.81 469 16 14 50 0.81 589
1 19 0.54 7 14 50 0.84 547 13 12 50 0.88 730
1/0 19 0.58 9 14 50 0.88 653 16 12 50 0.92 870
2/0 19 0.63 11 14 50 0.93 779 13 10 50 1.00 1089
3/0 19 0.68 14 14 50 0.98 941 16 10 50 1.05 1309
4/0 19 0.73 18 14 50 1.03 1146 16 9 50 1.14 1613
250 37 0.79 13 12 50 1.12 1340 — — — — —
350 37 0.89 18 12 50 1.23 1785 — — — — —
500 37 1.02 17 10 50 1.42 2535 — — — — —
750 61 1.21 20 9 80 1.70 3731 — — — — —
1000 61 1.36 26 9 80 1.85 4807 — — — — —
Aluminum 100% Insulation Level (90 mil)
2 1 0.48 6 14 50 0.78 311 10 14 50 0.78 360
2 7 0.50 6 14 50 0.81 325 10 14 50 0.81 374
1 19 0.54 6 14 50 0.84 355 13 14 50 0.84 439
1/0 1 0.54 6 14 50 0.85 370 16 14 50 0.85 491
1/0 19 0.58 6 14 50 0.88 389 16 14 50 0.88 510
2/0 19 0.62 7 14 50 0.93 444 13 12 50 0.96 629
3/0 19 0.67 9 14 50 0.98 519 16 12 50 1.01 738
4/0 19 0.73 11 14 50 1.03 606 13 10 50 1.11 921
250 37 0.79 13 14 50 1.09 686 16 10 50 1.17 1071
350 37 0.89 18 14 50 1.19 879 16 9 50 1.29 1356
500 37 1.02 16 12 50 1.38 1208 29 10 50 1.42 1823
750 61 1.22 15 10 80 1.69 1798 — — — — —
1000 61 1.37 16 9 80 1.86 2292 — — — — —

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.

Ampacities: Refer to beginning of section.

8 kV TR-XLPE Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft AWG mil in lb/kft
Copper 100% Insulation Level (115 mil)
2 7 0.55 6 14 50 0.86 496 16 14 50 0.86 616
1 19 0.59 7 14 50 0.90 576 13 12 50 0.93 760
1/0 19 0.63 9 14 50 0.94 683 16 12 50 0.97 901
2/0 19 0.68 11 14 50 0.98 810 13 10 50 1.06 1123
3/0 19 0.73 14 14 50 1.03 974 16 10 50 1.11 1344
4/0 19 0.78 18 14 50 1.09 1180 16 9 50 1.19 1651
250 37 0.84 13 12 50 1.18 1377 25 10 50 1.22 1923
350 37 0.94 18 12 50 1.28 1826 22 8 50 1.37 2628
500 37 1.07 17 10 50 1.47 2582 31 8 50 1.53 3617
750 61 1.26 20 9 80 1.75 3787 — — — — —
1000 61 1.41 26 9 80 1.90 4868 — — — — —
Aluminum 100% Insulation Level (115 mil)
2 1 0.53 6 14 50 0.83 337 10 14 50 0.83 386
2 7 0.55 6 14 50 0.86 352 10 14 50 0.86 401
1 19 0.59 6 14 50 0.89 383 13 14 50 0.89 467
1/0 1 0.59 6 14 50 0.90 399 16 14 50 0.90 519
1/0 19 0.63 6 14 50 0.93 419 16 14 50 0.93 540
2/0 19 0.68 7 14 50 0.98 475 13 12 50 1.01 661
3/0 19 0.73 9 14 50 1.03 552 16 12 50 1.06 772
4/0 19 0.78 11 14 50 1.08 640 13 10 50 1.16 958
250 37 0.84 13 14 50 1.14 722 16 10 50 1.22 1110
350 37 0.94 18 14 50 1.24 918 16 9 50 1.34 1398
500 37 1.07 16 12 50 1.43 1253 29 10 50 1.47 1869
750 61 1.27 15 10 80 1.74 1853 — — — — —
1000 61 1.42 16 9 80 1.91 2353 — — — — —

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.

Ampacities: Refer to beginning of section.

15 kV TR-XLPE Insulated

1/3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lbs/Mt Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lbs/Mt
Copper 100% Insulation Level (175 mil)
2 7 0.68 6 14 50 0.98 568 2 7 0.68 16 14 50 0.98 689
1 19 0.71 7 14 50 1.02 651 1 19 0.71 13 12 50 1.05 837
1/0 19 0.75 9 14 50 1.06 761 1/0 19 0.75 25 14 50 1.06 954
2/0 19 0.80 11 14 50 1.10 892 1/0 19 0.75 16 12 50 1.09 982
3/0 19 0.85 14 14 50 1.15 1059 2/0 19 0.80 32 14 50 1.10 1145
4/0 19 0.90 18 14 50 1.21 1270 2/0 19 0.80 20 12 50 1.14 1166
250 37 0.96 21 14 50 1.26 1451 2/0 19 0.80 13 10 50 1.18 1210
250 37 0.96 13 12 50 1.30 1474 3/0 19 0.85 16 10 50 1.23 1435
350 37 1.06 29 14 50 1.39 1930 4/0 19 0.90 32 12 50 1.24 1692
350 37 1.06 18 12 50 1.42 1955 4/0 19 0.90 20 10 50 1.28 1722
500 37 1.19 26 12 50 1.55 2640 4/0 19 0.90 16 9 50 1.31 1748
500 37 1.19 17 10 50 1.59 2702 250 37 0.96 25 10 50 1.34 2022
750 61 1.38 25 10 80 1.85 3892 350 37 1.06 22 8 50 1.52 2766
750 61 1.38 20 9 80 1.87 3928 500 37 1.19 31 8 80 1.71 3808
1000 61 1.53 26 9 80 2.05 5069 — — — — — — — —
Aluminum 100% Insulation Level (175 mil)
2 1 0.65 6 14 50 0.95 407 2 1 0.65 10 14 50 0.95 455
2 7 0.67 6 14 50 0.98 424 2 7 0.67 10 14 50 0.98 472
1 19 0.71 6 14 50 1.02 457 1 19 0.71 13 14 50 1.02 541
1/0 1 0.72 6 14 50 1.02 473 1/0 1 0.72 16 14 50 1.02 594
1/0 19 0.75 6 14 50 1.06 496 1/0 19 0.75 16 14 50 1.06 617
2/0 19 0.80 7 14 50 1.10 555 2/0 19 0.80 20 14 50 1.10 712
3/0 19 0.85 9 14 50 1.15 636 2/0 19 0.80 13 12 50 1.13 744
4/0 19 0.90 11 14 50 1.21 729 3/0 19 0.85 25 14 50 1.15 829
250 37 0.96 13 14 50 1.26 815 3/0 19 0.85 16 12 50 1.18 859
350 37 1.06 18 14 50 1.39 1042 4/0 19 0.90 32 14 50 1.21 982
350 37 1.06 11 12 50 1.42 1066 4/0 19 0.90 20 12 50 1.24 1006
500 37 1.19 25 14 50 1.52 1331 4/0 19 0.90 13 10 50 1.28 1052
500 37 1.19 16 12 50 1.55 1368 250 37 0.96 25 12 50 1.30 1164
750 61 1.40 24 12 80 1.82 1945 250 37 0.96 16 10 50 1.34 1208
750 61 1.40 15 10 80 1.86 1992 350 37 1.06 32 12 50 1.42 1468
1000 61 1.54 31 12 80 2.00 2446 350 37 1.06 20 10 50 1.46 1503
1000 61 1.54 20 10 80 2.04 2516 350 37 1.06 16 9 50 1.49 1532
— — — — — — — — 500 37 1.19 29 10 50 1.59 1988
— — — — — — — — 750 61 1.40 28 8 80 1.91 2956
— — — — — — — — 1000 61 1.54 37 8 80 2.09 3770

15 kV TR-XLPE Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 50 1.07 628
1 19 0.81 7 14 50 1.11 713
1/0 19 0.85 9 14 50 1.15 826
2/0 19 0.89 11 14 50 1.19 959
3/0 19 0.94 14 14 50 1.24 1129
4/0 19 1.00 18 14 50 1.30 1343
250 37 1.05 21 14 50 1.38 1552
250 37 1.05 13 12 50 1.41 1577
300 37 1.13 25 14 50 1.45 1794
300 37 1.13 16 12 50 1.49 1831
350 37 1.16 29 14 50 1.48 2015
350 37 1.16 18 12 50 1.52 2042
500 37 1.28 26 12 80 1.71 2799
500 37 1.28 17 10 80 1.75 2866
750 61 1.47 25 10 80 1.94 4003
750 61 1.47 20 9 80 1.96 4040
1000 61 1.62 26 9 80 2.14 5192
Aluminum 133% Insulation Level (220 mil)
2 1 0.74 6 14 50 1.04 465
2 7 0.76 6 14 50 1.07 483
1 19 0.80 6 14 50 1.11 519
1/0 1 0.81 6 14 50 1.11 535
1/0 19 0.84 6 14 50 1.15 560
2/0 19 0.89 7 14 50 1.19 622
3/0 19 0.94 9 14 50 1.24 705
4/0 19 0.99 11 14 50 1.30 801
250 37 1.05 13 14 50 1.38 914
350 37 1.15 18 14 50 1.48 1125
500 37 1.28 25 14 50 1.61 1421
500 37 1.28 16 12 80 1.70 1528
750 61 1.49 24 12 80 1.91 2053
750 61 1.49 15 10 80 1.95 2102
1000 61 1.64 31 12 80 2.09 2565
1000 61 1.64 20 10 80 2.13 2637
1000 61 1.64 16 9 80 2.16 2676
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation In Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 133% Insulation Level (220 mil)
2 7 0.77 16 14 50 1.07 749
1 19 0.81 13 12 50 1.14 902
1/0 19 0.85 25 14 50 1.15 1019
1/0 19 0.85 16 12 50 1.18 1049
2/0 19 0.89 32 14 50 1.19 1212
2/0 19 0.89 20 12 50 1.23 1235
2/0 19 0.89 13 10 50 1.27 1282
3/0 19 0.94 16 10 50 1.32 1510
4/0 19 1.00 32 12 50 1.33 1767
4/0 19 1.00 20 10 50 1.38 1800
4/0 19 1.00 16 9 50 1.40 1827
250 37 1.05 25 10 50 1.46 2129
300 37 1.13 18 8 50 1.58 2489
350 37 1.16 22 8 50 1.61 2858
500 37 1.28 31 8 80 1.80 3910
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (220 mil)
2 1 0.74 10 14 50 1.04 513
2 7 0.76 10 14 50 1.07 531
1 19 0.80 13 14 50 1.11 603
1/0 1 0.81 16 14 50 1.11 655
1/0 19 0.84 16 14 50 1.15 681
2/0 19 0.89 20 14 50 1.19 779
2/0 19 0.89 13 12 50 1.22 812
3/0 19 0.94 25 14 50 1.24 898
3/0 19 0.94 16 12 50 1.27 930
4/0 19 0.99 32 14 50 1.30 1055
4/0 19 0.99 20 12 50 1.33 1080
4/0 19 0.99 13 10 50 1.37 1129
250 37 1.05 25 12 50 1.41 1266
250 37 1.05 16 10 50 1.45 1313
350 37 1.15 32 12 50 1.51 1553
350 37 1.15 20 10 50 1.55 1591
350 37 1.15 16 9 50 1.58 1620
500 37 1.28 29 10 80 1.75 2152
750 61 1.49 28 8 80 2.01 3069
1000 61 1.64 37 8 80 2.18 3894

25 kV TR-XLPE Insulated

1/3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 100% Insulation Level (260 mil)
1 19 0.89 7 14 50 1.19 773 1 19 0.89 13 12 50 1.23 963
1/0 19 0.93 9 14 50 1.23 888 1/0 19 0.93 25 14 50 1.23 1081
2/0 19 0.97 11 14 50 1.28 1023 1/0 19 0.93 16 12 50 1.27 1113
3/0 19 1.02 14 14 50 1.35 1220 2/0 19 0.97 13 10 50 1.35 1350
4/0 19 1.08 18 14 50 1.40 1438 3/0 19 1.02 16 10 50 1.42 1605
250 37 1.13 21 14 50 1.46 1626 4/0 19 1.08 32 12 50 1.44 1864
250 37 1.13 13 12 50 1.49 1653 4/0 19 1.08 20 10 50 1.48 1900
350 37 1.24 29 14 50 1.56 2094 4/0 19 1.08 16 9 50 1.51 1928
350 37 1.24 18 12 50 1.60 2123 250 37 1.13 25 10 50 1.54 2207
500 37 1.37 17 10 80 1.83 2959 350 37 1.24 22 8 80 1.75 3012
750 61 1.56 25 10 80 2.05 4155 500 37 1.37 31 8 80 1.88 4006
750 61 1.56 20 9 80 2.08 4194 — — — — — — —
1000 61 1.70 26 9 80 2.23 5306 — — — — — — —
1000 61 1.70 21 8 80 2.25 5365 — — — — — — —
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 6 14 50 1.19 578 1 19 0.88 13 14 50 1.19 662
1/0 1 0.89 6 14 50 1.19 594 1/0 1 0.89 16 14 50 1.19 715
1/0 19 0.92 6 14 50 1.23 621 1/0 19 0.92 16 14 50 1.23 742
2/0 19 0.97 7 14 50 1.27 685 2/0 19 0.97 20 14 50 1.27 842
3/0 19 1.02 9 14 50 1.34 794 2/0 19 0.97 13 12 50 1.30 877
4/0 19 1.07 11 14 50 1.40 894 3/0 19 1.02 25 14 50 1.34 987
250 37 1.13 13 14 50 1.46 987 3/0 19 1.02 16 12 50 1.38 1021
350 37 1.23 18 14 50 1.56 1204 4/0 19 1.07 32 14 50 1.40 1147
500 37 1.36 25 14 80 1.75 1575 4/0 19 1.07 20 12 50 1.43 1175
500 37 1.36 16 12 80 1.78 1618 4/0 19 1.07 13 10 50 1.48 1227
750 61 1.57 24 12 80 2.02 2200 250 37 1.13 25 12 50 1.49 1341
750 61 1.57 15 10 80 2.06 2252 250 37 1.13 16 10 50 1.53 1390
1000 61 1.72 31 12 80 2.17 2674 350 37 1.23 32 12 50 1.59 1633
1000 61 1.72 20 10 80 2.21 2748 350 37 1.23 20 10 80 1.70 1740
1000 61 1.72 16 9 80 2.24 2789 350 37 1.23 16 9 80 1.72 1772
— — — — — — — — 500 37 1.36 29 10 80 1.83 2244
— — — — — — — — 750 61 1.57 28 8 80 2.12 3223
— — — — — — — — 1000 61 1.72 37 8 80 2.27 4008

25 kV TR-XLPE Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper 133% Insulation Level (320 mil)
1/0 19 1.05 9 14 50 1.38 1013
2/0 19 1.09 11 14 50 1.42 1152
3/0 19 1.14 14 14 50 1.47 1330
4/0 19 1.20 18 14 50 1.53 1552
250 37 1.26 13 12 50 1.62 1775
350 37 1.36 18 12 80 1.78 2321
500 37 1.49 17 10 80 1.95 3106
750 61 1.68 20 9 80 2.20 4361
1000 61 1.83 26 9 80 2.35 5484
Aluminum 133% Insulation Level (320 mil)
1/0 1 1.01 6 14 50 1.31 691
1/0 19 1.05 6 14 50 1.37 744
2/0 19 1.09 7 14 50 1.42 812
3/0 19 1.14 9 14 50 1.47 903
4/0 19 1.20 11 14 50 1.52 1007
250 37 1.25 13 14 50 1.58 1105
350 37 1.35 18 14 80 1.74 1398
500 37 1.48 25 14 80 1.87 1715
500 37 1.48 16 12 80 1.91 1760
750 61 1.69 24 12 80 2.14 2361
750 61 1.69 15 10 80 2.18 2417
1000 61 1.84 31 12 80 2.29 2846
1000 61 1.84 20 10 80 2.33 2924
1000 61 1.84 16 9 80 2.36 2966
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper 133% Insulation Level (320 mil)
1/0 19 1.05 16 12 50 1.41 1241
2/0 19 1.09 13 10 50 1.50 1486
3/0 19 1.14 16 10 50 1.55 1721
4/0 19 1.20 16 9 80 1.69 2116
250 37 1.26 25 10 80 1.72 2398
350 37 1.36 22 8 80 1.88 3153
500 37 1.49 31 8 80 2.01 4157
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (320 mil)
1/0 1 1.01 16 14 50 1.31 811
1/0 19 1.05 16 14 50 1.37 865
2/0 19 1.09 20 14 50 1.42 969
2/0 19 1.09 13 12 50 1.45 1007
3/0 19 1.14 25 14 50 1.47 1096
3/0 19 1.14 16 12 50 1.50 1132
4/0 19 1.20 32 14 50 1.52 1260
4/0 19 1.20 20 12 50 1.55 1290
4/0 19 1.20 13 10 50 1.60 1346
250 37 1.25 25 12 50 1.61 1461
250 37 1.25 16 10 80 1.72 1581
350 37 1.35 32 12 80 1.78 1831
350 37 1.35 20 10 80 1.82 1876
350 37 1.35 16 9 80 1.84 1910
500 37 1.48 29 10 80 1.95 2389
750 61 1.69 28 8 80 2.24 3391
1000 61 1.84 37 8 80 2.39 4188

35 kV TR-XLPE Insulated

1/3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 9 14 50 1.43 1059 1/0 19 1.10 25 14 50 1.43 1252
2/0 19 1.15 11 14 50 1.47 1200 1/0 19 1.10 16 12 50 1.46 1287
3/0 19 1.20 14 14 50 1.52 1379 2/0 19 1.15 32 14 50 1.47 1453
4/0 19 1.25 18 14 50 1.58 1603 2/0 19 1.15 20 12 50 1.51 1482
250 37 1.31 21 14 80 1.70 1863 2/0 19 1.15 13 10 50 1.55 1536
250 37 1.31 13 12 80 1.73 1895 3/0 19 1.20 16 10 50 1.60 1773
350 37 1.41 29 14 80 1.80 2346 4/0 19 1.25 32 12 50 1.61 2033
350 37 1.41 18 12 80 1.83 2380 4/0 19 1.25 20 10 80 1.72 2140
500 37 1.54 17 10 80 2.04 3219 4/0 19 1.25 16 9 80 1.74 2172
750 61 1.73 25 10 80 2.22 4391 250 37 1.31 25 10 80 1.77 2455
750 61 1.73 20 9 80 2.25 4433 350 37 1.41 22 8 80 1.93 3215
1000 61 1.88 26 9 80 2.40 5561 500 37 1.54 31 8 80 2.09 4273
Aluminum 100% Insulation Level (345 mil)
1/0 1 1.06 6 14 50 1.38 757 1/0 1 1.06 16 14 50 1.38 878
1/0 19 1.10 6 14 50 1.42 789 1/0 19 1.10 16 14 50 1.42 910
2/0 19 1.14 7 14 50 1.47 859 2/0 19 1.14 20 14 50 1.47 1016
3/0 19 1.19 9 14 50 1.52 951 2/0 19 1.14 13 12 50 1.50 1055
4/0 19 1.25 11 14 50 1.57 1057 3/0 19 1.19 25 14 50 1.52 1144
250 37 1.30 13 14 80 1.69 1223 3/0 19 1.19 16 12 50 1.55 1181
350 37 1.40 18 14 80 1.79 1454 4/0 19 1.25 32 14 50 1.57 1310
500 37 1.53 25 14 80 1.95 1822 4/0 19 1.25 20 12 50 1.61 1341
500 37 1.53 16 12 80 1.99 1868 4/0 19 1.25 13 10 80 1.71 1465
750 61 1.74 24 12 80 2.19 2431 250 37 1.30 25 12 80 1.73 1582
750 61 1.74 15 10 80 2.24 2488 250 37 1.30 16 10 80 1.77 1637
1000 61 1.89 31 12 80 2.34 2921 350 37 1.40 32 12 80 1.83 1889
1000 61 1.89 20 10 80 2.38 3000 350 37 1.40 20 10 80 1.87 1935
1000 61 1.89 16 9 80 2.41 3043 350 37 1.40 16 9 80 1.89 1970
— — — — — — — — 500 37 1.53 29 10 80 2.03 2500
— — — — — — — — 750 61 1.74 28 8 80 2.29 3464
— — — — — — — — 1000 61 1.89 37 8 80 2.44 4265

35 kV TR-XLPE Insulated

1/3 Neutral
Site AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 9 14 50 1.58 1206
2/0 19 1.30 11 14 50 1.63 1351
3/0 19 1.35 14 14 80 1.74 1602
4/0 19 1.40 18 14 80 1.79 1834
250 37 1.46 13 12 80 1.88 2071
350 37 1.56 18 12 80 2.02 2614
500 37 1.69 17 10 80 2.19 3425
750 61 1.88 20 9 80 2.40 4660
1000 61 2.03 26 9 80 2.55 5802
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 50 1.57 934
2/0 19 1.29 7 14 50 1.62 1008
3/0 19 1.34 9 14 80 1.73 1173
4/0 19 1.40 11 14 80 1.79 1287
250 37 1.45 13 14 80 1.84 1394
350 37 1.56 18 14 80 1.98 1681
500 37 1.68 25 14 80 2.11 2018
500 37 1.68 16 12 80 2.14 2068
750 61 1.89 24 12 80 2.34 2650
750 61 1.89 15 10 80 2.39 2710
1000 61 2.04 16 9 80 2.56 3282
Full Neutral
Site AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 16 12 50 1.61 1438
2/0 19 1.30 13 10 80 1.76 1763
3/0 19 1.35 16 10 80 1.81 2006
4/0 19 1.40 16 9 80 1.89 2349
250 37 1.46 25 10 80 1.95 2635
350 37 1.56 22 8 80 2.11 3461
500 37 1.69 31 8 80 2.24 4484
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 50 1.57 934
2/0 19 1.29 7 14 50 1.62 1008
3/0 19 1.34 9 14 80 1.73 1173
4/0 19 1.40 11 14 80 1.79 1287
250 37 1.45 13 14 80 1.84 1394
350 37 1.56 18 14 80 1.98 1681
500 37 1.68 25 14 80 2.11 2018
500 37 1.68 16 12 80 2.14 2068
750 61 1.89 24 12 80 2.34 2650
750 61 1.89 15 10 80 2.39 2710
1000 61 2.04 16 9 80 2.56 3282

Primary UD EPR / LLDPE, Concentric Neutral 5 kV – 46 kV

Features

Low tension stripping compounds.

True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

On request, Sealed conductor with strand filled compound passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

When requested, Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.

On request, Dual sealed cable (Strand Filled on conductor + WSP on Neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.

On request, can be UL Listed as MV90 for use in accordance with Article 328 of the NEC.

On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.

Application

Underground primary residential and commercial distribution circuits.

May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.

Specifications

Maximum operating voltage:

• 5 kV – 46 kV 100% and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

ParameterSpecification
1. ConductorSoft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On requeststrand filled.
Sizes8 AWG – 1000 kcmil.
On requestlarger sizes available.
2. Conductor ShieldSemi conducting cross-linked polyethylene (XLPE).

On request, super clean and super smooth materials.

ParameterSpecification
3. InsulationThermoset ethylene propylene rubber (EPR).
On requestamorphous EPR.
4. Insulation ShieldSemi conducting cross-linked polyethylene (XLPE).
5. Concentric NeutralSoft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced.

Full or 1/3 Neutral.

ParameterSpecification
On request optionsalternate neutral constructions, Water Swellable Powder (WSP), and ripcords.
6. JacketExtruded to fill (Encapsulated) Black sunlight resistant linear low density polyethylene (LLDPE), with three Red Stripes.
On requestsemiconducting PE or Black HDPE.

Configuration Options:

On request: Triplex or Paralleled configurations.

Technical Data

5 kV EPR Insulated

1⁄3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
In AWG mil in lb/Aft in AWG mil in lb/Aft
Copper 100% Insulation Level (90 mil)
2 7 0.50 6 14 50 0.81 484 2 7 0.50 16 14 50 0.81 604
1 19 0.54 7 14 50 0.84 564 1 19 0.54 13 12 50 0.88 747
1/0 19 0.58 9 14 50 0.88 672 1/0 19 0.58 16 12 50 0.92 889
2/0 19 0.63 11 14 50 0.93 799 2/0 19 0.63 13 10 50 1.00 1109
3/0 19 0.68 14 14 50 0.98 963 3/0 19 0.68 16 10 50 1.05 1331
4/0 19 0.73 18 14 50 1.03 1170 4/0 19 0.73 16 9 50 1.14 1637
250 37 0.79 13 12 50 1.12 1366 250 37 0.79 25 10 50 1.17 1910
350 37 0.89 18 12 50 1.23 1815 350 37 0.89 22 8 50 1.32 2614
500 37 1.02 17 10 50 1.42 2569 500 37 1.02 31 8 50 1.47 3603
750 61 1.21 20 9 80 1.70 3773 — — — — — — — —
1000 61 1.36 26 9 80 1.85 4854 — — — — — — — —

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.

Ampacities: Refer to beginning of section.

8 kV EPR Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/kft
Copper 100% Insulation Level (115 mil)
2 7 0.55 6 14 50 0.86 517
1 19 0.59 7 14 50 0.90 598
1/0 19 0.63 9 14 50 0.94 708
2/0 19 0.68 11 14 50 0.98 837
3/0 19 0.73 14 14 50 1.03 1003
4/0 19 0.78 18 14 50 1.09 1212
250 37 0.84 13 12 50 1.18 1412
350 37 0.94 18 12 50 1.28 1865
500 37 1.07 17 10 50 1.47 2627
750 61 1.26 20 9 80 1.75 3841
1000 61 1.41 26 9 80 1.90 4929
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/kft
Copper 100% Insulation Level (115 mil)
2 7 0.55 16 14 50 0.86 637
1 19 0.59 13 12 50 0.93 782
1/0 19 0.63 16 12 50 0.97 925
2/0 19 0.68 13 10 50 1.06 1149
3/0 19 0.73 16 10 50 1.11 1373
4/0 19 0.78 16 9 50 1.19 1682
250 37 0.84 25 10 50 1.22 1957
350 37 0.94 22 8 50 1.37 2667
500 37 1.07 31 8 50 1.53 3663
— — — — — — — —
— — — — — — — —

15 kV EPR Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 100% Insulation Level (175 mil)
2 7 0.68 6 14 50 0.98 604
1 19 0.71 7 14 50 1.02 689
1/0 19 0.75 9 14 50 1.06 803
2/0 19 0.80 11 14 50 1.10 937
3/0 19 0.85 14 14 50 1.15 1108
4/0 19 0.90 18 14 50 1.21 1323
250 37 0.96 13 12 50 1.30 1537
350 37 1.06 18 12 50 1.42 2019
500 37 1.19 17 10 50 1.59 2775
750 61 1.38 20 9 80 1.87 4015
1000 61 1.53 26 9 80 2.05 5167
Aluminum 100% Insulation Level (175 mil)
2 1 0.65 6 14 50 0.95 441
2 7 0.67 6 14 50 0.98 459
1 19 0.71 6 14 50 1.02 495
1/0 1 0.72 6 14 50 1.02 512
1/0 19 0.75 6 14 50 1.06 537
2/0 19 0.80 7 14 50 1.10 600
3/0 19 0.85 9 14 50 1.15 684
4/0 19 0.90 11 14 50 1.21 781
250 37 0.96 13 14 50 1.26 871
300 37 1.01 15 14 50 1.34 994
350 37 1.06 18 14 50 1.39 1106
500 37 1.19 25 14 50 1.52 1403
500 37 1.19 16 12 50 1.55 1441
750 61 1.40 24 12 80 1.82 2033
750 61 1.40 15 10 80 1.86 2079
1000 61 1.54 31 12 80 2.00 2544
1000 61 1.54 20 10 80 2.04 2614
1000 61 1.54 16 9 80 2.07 2651
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 100% Insulation Level (175 mil)
2 7 0.68 16 14 50 0.98 725
1 19 0.71 13 12 50 1.05 876
1/0 19 0.75 16 12 50 1.09 1024
2/0 19 0.80 13 10 50 1.18 1255
3/0 19 0.85 16 10 50 1.23 1484
4/0 19 0.90 16 9 50 1.31 1801
250 37 0.96 25 10 50 1.34 2079
350 37 1.06 22 8 50 1.52 2830
500 37 1.19 31 8 80 1.71 3881
— — — — — — — —
— — — — — — — —
Aluminum 100% Insulation Level (175 mil)
2 1 0.65 10 14 50 0.95 489
2 7 0.67 10 14 50 0.98 507
1 19 0.71 13 14 50 1.02 580
1/0 1 0.72 16 14 50 1.02 632
1/0 19 0.75 16 14 50 1.06 658
2/0 19 0.80 20 14 50 1.10 757
2/0 19 0.80 13 12 50 1.13 788
3/0 19 0.85 25 14 50 1.15 877
3/0 19 0.85 16 12 50 1.18 907
4/0 19 0.90 32 14 50 1.21 1034
4/0 19 0.90 20 12 50 1.24 1058
4/0 19 0.90 13 10 50 1.28 1104
250 37 0.96 25 12 50 1.30 1220
250 37 0.96 16 10 50 1.34 1264
350 37 1.06 32 12 50 1.42 1532
350 37 1.06 20 10 50 1.46 1567
350 37 1.06 16 9 50 1.49 1595
500 37 1.19 29 10 50 1.59 2060
750 61 1.40 28 8 80 1.91 3043
1000 61 1.54 37 8 80 2.09 3868

15 kV EPR Insulated

1⁄3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
In AWG mil in lb/Mt In AWG mil in lb/Mt
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 50 1.07 678 2 7 0.77 16 14 50 1.07 798
1 19 0.81 7 14 50 1.11 766 1 19 0.81 13 12 50 1.14 955
1/0 19 0.85 9 14 50 1.15 883 1/0 19 0.85 16 12 50 1.18 1105
2/0 19 0.89 11 14 50 1.19 1020 2/0 19 0.89 13 10 50 1.27 1342
3/0 19 0.94 14 14 50 1.24 1195 3/0 19 0.94 16 10 50 1.32 1575
4/0 19 1.00 18 14 50 1.30 1414 4/0 19 1.00 16 9 50 1.40 1898
250 37 1.05 13 12 50 1.41 1653 250 37 1.05 25 10 50 1.46 2204
350 37 1.16 18 12 50 1.52 2126 350 37 1.16 22 8 50 1.61 2942
500 37 1.28 17 10 80 1.75 2962 500 37 1.28 31 8 80 1.80 4007
750 61 1.47 20 9 80 1.96 4154 — — — — — — — —
1000 61 1.62 26 9 80 2.14 5320 — — — — — — — —
Aluminum 133% Insulation Level (220 mil)
2 1 0.74 6 14 50 1.04 511 2 1 0.74 10 14 50 1.04 560
2 7 0.76 6 14 50 1.07 532 2 7 0.76 10 14 50 1.07 580
1 19 0.80 6 14 50 1.11 571 1 19 0.80 13 14 50 1.11 655
1/0 1 0.81 6 14 50 1.11 588 1/0 1 0.81 16 14 50 1.11 708
1/0 19 0.84 6 14 50 1.16 629 1/0 19 0.84 16 14 50 1.15 737
2/0 19 0.89 7 14 50 1.19 682 2/0 19 0.89 20 14 50 1.19 839
3/0 19 0.94 9 14 50 1.24 770 2/0 19 0.89 13 12 50 1.22 872
4/0 19 0.99 11 14 50 1.30 871 3/0 19 0.94 25 14 50 1.24 963
250 37 1.05 13 14 50 1.38 989 3/0 19 0.94 16 12 50 1.27 994
350 37 1.15 18 14 50 1.48 1209 4/0 19 0.99 32 14 50 1.30 1124
500 37 1.28 25 14 50 1.61 1517 4/0 19 0.99 20 12 50 1.33 1149
500 37 1.28 16 12 80 1.70 1623 4/0 19 0.99 13 10 50 1.37 1199
750 61 1.49 24 12 80 1.91 2167 250 37 1.05 25 12 50 1.41 1341
750 61 1.49 15 10 80 1.95 2216 250 37 1.05 16 10 50 1.45 1388
1000 61 1.64 31 12 80 2.09 2692 350 37 1.15 32 12 50 1.51 1637
1000 61 1.64 20 10 80 2.13 2764 350 37 1.15 20 10 50 1.55 1674
1000 61 1.64 16 9 80 2.16 2803 350 37 1.15 16 9 50 1.58 1704
— — — — — — — — 500 37 1.28 29 10 80 1.75 2247
— — — — — — — — 750 61 1.49 28 8 80 2.01 3183
— — — — — — — — 1000 61 1.64 37 8 80 2.18 4021

25 kV EPR Insulated

1⁄3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/Kft
Copper 100% Insulation Level (260 mil)
1 19 0.89 7 14 50 1.19 840
1/0 19 0.93 9 14 50 1.23 959
2/0 19 0.97 11 14 50 1.28 1099
3/0 19 1.02 14 14 50 1.35 1301
4/0 19 1.08 18 14 50 1.40 1525
250 37 1.13 13 12 50 1.49 1747
350 37 1.24 18 12 50 1.60 2227
500 37 1.37 17 10 80 1.83 3077
750 61 1.56 20 9 80 2.08 4333
1000 61 1.70 26 9 80 2.23 5461
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 6 14 50 1.19 644
1/0 1 0.89 6 14 50 1.19 661
1/0 19 0.92 6 14 50 1.23 692
2/0 19 0.97 7 14 50 1.27 760
3/0 19 1.02 9 14 50 1.34 875
4/0 19 1.07 11 14 50 1.40 981
250 37 1.13 13 14 50 1.46 1080
350 37 1.23 18 14 50 1.56 1307
500 37 1.36 25 14 80 1.75 1692
500 37 1.36 16 12 80 1.78 1735
750 61 1.57 24 12 80 2.02 2340
750 61 1.57 15 10 80 2.06 2392
1000 61 1.72 31 12 80 2.17 2829
1000 61 1.72 20 10 80 2.21 2903
1000 61 1.72 16 9 80 2.24 2944
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/Kft
Copper 100% Insulation Level (260 mil)
1 19 0.89 13 12 50 1.23 1030
1/0 19 0.93 16 12 50 1.27 1184
2/0 19 0.97 13 10 50 1.35 1426
3/0 19 1.02 16 10 50 1.42 1687
4/0 19 1.08 16 9 50 1.51 2016
250 37 1.13 25 10 50 1.54 2300
350 37 1.24 22 8 80 1.75 3116
500 37 1.37 31 8 80 1.88 4124
— — — — — — — —
— — — — — — — —
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 13 14 50 1.19 728
1/0 1 0.89 16 14 50 1.19 781
1/0 19 0.92 16 14 50 1.23 812
2/0 19 0.97 20 14 50 1.27 917
2/0 19 0.97 13 12 50 1.30 952
3/0 19 1.02 25 14 50 1.34 1068
3/0 19 1.02 16 12 50 1.38 1102
4/0 19 1.07 32 14 50 1.40 1234
4/0 19 1.07 20 12 50 1.43 1261
4/0 19 1.07 13 10 50 1.48 1313
250 37 1.13 25 12 50 1.49 1433
250 37 1.13 16 10 50 1.53 1482
350 37 1.23 32 12 50 1.59 1736
350 37 1.23 20 10 80 1.70 1843
350 37 1.23 16 9 80 1.72 1875
500 37 1.36 29 10 80 1.83 2361
750 61 1.57 28 8 80 2.12 3362
1000 61 1.72 37 8 80 2.27 4163

25 kV EPR Insulated

1⁄3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 133% Insulation Level (320 mil)
1 19 1.01 7 14 50 1.31 961
1/0 19 1.05 9 14 50 1.38 1109
2/0 19 1.09 11 14 50 1.42 1254
3/0 19 1.14 14 14 50 1.47 1439
4/0 19 1.20 18 14 50 1.53 1668
250 37 1.26 13 12 50 1.62 1898
350 37 1.36 18 12 80 1.78 2458
500 37 1.49 17 10 80 1.95 3260
750 61 1.68 20 9 80 2.20 4540
1000 61 1.83 26 9 80 2.35 5683
Aluminum 133% Insulation Level (320 mil)
1/0 19 1.05 6 14 50 1.37 839
2/0 19 1.09 7 14 50 1.42 913
3/0 19 1.14 9 14 50 1.47 1010
4/0 19 1.20 11 14 50 1.52 1122
250 37 1.25 13 14 50 1.58 1226
350 37 1.35 18 14 80 1.74 1533
500 37 1.48 25 14 80 1.87 1867
500 37 1.48 16 12 80 1.91 1912
750 61 1.69 24 12 80 2.14 2540
750 61 1.69 15 10 80 2.18 2596
1000 61 1.84 31 12 80 2.29 3045
1000 61 1.84 20 10 80 2.33 3123
1000 61 1.84 16 9 80 2.36 3165
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 133% Insulation Level (320 mil)
1 19 1.01 13 12 50 1.35 1154
1/0 19 1.05 16 12 50 1.41 1337
2/0 19 1.09 13 10 50 1.50 1588
3/0 19 1.14 16 10 50 1.55 1830
4/0 19 1.20 16 9 80 1.69 2232
250 37 1.26 25 10 80 1.72 2522
350 37 1.36 22 8 80 1.88 3290
500 37 1.49 31 8 80 2.01 4311
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (320 mil)
1/0 19 1.05 16 14 50 1.37 959
2/0 19 1.09 20 14 50 1.42 1070
2/0 19 1.09 13 12 50 1.45 1108
3/0 19 1.14 25 14 50 1.47 1203
3/0 19 1.14 16 12 50 1.50 1239
4/0 19 1.20 32 14 50 1.52 1375
4/0 19 1.20 20 12 50 1.55 1405
4/0 19 1.20 13 10 50 1.60 1460
250 37 1.25 25 12 50 1.61 1583
250 37 1.25 16 10 80 1.72 1703
350 37 1.35 32 12 80 1.78 1966
350 37 1.35 20 10 80 1.82 2011
350 37 1.35 16 9 80 1.84 2045
500 37 1.48 29 10 80 1.95 2541

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.

35 kV EPR Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
in
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 9 14 50 1.43 1166
2/0 19 1.15 11 14 50 1.47 1313
3/0 19 1.20 14 14 50 1.52 1499
4/0 19 1.25 18 14 50 1.58 1731
250 37 1.31 13 12 80 1.73 2032
350 37 1.41 18 12 80 1.83 2531
500 37 1.54 17 10 80 2.04 3388
750 61 1.73 20 9 80 2.25 4630
1000 61 1.88 26 9 80 2.40 5779
Aluminum 100% Insulation Level (345 mil)
1/0 1 1.06 6 14 50 1.38 858
1/0 19 1.10 6 14 50 1.42 895
2/0 19 1.14 7 14 50 1.47 971
3/0 19 1.19 9 14 50 1.52 1070
4/0 19 1.25 11 14 50 1.57 1184
250 37 1.30 13 14 80 1.69 1358
350 37 1.40 18 14 80 1.79 1604
500 37 1.53 25 14 80 1.95 1989
500 37 1.53 16 12 80 1.99 2036
750 61 1.74 24 12 80 2.19 2628
750 61 1.74 15 10 80 2.24 2684
1000 61 1.89 31 12 80 2.34 3139
1000 61 1.89 20 10 80 2.38 3217
1000 61 1.89 16 9 80 2.41 3260
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 16 12 50 1.46 1395
2/0 19 1.15 13 10 50 1.55 1649
3/0 19 1.20 16 10 50 1.60 1893
4/0 19 1.25 16 9 80 1.74 2301
250 37 1.31 25 10 80 1.77 2592
350 37 1.41 22 8 80 1.93 3366
500 37 1.54 31 8 80 2.09 4443
— — — — — — — —
— — — — — — — —
Aluminum 100% Insulation Level (345 mil)
1/0 1 1.06 16 14 50 1.38 979
1/0 19 1.10 16 14 50 1.42 1015
2/0 19 1.14 20 14 50 1.47 1127
2/0 19 1.14 13 12 50 1.50 1167
3/0 19 1.19 25 14 50 1.52 1263
3/0 19 1.19 16 12 50 1.55 1300
4/0 19 1.25 32 14 50 1.57 1437
4/0 19 1.25 20 12 50 1.61 1468
4/0 19 1.25 13 10 80 1.71 1592
250 37 1.30 25 12 80 1.73 1716
250 37 1.30 16 10 80 1.77 1772
350 37 1.40 32 12 80 1.83 2038
350 37 1.40 20 10 80 1.87 2084
350 37 1.40 16 9 80 1.89 2119
500 37 1.53 29 10 80 2.03 2667
750 61 1.74 28 8 80 2.29 3661
1000 61 1.89 37 8 80 2.44 4483

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.

35 kV EPR Insulated

1⁄3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 9 14 50 1.58 1349
2/0 19 1.30 11 14 50 1.63 1502
3/0 19 1.35 14 14 80 1.74 1762
4/0 19 1.40 18 14 80 1.79 2004
250 37 1.46 13 12 80 1.88 2251
350 37 1.56 18 12 80 2.02 2811
500 37 1.69 17 10 80 2.19 3645
750 61 1.88 20 9 80 2.40 4912
1000 61 2.03 26 9 80 2.55 6081
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 50 1.57 1076
2/0 19 1.29 7 14 50 1.62 1157
3/0 19 1.34 9 14 80 1.73 1331
4/0 19 1.40 11 14 80 1.79 1454
250 37 1.45 13 14 80 1.84 1571
350 37 1.56 18 14 80 1.98 1876
500 37 1.68 25 14 80 2.11 2235
500 37 1.68 16 12 80 2.14 2285
750 61 1.89 24 12 80 2.34 2902
750 61 1.89 15 10 80 2.39 2963
1000 61 2.04 16 9 80 2.56 3560
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 16 12 50 1.61 1581
2/0 19 1.30 13 10 80 1.76 1914
3/0 19 1.35 16 10 80 1.81 2166
4/0 19 1.40 16 9 80 1.89 2519
250 37 1.46 25 10 80 1.93 2815
350 37 1.56 22 8 80 2.11 3658
500 37 1.69 31 8 80 2.24 4704
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 16 14 50 1.57 1196
2/0 19 1.29 20 14 80 1.68 1380
2/0 19 1.29 13 12 80 1.71 1424
3/0 19 1.34 25 14 80 1.73 1524
3/0 19 1.34 16 12 80 1.76 1566
4/0 19 1.40 32 14 80 1.79 1707
4/0 19 1.40 20 12 80 1.82 1743
4/0 19 1.40 13 10 80 1.86 1805
250 37 1.45 25 12 80 1.88 1933
250 37 1.45 16 10 80 1.92 1992
350 37 1.56 32 12 80 2.01 2314
350 37 1.56 20 10 80 2.05 2365
350 37 1.56 16 9 80 2.08 2403
500 37 1.68 29 10 80 2.18 2920

The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.

Primary UD TR-XLPE / PVC, Concentric Neutral 5 kV – 46 kV

Features

Low tension stripping compounds.

Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.

True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

On request, can be UL Listed as MV105 for use in accordance with Article 328 of the NEC.

On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.

Application

Underground primary residential and commercial distribution circuits.

May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, Rated 5 – 46 kV.

Specifications

Maximum operating voltage:

• 5 kV – 46 kV, 100 and 133% IL

Maximum conductor operation temperatures:

Wet and dry locations

For TR-XLPE

  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

For XLPE

  • Normal: 90 °C
  • Emergency: 130 °C
  • Short Circuit: 250 °C

Engineering Information

ParameterSpecification
1. ConductorSoft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On requeststrand filled.
Sizes8 AWG – 1000 kcmil.
On requestlarger sizes.
2. Conductor ShieldSemi conducting cross-linked polyethylene (XLPE).
On requestsuper clean and super smooth materials.
3. InsulationThermoset tree-retardant cross-linked polyethylene (TR-XLPE).
On requestcross-linked polyethylene (XLPE).
4. Insulation ShieldSemi conducting cross-linked polyethylene (XLPE).
5. Concentric NeutralSoft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced.

Full or 1/3 Neutral.

ParameterSpecification
On request optionsalternate neutral constructions, Water Swellable Powder (WSP), and ripcords.
6. Binder TapeA suitable polyester tape, as required.
7. JacketOverlying (sleeve) black polyvinyl chloride (PVC).

Configuration Options:

On request: Triplex or Paralleled configurations.

Technical Data

5 kV TR-XLPE Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation in 1/3Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/kft
Copper 100% Insulation Level (90 mil)
2 7 0.50 6 14 60 0.83 472 16 14 60 0.83 606
1 19 0.54 7 14 60 0.87 551 13 12 80 0.95 775
1/0 19 0.58 9 14 80 0.95 697 16 12 80 0.99 922
2/0 19 0.63 11 14 80 1.00 826 13 10 80 1.07 1131
3/0 19 0.68 14 14 80 1.05 993 16 10 80 1.12 1359
4/0 19 0.73 18 14 80 1.10 1204 16 9 80 1.20 1662
250 37 0.79 13 12 80 1.19 1385 25 10 80 1.23 1961
350 37 0.89 18 12 80 1.29 1841 22 8 80 1.39 2656
500 37 1.02 17 10 80 1.49 2578 31 8 80 1.54 3678
750 61 1.21 20 9 110 1.77 3815 — — — — —
1000 61 1.36 26 9 110 1.91 4912 — — — — —
Aluminum 100% Insulation Level (90 mil)
2 7 0.50 6 14 60 0.83 330 10 14 60 0.83 383
1 19 0.54 6 14 80 0.91 395 13 14 80 0.91 489
1/0 19 0.58 6 14 80 0.95 431 16 14 80 0.95 564
2/0 19 0.62 7 14 80 1.00 488 13 12 80 1.03 676
3/0 19 0.67 9 14 80 1.05 567 16 12 80 1.08 792
4/0 19 0.73 11 14 80 1.10 657 13 10 80 1.18 962
250 37 0.79 13 14 80 1.16 741 16 10 80 1.24 1121
350 37 0.89 18 14 80 1.26 942 16 9 80 1.36 1400
500 37 1.02 16 12 80 1.45 1261 29 10 80 1.49 1908
750 61 1.22 15 10 110 1.76 1872 — — — — —
1000 61 1.37 16 9 110 1.93 2360 — — — — —

8 kV TR-XLPE Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft AWG mil in lb/kft
Copper 100% Insulation Level (115 mil)
2 7 0.55 6 14 60 0.88 498 16 14 60 0.88 632
1 19 0.59 7 14 80 0.96 617 13 12 80 1.00 805
1/0 19 0.63 9 14 80 1.00 728 16 12 80 1.04 953
2/0 19 0.68 11 14 80 1.05 858 13 10 80 1.12 1163
3/0 19 0.73 14 14 80 1.10 1027 16 10 80 1.17 1393
4/0 19 0.78 18 14 80 1.15 1240 16 9 80 1.25 1697
250 37 0.84 13 12 80 1.24 1423 — — — — —
350 37 0.94 18 12 80 1.35 1881 — — — — —
500 37 1.07 17 10 80 1.54 2624 — — — — —
750 61 1.26 20 9 110 1.82 3870 — — — — —
1000 61 1.41 26 9 110 1.97 4972 — — — — —
Aluminum 100% Insulation Level (1 15 mil)
2 7 0.55 6 14 80 0.92 393 10 14 80 0.92 447
1 19 0.59 6 14 80 0.96 424 13 14 80 0.96 518
1/0 19 0.63 6 14 80 1.00 461 16 14 80 1.00 595
2/0 19 0.68 7 14 80 1.05 520 13 12 80 1.08 708
3/0 19 0.73 9 14 80 1.10 600 16 12 80 1.13 825
4/0 19 0.78 11 14 80 1.15 693 13 10 80 1.23 998
250 37 0.84 13 14 80 1.21 778 16 10 80 1.29 1158
350 37 0.94 18 14 80 1.31 983 16 9 80 1.41 1440
500 37 1.07 16 12 80 1.50 1307 29 10 80 1.54 1954
750 61 1.27 15 10 110 1.81 1927 — — — — —
1000 61 1.42 16 9 110 1.98 2419 — — — — —

15 kV TR-XLPE Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 100% Insulation Level (175 mil)
2 1 0.68 6 14 80 1.05 610
2 7 0.68 6 14 80 1.05 610 16 14 80 1.05 743
1 19 0.71 7 14 80 1.09 694 13 12 80 1.12 883
1/0 19 0.75 9 14 80 1.13 808 16 12 80 1.16 1034
2/0 19 0.80 11 14 80 1.17 942 13 10 80 1.25 1247
3/0 19 0.85 14 14 80 1.22 1115 16 10 80 1.30 1481
4/0 19 0.90 18 14 80 1.28 1332 16 9 80 1.38 1790
250 37 0.96 13 12 80 1.37 1519 25 10 80 1.41 2095
350 37 1.06 18 12 80 1.49 2011 22 8 80 1.59 2826
500 37 1.19 17 10 80 1.66 2741 31 8 110 1.78 3947
750 61 1.38 20 9 110 1.94 4008 — — — — —
1000 61 1.53 26 9 110 2.12 5170 — — — — —
Aluminum 100% Insulation Level (175 mil)
2 7 0.67 6 14 80 1.05 467 10 14 80 1.05 520
1 19 0.71 6 14 80 1.08 501 13 14 80 1.08 595
1/0 19 0.75 6 14 80 1.12 541 16 14 80 1.12 675
2/0 19 0.80 7 14 80 1.17 603 13 12 80 1.20 791
3/0 19 0.85 9 14 80 1.22 687 16 12 80 1.25 912
4/0 19 0.90 11 14 80 1.27 784 13 10 80 1.35 1089
250 37 0.96 13 14 80 1.33 874 16 10 80 1.41 1253
350 37 1.06 18 14 80 1.46 1110 16 9 80 1.56 1568
500 37 1.19 16 12 80 1.62 1422 29 10 80 1.66 2069
750 61 1.40 24 12 110 1.89 2059 — — — — —
750 61 1.40 15 10 110 1.93 2065 — — — — —
1000 61 1.54 16 9 110 2.13 2616 — — — — —

15 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
in AWG mil in lb/kft AWG mil in lb/kft
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 80 1.14 672 16 14 80 1.14 805
1 19 0.81 7 14 80 1.18 759 13 12 80 1.21 947
1/0 19 0.85 9 14 80 1.22 875 16 12 80 1.25 1100
2/0 19 0.89 11 14 80 1.26 1012 13 10 80 1.34 1316
3/0 19 0.94 14 14 80 1.31 1187 16 10 80 1.39 1553
4/0 19 1.00 18 14 80 1.37 1407 16 9 80 1.47 1865
250 37 1.05 13 12 80 1.48 1622 25 10 80 1.52 2198
350 37 1.16 18 12 80 1.58 2097 22 8 80 1.68 2912
500 37 1.28 17 10 110 1.82 2943 31 8 110 1.87 4046
750 61 1.47 20 9 110 2.03 4118 — — — — —
1000 61 1.62 26 9 110 2.21 5291 — — — — —
Aluminum 133% Insulation Level (220 mil)
2 7 0.76 6 14 80 1.14 528 10 14 80 1.14 582
1 19 0.80 6 14 80 1.18 565 13 14 80 1.18 658
1/0 19 0.84 6 14 80 1.22 607 16 14 80 1.22 741
2/0 19 0.89 7 14 80 1.26 671 13 12 80 1.29 859
3/0 19 0.94 9 14 80 1.31 758 16 12 80 1.34 983
4/0 19 0.99 11 14 80 1.37 858 13 10 80 1.44 1163
250 37 1.05 13 14 80 1.44 975 16 10 80 1.52 1355
350 37 1.15 18 14 80 1.55 1195 16 9 80 1.65 1653
500 37 1.28 16 12 110 1.77 1622 29 10 110 1.81 2272
750 61 1.49 15 10 110 2.02 2175 — — — — —
1000 61 1.64 16 9 110 2.23 2737 — — — — —

25 kV TR-XLPE Insulated

1/3 Neutral Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Size AWG or kcmil Number of Strands Nominal OD Over Insulation in Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/ft AWG mil in lb/ft
Copper 100% Insulation Level (260 mil)
1 19 0.89 7 14 80 1.26 820 1 19 0.89 13 12 80 1.29 1009
1/0 19 0.93 9 14 80 1.30 939 1/0 19 0.93 16 12 80 1.33 1164
2/0 19 0.97 11 14 80 1.34 1077 2/0 19 0.97 32 14 80 1.34 1358
3/0 19 1.02 14 14 80 1.42 1280 2/0 19 0.97 20 12 80 1.38 1361
4/0 19 1.08 18 14 80 1.47 1504 2/0 19 0.97 13 10 80 1.42 1382
250 37 1.13 13 12 80 1.56 1698 3/0 19 1.02 16 10 80 1.49 1646
350 37 1.24 18 12 80 1.66 2178 4/0 19 1.08 16 9 80 1.57 1961
500 37 1.37 17 10 110 1.90 3035 250 37 1.13 25 10 80 1.60 2274
750 61 1.56 20 9 110 2.14 4269 350 37 1.24 22 8 110 1.82 3102
1000 61 1.70 26 9 110 2.29 5403 500 37 1.37 31 8 110 1.95 4139
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 6 14 80 1.26 626 1 19 0.88 13 14 80 1.26 719
1/0 19 0.92 6 14 80 1.30 670 1/0 19 0.92 16 14 80 1.30 804
2/0 19 0.97 7 14 80 1.34 736 2/0 19 0.97 13 12 80 1.37 925
3/0 19 1.02 9 14 80 1.41 849 3/0 19 1.02 16 12 80 1.45 1075
4/0 19 1.07 11 14 80 1.47 953 4/0 19 1.07 13 10 80 1.54 1258
250 37 1.13 13 14 80 1.53 1050 250 37 1.13 16 10 80 1.60 1430
350 37 1.23 18 14 80 1.63 1275 350 37 1.23 16 9 110 1.79 1842
500 37 1.36 16 12 110 1.85 1714 500 37 1.36 29 10 110 1.90 2363
750 61 1.57 15 10 110 2.13 2325 — — — — — — — —
1000 61 1.72 16 9 110 2.31 2848 — — — — — — — —

25 kV TR-XLPE Insulated

1/3 Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation Number of Wires Size AWG Jacket Thickness mm Approximate Outside Diameter mm Approximate Net Weight lb/kft
Copper 133% Insulation Level (320 mil)
1/0 19 1.05 9 14 80 1.44 1067
2/0 19 1.09 11 14 80 1.49 1210
3/0 19 1.14 14 14 80 1.54 1392
4/0 19 1.20 18 14 80 1.59 1621
250 37 1.26 13 12 80 1.68 1820
350 37 1.36 18 12 110 1.85 2418
500 37 1.49 17 10 110 2.02 3182
750 61 1.68 20 9 110 2.27 4433
1000 61 1.83 26 9 110 2.42 5578
Aluminum 133% Insulation Level (320 mil)
1/0 1 1.01 6 14 50 1.31 691
1/0 19 1.05 6 14 50 1.37 744
2/0 19 1.09 7 14 50 1.42 812
3/0 19 1.14 9 14 50 1.47 903
4/0 19 1.20 11 14 50 1.52 1007
250 37 1.25 13 14 50 1.58 1105
350 37 1.35 18 14 80 1.74 1398
500 37 1.48 25 14 80 1.87 1715
500 37 1.48 16 12 80 1.91 1760
750 61 1.69 24 12 80 2.14 2361
750 61 1.69 15 10 80 2.18 2417
1000 61 1.84 31 12 80 2.29 2846
1000 61 1.84 20 10 80 2.33 2924
1000 61 1.84 16 9 80 2.36 2966
— — — — — — — —
— — — — — — — —
— — — — — — — —
Full Neutral
Size AWG or kcmil Number of Strands Nominal OD Over Insulation In Number of Wires Size AWG Jacket Thickness mm Approximate Outside Diameter mm Approximate Net Weight lb/kft
Copper 133% Insulation Level (320 mil)
1/0 19 1.05 16 12 80 1.48 1292
2/0 19 1.09 13 10 80 1.56 1515
3/0 19 1.14 16 10 80 1.61 1758
4/0 19 1.20 16 9 110 1.76 2184
250 37 1.26 25 10 110 1.79 2502
350 37 1.36 22 8 110 1.94 3239
500 37 1.49 31 8 110 2.07 4285
— — — — — — — —
— — — — — — — —
Aluminum 133% Insulation Level (320 mil)
1/0 1 1.01 16 14 50 1.31 811
1/0 19 1.05 16 14 50 1.37 865
2/0 19 1.09 20 14 50 1.42 969
2/0 19 1.09 13 12 50 1.45 1007
3/0 19 1.14 25 14 50 1.47 1096
3/0 19 1.14 16 12 50 1.50 1132
4/0 19 1.20 32 14 50 1.52 1260
4/0 19 1.20 20 12 50 1.55 1290
4/0 19 1.20 13 10 50 1.60 1346
250 37 1.25 25 12 50 1.61 1461
250 37 1.25 16 10 80 1.72 1581
350 37 1.35 32 12 80 1.78 1831
350 37 1.35 20 10 80 1.82 1876
350 37 1.35 16 9 80 1.84 1910
500 37 1.48 29 10 80 1.95 2389
750 61 1.69 28 8 80 2.24 3391
1000 61 1.84 37 8 80 2.39 4188

35 kV TR-XLPE Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation In 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil In lb/kft AWG mil In lb/kft
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 9 14 80 1.50 1114 16 12 80 1.53 1397
2/0 19 1.15 11 14 80 1.54 1258 13 10 80 1.62 1652
3/0 19 1.20 14 14 80 1.59 1442 16 10 80 1.67 1896
4/0 19 1.25 18 14 80 1.65 1673 16 9 110 1.81 2305
250 37 1.31 13 12 110 1.80 1981 25 10 110 1.84 2596
350 37 1.41 18 12 110 1.90 2477 22 8 110 2.00 3371
500 37 1.54 17 10 110 2.10 3294 31 8 110 2.16 4448
750 61 1.73 20 9 110 2.32 4504 — — — — —
1000 61 1.88 26 9 110 2.47 5654 — — — — —
Aluminum 100% Insulation Level (345 mil)
1/0 19 1.10 6 14 80 1.49 842 16 14 80 1.49 976
2/0 19 1.14 7 14 80 1.53 914 13 12 80 1.57 1102
3/0 19 1.19 9 14 80 1.58 1010 16 12 80 1.62 1235
4/0 19 1.25 11 14 80 1.64 1120 13 10 110 1.78 1533
250 37 1.30 13 14 110 1.76 1330 16 10 110 1.84 1714
350 37 1.40 18 14 110 1.86 1572 16 9 110 1.96 2036
500 37 1.53 16 12 110 2.06 1969 29 10 110 2.10 2619
750 61 1.74 15 10 110 2.30 2560 — — — — —
1000 61 1.89 16 9 110 2.48 3099 — — — — —

35 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/kft AWG mil in lb/kft
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 9 14 80 1.65 1264 16 12 80 1.68 1489
2/0 19 1.30 11 14 110 1.76 1517 13 10 110 1.83 1827
3/0 19 1.35 14 14 110 1.81 1709 16 10 110 1.88 2080
4/0 19 1.40 18 14 110 1.86 1948 16 9 110 1.96 2412
250 37 1.46 13 12 110 1.95 2160 25 10 110 1.99 2738
350 37 1.56 18 12 110 2.08 2716 22 8 110 2.18 3537
500 37 1.69 17 10 110 2.26 3499 31 8 110 2.31 4603
750 61 1.88 20 9 110 2.47 4728 — — — — —
1000 61 2.03 26 9 110 2.62 5892 — — — — —
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 80 1.64 990 16 14 80 1.64 1124
2/0 19 1.29 7 14 110 1.75 1173 13 12 110 1.78 1363
3/0 19 1.34 9 14 110 1.80 1276 16 12 110 1.83 1504
4/0 19 1.40 11 14 110 1.86 1395 13 10 110 1.93 1705
250 37 1.45 13 14 110 1.91 1507 16 10 110 1.99 1891
350 37 1.56 18 14 110 2.04 1807 16 9 110 2.15 2271
500 37 1.68 16 12 110 2.21 2172 29 10 110 2.25 2821
750 61 1.89 15 10 110 2.46 2782 — — — — —
1000 61 2.04 16 9 110 2.63 3335 — — — — —

Primary UD EPR / PVC, Concentric Neutral 15 kV – 46 kV

Features

Low tension stripping compounds.

Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.

True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

On request, can be UL Listed as MV105 for use in accordance with Article 328 of the NEC.

On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.

Application

Underground primary residential and commercial distribution circuits.

May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV

Specifications

Maximum operating voltage:

• 5 kV – 46 kV, 100 and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

ParameterSpecification
1. ConductorSoft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On requeststrand filled.
Sizes8 AWG – 1000 kcmil.

On request, larger sizes.

ParameterSpecification
2. Conductor ShieldSemi conducting cross-linked polyethylene (XLPE).
On requestsuper clean and super smooth materials.
3. InsulationThermoset ethylene propylene rubber (EPR).
On requestamorphous EPR.
4. Insulation ShieldSemi conducting cross-linked polyethylene (XLPE).
5. Concentric NeutralSoft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced.

Full or 1/3 Neutral.

ParameterSpecification
On request optionsalternate neutral constructions, Water Swellable Powder (WSP), and ripcords.
6. Binder TapeA suitable polyester tape, as required.
7. JacketExtruded Overlying (Sleeve) Black polyvinyl chloride (PVC) sunlight resistant.

Configuration Options:

On request: Triplex or Paralleled configurations.

Technical Data

15 kV EPR Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/KR Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/KR
Copper 100% Insulation Level (175 mil)
2 7 0.68 6 14 80 1.05 646 16 14 80 1.05 779
1 19 0.71 7 14 80 1.09 733 13 12 80 1.12 921
1/0 19 0.75 9 14 80 1.13 850 16 12 80 1.16 1075
2/0 19 0.80 11 14 80 1.17 987 13 10 80 1.25 1292
3/0 19 0.85 14 14 80 1.22 1163 16 10 80 1.30 1530
4/0 19 0.90 18 14 80 1.28 1385 16 9 80 1.38 1842
250 37 0.96 13 12 80 1.37 1576 25 10 80 1.41 2151
350 37 1.06 18 12 80 1.49 2075 22 8 80 1.59 2890
500 37 1.19 17 10 80 1.66 2814 31 8 110 1.78 4020
750 61 1.38 20 9 110 1.94 4095 — — — — —
1000 61 1.53 26 9 110 2.12 5268 — — — — —
Aluminum 100% Insulation Level (175 mil)
2 7 0.67 6 14 80 1.05 503 10 14 80 1.05 556
1 19 0.71 6 14 80 1.08 540 13 14 80 1.08 633
1/0 19 0.75 6 14 80 1.12 582 16 14 80 1.12 716
2/0 19 0.80 7 14 80 1.17 647 13 12 80 1.20 835
3/0 19 0.85 9 14 80 1.22 735 16 12 80 1.25 960
4/0 19 0.90 11 14 80 1.27 836 13 10 80 1.35 1141
250 37 0.96 13 14 80 1.33 930 16 10 80 1.41 1309
350 37 1.06 18 14 80 1.46 1174 16 9 80 1.56 1631
500 37 1.19 16 12 80 1.62 1495 29 10 80 1.66 2142
750 61 1.40 15 10 110 1.93 2153 — — — — —
1000 61 1.54 16 9 110 2.13 2715 — — — — —

15 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 80 1.14 721 16 14 80 1.14 855
1 19 0.81 7 14 80 1.18 812 13 12 80 1.21 1000
1/0 19 0.85 9 14 80 1.22 932 16 12 80 1.25 1157
2/0 19 0.89 11 14 80 1.26 1072 13 10 80 1.34 1377
3/0 19 0.94 14 14 80 1.31 1252 16 10 80 1.39 1618
4/0 19 1.00 18 14 80 1.37 1478 16 9 80 1.47 1935
250 37 1.05 13 12 80 1.48 1698 25 10 80 1.52 2273
350 37 1.16 18 12 80 1.58 2182 22 8 80 1.68 2997
500 37 1.28 17 10 110 1.82 3039 31 8 110 1.87 4143
750 61 1.47 20 9 110 2.03 4232 — — — — —
1000 61 1.62 26 9 110 2.21 5418 — — — — —
Aluminum 133% Insulation Level (220 mil)
2 7 0.76 6 14 80 1.14 577 10 14 80 1.14 631
1 19 0.80 6 14 80 1.18 617 13 14 80 1.18 711
1/0 19 0.84 6 14 80 1.22 663 16 14 80 1.22 797
2/0 19 0.89 7 14 80 1.26 731 13 12 80 1.29 919
3/0 19 0.94 9 14 80 1.31 823 16 12 80 1.34 1048
4/0 19 0.99 11 14 80 1.37 928 13 10 80 1.44 1233
250 37 1.05 13 14 80 1.44 1050 16 10 80 1.52 1430
350 37 1.15 18 14 80 1.55 1279 16 9 80 1.65 1737
500 37 1.28 16 12 110 1.77 1718 29 10 110 1.81 2367
750 61 1.49 15 10 110 2.02 2289 — — — — —
1000 61 1.64 16 9 110 2.23 2864 — — — — —

25 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation
in
1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lb/kft AWG mil in lb/kft
Copper 100% Insulation Level (260 mil)
1 19 0.89 7 14 80 1.26 887 13 12 80 1.29 1076
1/0 19 0.93 9 14 80 1.30 1010 16 12 80 1.33 1235
2/0 19 0.97 11 14 80 1.34 1154 13 10 80 1.42 1458
3/0 19 1.02 14 14 80 1.42 1361 16 10 80 1.49 1727
4/0 19 1.08 18 14 80 1.47 1591 16 9 80 1.57 2049
250 37 1.13 13 12 80 1.56 1792 25 10 80 1.60 2367
350 37 1.24 18 12 80 1.66 2282 22 8 110 1.82 3207
500 37 1.37 17 10 110 1.90 3154 31 8 110 1.95 4257
750 61 1.56 20 9 110 2.14 4408 — — — — —
1000 61 1.70 26 9 110 2.29 5558 — — — — —
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 6 14 80 1.26 692 13 14 80 1.26 785
1/0 19 0.92 6 14 80 1.30 741 16 14 80 1.30 874
2/0 19 0.97 7 14 80 1.34 812 13 12 80 1.37 1000
3/0 19 1.02 9 14 80 1.41 930 16 12 80 1.45 1155
4/0 19 1.07 11 14 80 1.47 1040 13 10 80 1.54 1345
250 37 1.13 13 14 80 1.53 1143 16 10 80 1.60 1522
350 37 1.23 18 14 80 1.63 1379 16 9 110 1.79 1945
500 37 1.36 16 12 110 1.85 1831 29 10 110 1.90 2480
750 61 1.57 15 10 110 2.13 2464 — — — — —
1000 61 1.72 16 9 110 2.31 3003 — — — — —

25 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kt Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kt
Copper 133% Insulation Level (320 mil)
1 19 1.01 7 14 80 1.38 1011 13 12 80 1.41 1199
1/0 19 1.05 9 14 80 1.44 1163 16 12 80 1.48 1388
2/0 19 1.09 11 14 80 1.49 1311 13 10 80 1.56 1616
3/0 19 1.14 14 14 80 1.54 1501 16 10 80 1.61 1867
4/0 19 1.20 18 14 80 1.59 1737 16 9 110 1.76 2299
250 37 1.26 13 12 80 1.68 1943 25 10 110 1.79 2625
350 37 1.36 18 12 110 1.85 2554 22 8 110 1.94 3376
500 37 1.49 17 10 110 2.02 3336 31 8 110 2.07 4439
750 61 1.68 20 9 110 2.27 4612 — — — — —
1000 61 1.83 26 9 110 2.42 5777 — — — — —
Aluminum 133% Insulation Level (320 mil)
1/0 19 1.05 6 14 80 1.44 891 16 14 80 1.44 1024
2/0 19 1.09 7 14 80 1.48 967 13 12 80 1.52 1155
3/0 19 1.14 9 14 80 1.53 1068 16 12 80 1.57 1293
4/0 19 1.20 11 14 80 1.59 1183 13 10 80 1.67 1488
250 37 1.25 13 14 80 1.65 1292 16 10 110 1.79 1780
350 37 1.35 18 14 110 1.81 1648 16 9 110 1.91 2112
500 37 1.48 16 12 110 1.97 2011 29 10 110 2.02 2660
750 61 1.69 15 10 110 2.25 2668 — — — — —
1000 61 1.84 16 9 110 2.43 3222 — — — — —

35 kV EPR Insulated

Size AWG or kmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight Number of Wires Size Jacket Thickness Approximate Outside Diameter Approximate Net Weight
AWG mil in lbs/kft AWG mil in lbs/kft
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 9 14 80 1.50 1221 16 12 80 1.53 1446
2/0 19 1.15 11 14 80 1.54 1371 13 10 80 1.62 1676
3/0 19 1.20 14 14 80 1.59 1563 16 10 80 1.67 1929
4/0 19 1.25 18 14 80 1.65 1801 16 9 110 1.81 2367
250 37 1.31 13 12 110 1.80 2117 25 10 110 1.84 2695
350 37 1.41 18 12 110 1.90 2629 22 8 110 2.00 3450
500 37 1.54 17 10 110 2.10 3464 31 8 110 2.16 4567
750 61 1.73 20 9 110 2.32 4701 — — — — —
1000 61 1.88 26 9 110 2.47 5872 — — — — —
Aluminum 100% Insulation Level (345 mil)
1/0 19 1.10 6 14 80 1.49 948 16 14 80 1.49 1082
2/0 19 1.14 7 14 80 1.53 1026 13 12 80 1.57 1214
3/0 19 1.19 9 14 80 1.58 1129 16 12 80 1.62 1354
4/0 19 1.25 11 14 80 1.64 1247 13 10 110 1.78 1660
250 37 1.30 13 14 110 1.76 1465 16 10 110 1.84 1849
350 37 1.40 18 14 110 1.86 1722 16 9 110 1.96 2186
500 37 1.53 16 12 110 2.06 2137 29 10 110 2.10 2786
750 61 1.74 15 10 110 2.30 2756 — — — — —
1000 61 1.89 16 9 110 2.48 3317 — — — — —

35 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/ft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/ft
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 9 14 80 1.65 1407 16 12 80 1.68 1632
2/0 19 1.30 11 14 110 1.76 1668 13 10 110 1.83 1978
3/0 19 1.35 14 14 110 1.81 1869 16 10 110 1.88 2240
4/0 19 1.40 18 14 110 1.86 2118 16 9 110 1.96 2582
250 37 1.46 13 12 110 1.95 2339 25 10 110 1.99 2917
350 37 1.56 18 12 110 2.08 2913 22 8 110 2.18 3734
500 37 1.69 17 10 110 2.26 3719 31 8 110 2.31 4822
750 61 1.88 20 9 110 2.47 4980 — — — — —
1000 61 2.03 26 9 110 2.62 6171 — — — — —
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 80 1.64 1132 16 14 80 1.64 1266
2/0 19 1.29 7 14 110 1.75 1322 13 12 110 1.78 1512
3/0 19 1.34 9 14 110 1.80 1434 16 12 110 1.83 1662
4/0 19 1.40 11 14 110 1.86 1563 13 10 110 1.93 1872
250 37 1.45 13 14 110 1.91 1684 16 10 110 1.99 2069
350 37 1.56 18 14 110 2.04 2001 16 9 110 2.15 2466
500 37 1.68 16 12 110 2.21 2389 29 10 110 2.25 3038
750 61 1.89 15 10 110 2.46 3034 — — — — —
1000 61 2.04 16 9 110 2.63 3613 — — — — —

Primary UD PILC Replacement, EPR/PE 15 kV – 35 kV

Features

Reduced overall OD.

True triple extrusion system, for optimum concentricity, and excellent electric field control.

Closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

Sealed conductor passes the Production Water Penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

Heavy duty mechanical and sunlight resistance jacket.

Application

Underground primary distribution circuits where existing duct spacing is limited and reduced cable OD is desired.

May be used in wet or dry locations, installed in underground ducts, or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV.

Specifications

Maximum operating voltage:

• 15 kV – 35 kV, 100% and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

1. Conductor: Uncoated soft annealed copper Class B compacted stranding per ASTM B496.

On request, Filled strand conductor.

ParameterSpecification
Sizes4/0 AWG – 1000 kcmil.
2. Conductor ShieldExtruded semiconducting cross-linked polyethylene per ICEA and AEIC.
3. InsulationHigh quality, heat, moisture, ozone and corona resistant, thermosetting ethylene propylene rubber (EPR) per ICEA and AEIC.
4. Insulation ShieldExtruded Semiconducting cross-linked polyethylene per ICEA and AEIC.
5. ShieldFlat wires straps of annealed uncoated copper per ICEA, helically applied and uniformly spaced.
NoteSpecific flat strap constructions and configuration will vary per customer fault current requirements.
6. JacketExtruded to fill of Black Linear Low Density Polyethylene (LLDPE) sunlight resistant thermoplastic compound, per ICEA S-97-682.

On request, XLPE jacket.

15 kV EPR Insulated

100% Insulation Level (175 mils) 133% Insulation Level (220 mils)
Size AWG or kcmil Number of Strands Flat Straps Jacket Thickness Approximate Outside Diameter Approximate Net Weight Flat Straps Jacket Thickness Approximate Outside Diameter Approximate Net Weight
No. of Wires Dimensions No. of Wires Dimensions
mil mil mil in lb/kft mil mil mil in lb/kft
4/0 19 12 20 x 175 50 1.08 1185 12 20 x 175 50 1.17 1267
250 37 14 20 x 175 50 1.12 1353 14 20 x 175 50 1.22 1439
350 37 14 20 x 175 50 1.25 1742 14 20 x 175 50 1.35 1838
500 37 14 20 X 175 50 1.37 2270 14 20 x 175 50 1.47 2376
750 61 16 20 x 175 50 1.56 3176 16 20 x 175 50 1.65 3295
1000 61 16 20 x 175 50 1.71 4041 16 20 x 175 50 1.83 4214

25 kV EPR Insulated

100% Insulation Level (260 mls)
Size AWG or kcmil Number of Strands Flat Straps Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Number of Wires Dimensions
mil mil mil in lb/kft
4/0 19 12 20 x 175 50 1.27 1368
250 37 14 20 x 175 50 1.32 1544
350 37 14 20 x 175 50 1.43 1929
500 37 14 20 x 175 50 1.55 2475
750 61 16 20 x 175 50 1.73 3406
1000 61 16 20 x 175 50 1.91 4338

35 kV EPR Insulated

100% Insulation Level (345 mIL)
Size AWG or kcmil Number of Strands Flat Straps Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Number of Wires Dimensions
mil mil mil in lb/kft
4/0 19 12 20 x 175 50 1.45 1558
250 37 14 20 x 175 50 1.49 1741
350 37 14 20 x 175 50 1.60 2142
500 37 14 20 x 175 50 1.72 2705
750 61 16 20 x 175 50 1.93 3707
1000 61 16 20 x 175 50 2.08 4620

Primary UD TR-XLPE Insulated, Concentric Neutral 15 kV – 35 kV

Features

Low tension stripping compounds.

True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

Application

Underground primary residential and commercial distribution circuits.

May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV.

Specifications

Maximum operating voltage:

• 5 kV – 46 kV, 100% and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

1. Conductor: Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.

On request, strand filled.

Sizes: 8 AWG – 1000 kcmil.

On request, larger sizes available.

2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).

On request, super clean and super smooth materials.

ParameterSpecification
3. InsulationThermoset tree-retardant cross-linked polyethylene (TR-XLPE).
4. Insulation ShieldSemi conducting cross-linked polyethylene (XLPE).
5. Concentric NeutralTinned coated soft annealed solid copper wires per ASTM B3 and B33, helically applied and uniformly spaced.

Full or 1/3 Neutral.

On request, a Contrahelical Wire can be applied per customer request.

5 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires in Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (90 mil)
2 7 0.50 6 14 0.70 375 16 14 0.70 509
1 19 0.54 7 14 0.74 449 13 12 0.77 632
1/0 19 0.58 9 14 0.78 552 16 12 0.81 772
2/0 19 0.63 11 14 0.82 674 13 10 0.90 967
3/0 19 0.68 14 14 0.87 833 16 10 0.95 1187
4/0 19 0.73 18 14 0.93 1035 16 9 1.03 1476
250 37 0.79 13 12 1.02 1201 — — — —
350 37 0.89 18 12 1.12 1639 — — — —
500 37 1.02 17 10 1.32 2345 — — — —
750 61 1.21 20 9 1.53 3440 — — — —
1000 61 1.36 26 9 1.68 4504 — — — —
Aluminum 100% Insulation Level (90 mil)
2 1 0.48 6 14 0.67 221 10 14 0.67 275
2 7 0.50 6 14 0.70 232 10 14 0.70 285
1 19 0.54 6 14 0.74 255 13 14 0.74 349
1/0 1 0.54 6 14 0.74 270 16 14 0.74 404
1/0 19 0.58 6 14 0.78 284 16 14 0.78 418
2/0 19 0.62 7 14 0.82 333 13 12 0.86 516
3/0 19 0.67 9 14 0.87 404 16 12 0.91 624
4/0 19 0.73 11 14 0.93 485 13 10 1.00 778
250 37 0.79 13 14 0.98 559 16 10 1.06 927
350 37 0.89 18 14 1.09 743 16 9 1.19 1185
500 37 1.02 16 12 1.27 1031 29 10 1.31 1672
750 61 1.22 15 10 1.52 1493 — — — —
1000 61 1.37 16 9 1.69 1941 — — — —

8 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (115 mil)
2 7 0.55 6 14 0.75 395 16 14 0.75 529
1 19 0.59 7 14 0.79 470 13 12 0.83 653
1/0 19 0.63 9 14 0.83 575 16 12 0.87 794
2/0 19 0.68 11 14 0.88 698 13 10 0.95 990
3/0 19 0.73 14 14 0.93 858 16 10 1.00 1212
4/0 19 0.78 18 14 0.98 1062 16 9 1.08 1503
250 37 0.84 13 12 1.07 1229 — — — —
350 37 0.94 18 12 1.17 1671 — — — —
500 37 1.07 17 10 1.37 2382 — — — —
750 61 1.26 20 9 1.58 3483 — — — —
1000 61 1.41 26 9 1.73 4552 — — — —
Aluminum 100% Insulation Level (115 mil)
2 1 0.53 6 14 0.72 240 10 14 0.72 293
2 7 0.55 6 14 0.75 251 10 14 0.75 305
1 19 0.59 6 14 0.79 276 13 14 0.79 369
1/0 1 0.59 6 14 0.79 291 16 14 0.79 425
1/0 19 0.63 6 14 0.83 306 16 14 0.83 440
2/0 19 0.68 7 14 0.87 357 13 12 0.91 540
3/0 19 0.73 9 14 0.92 429 16 12 0.96 649
4/0 19 0.78 11 14 0.98 512 13 10 1.05 805
250 37 0.84 13 14 1.04 588 16 10 1.11 955
350 37 0.94 18 14 1.14 775 16 9 1.24 1216
500 37 1.07 16 12 1.32 1068 29 10 1.36 1709
750 61 1.27 15 10 1.57 1536 — — — —
1000 61 1.42 16 9 1.74 1988 — — — —

15 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (175 mil)
2 7 0.68 6 14 0.88 449 16 14 0.88 583
1 19 0.71 7 14 0.91 527 13 12 0.95 710
1/0 19 0.75 9 14 0.95 635 16 12 0.99 855
2/0 19 0.80 11 14 1.00 761 13 10 1.07 1054
3/0 19 0.85 14 14 1.05 926 16 10 1.12 1279
4/0 19 0.90 18 14 1.10 1133 16 9 1.20 1575
250 37 0.96 13 12 1.19 1305 — — — —
350 37 1.06 18 12 1.32 1776 — — — —
500 37 1.19 17 10 1.49 2478 — — — —
750 61 1.38 20 9 1.71 3593 — — — —
1000 61 1.53 26 9 1.89 4715 — — — —
1000 61 1.53 26 9 2.12 5170 — — — —
Aluminum 100% Insulation Level (175 mil)
2 1 0.65 6 14 0.85 291 10 14 0.85 345
2 7 0.67 6 14 0.87 304 10 14 0.87 358
1 19 0.71 6 14 0.91 332 13 14 0.91 426
1/0 1 0.72 6 14 0.91 347 16 14 0.91 482
1/0 19 0.75 6 14 0.95 365 16 14 0.95 499
2/0 19 0.80 7 14 0.99 419 13 12 1.03 602
3/0 19 0.85 9 14 1.04 495 16 12 1.08 715
4/0 19 0.90 11 14 1.10 582 13 10 1.18 875
250 37 0.96 13 14 1.16 663 16 10 1.23 1030
350 37 1.06 18 14 1.28 878 16 9 1.38 1320
500 37 1.19 16 12 1.44 1162 29 10 1.49 1804
750 61 1.40 15 10 1.69 1647 — — — —
1000 61 1.54 16 9 1.90 2150 — — — —

15 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
AWG in lb/kft AWG in lb/kft
Copper 133% Insulation Level (220 mil)
2 7 0.77 6 14 0.97 496 16 14 0.97 630
1 19 0.81 7 14 1.01 576 13 12 1.04 759
1/0 19 0.85 9 14 1.05 686 16 12 1.08 906
2/0 19 0.89 11 14 1.09 815 13 10 1.17 1108
3/0 19 0.94 14 14 1.14 982 16 10 1.22 1336
4/0 19 1.00 18 14 1.20 1193 16 9 1.30 1635
250 37 1.05 13 12 1.31 1390 — — — —
350 37 1.16 18 12 1.41 1847 — — — —
500 37 1.28 17 10 1.58 2556 — — — —
750 61 1.47 20 9 1.80 3682 — — — —
1000 61 1.62 26 9 1.98 4815 — — — —
Aluminum 133% Insulation Level (220 mil)
2 1 0.74 6 14 0.94 336 10 14 0.94 389
2 7 0.76 6 14 0.96 350 10 14 0.96 404
1 19 0.80 6 14 1.00 380 13 14 1.00 474
1/0 1 0.81 6 14 1.00 396 16 14 1.00 530
1/0 19 0.84 6 14 1.04 415 16 14 1.04 550
2/0 19 0.89 7 14 1.08 472 13 12 1.12 655
3/0 19 0.94 9 14 1.13 551 16 12 1.17 771
4/0 19 0.99 11 14 1.19 641 13 10 1.27 934
250 37 1.05 13 14 1.27 745 16 10 1.35 1113
350 37 1.15 18 14 1.37 948 16 9 1.47 1389
500 37 1.28 16 12 1.53 1239 29 10 1.58 1881
750 61 1.49 15 10 1.78 1735 — — — —
1000 61 1.64 16 9 1.99 2250 — — — —

25 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (260 mil)
1 19 0.89 7 14 1.09 624 13 12 1.12 807
1/0 19 0.93 9 14 1.13 736 16 12 1.16 956
2/0 19 0.97 11 14 1.17 867 13 10 1.25 1160
3/0 19 1.02 14 14 1.24 1057 16 10 1.32 1411
4/0 19 1.08 18 14 1.30 1272 16 9 1.40 1714
250 37 1.13 13 12 1.39 1452 — — — —
350 37 1.24 18 12 1.49 1914 — — — —
500 37 1.37 17 10 1.66 2630 — — — —
750 61 1.56 20 9 1.91 3808 — — — —
1000 61 1.70 26 9 2.06 4908 — — — —
Aluminum 100% Insulation Level (260 mil)
1 19 0.88 6 14 1.08 427 13 14 1.08 521
1/0 1 0.89 6 14 1.08 443 16 14 1.08 577
1/0 19 0.92 6 14 1.12 465 16 14 1.12 599
2/0 19 0.97 7 14 1.17 524 13 12 1.20 707
3/0 19 1.02 9 14 1.24 624 16 12 1.27 845
4/0 19 1.07 11 14 1.29 719 13 10 1.37 1012
250 37 1.13 13 14 1.35 806 16 10 1.43 1174
350 37 1.23 18 14 1.45 1014 16 9 1.55 1455
500 37 1.36 16 12 1.62 1312 29 10 1.66 1954
750 61 1.57 15 10 1.89 1859 — — — —
1000 61 1.72 16 9 2.07 2342 — — — —

25 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Approximate Outside Diameter in Approximate Net Weight lb/kft
Copper 133% Insulation Level (320 mil)
1 19 1.01 7 14 1.22 710 13 12 1.24 887
1/0 19 1.05 9 14 1.28 846 16 12 1.31 1060
2/0 19 1.09 11 14 1.32 982 13 10 1.39 1268
3/0 19 1.14 14 14 1.37 1156 16 10 1.44 1503
4/0 19 1.20 18 14 1.43 1376 16 9 1.52 1810
250 37 1.26 13 12 1.52 1560 — — — —
350 37 1.36 18 12 1.62 2030 — — — —
500 37 1.49 17 10 1.79 2756 — — — —
750 61 1.68 20 9 2.04 3953 — — — —
1000 61 1.83 26 9 2.19 5065 — — — —
Aluminum 133% Insulation Level (320 mil)
1 19 1.01 6 14 1.20 506 13 14 1.20 599
1/0 1 1.01 6 14 1.21 522 16 14 1.21 656
1/0 19 1.05 6 14 1.27 566 16 14 1.27 700
2/0 19 1.09 7 14 1.31 629 13 12 1.34 812
3/0 19 1.14 9 14 1.36 715 16 12 1.39 935
4/0 19 1.20 11 14 1.42 814 13 10 1.49 1107
250 37 1.25 13 14 1.47 906 16 10 1.55 1273
350 37 1.35 18 14 1.57 1121 16 9 1.67 1563
500 37 1.48 16 12 1.74 1429 29 10 1.78 2070
750 61 1.69 15 10 2.01 1995 — — — —
1000 61 1.84 16 9 2.19 2489 — — — —

35 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (345 mil)
1/0 19 1.10 9 14 1.33 884 16 12 1.36 1098
2/0 19 1.15 11 14 1.37 1021 13 10 1.44 1307
3/0 19 1.20 14 14 1.42 1198 16 10 1.49 1545
4/0 19 1.25 18 14 1.48 1419 16 9 1.57 1853
250 37 1.31 13 12 1.57 1605 — — — —
350 37 1.41 18 12 1.67 2079 — — — —
500 37 1.54 17 10 1.87 2850 — — — —
750 61 1.73 20 9 2.09 4013 — — — —
1000 61 1.88 26 9 2.24 5129 — — — —
Aluminum 100% Insulation Level (345 mil)
1/0 1 1.06 6 14 1.28 578 16 14 1.28 712
1/0 19 1.10 6 14 1.32 604 16 14 1.32 738
2/0 19 1.14 7 14 1.36 668 13 12 1.39 851
3/0 19 1.19 9 14 1.41 756 16 12 1.44 976
4/0 19 1.25 11 14 1.47 856 13 10 1.54 1149
250 37 1.30 13 14 1.52 950 16 10 1.60 1317
350 37 1.40 18 14 1.62 1169 16 9 1.73 1610
500 37 1.53 16 12 1.82 1521 29 10 1.86 2162
750 61 1.74 15 10 2.07 2054 — — — —
1000 61 1.89 16 9 2.24 2553 — — — —

35 kV TR-XLPE Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 133% Insulation Level (420 mil)
1/0 19 1.25 9 14 1.48 1002 16 12 1.51 1222
2/0 19 1.30 11 14 1.52 1144 13 10 1.60 1436
3/0 19 1.35 14 14 1.57 1324 16 10 1.65 1678
4/0 19 1.40 18 14 1.63 1551 16 9 1.73 1992
250 37 1.46 13 12 1.72 1742 — — — —
350 37 1.56 18 12 1.85 2267 — — — —
500 37 1.69 17 10 2.02 3012 — — — —
750 61 1.88 20 9 2.24 4192 — — — —
1000 61 2.03 26 9 2.39 5323 — — — —
Aluminum 133% Insulation Level (420 mil)
1/0 19 1.25 6 14 1.47 726 16 14 1.47 860
2/0 19 1.29 7 14 1.51 795 13 12 1.54 978
3/0 19 1.34 9 14 1.56 887 16 12 1.59 1107
4/0 19 1.40 11 14 1.62 993 13 10 1.69 1285
250 37 1.45 13 14 1.67 1092 16 10 1.75 1459
350 37 1.56 18 14 1.81 1361 16 9 1.91 1802
500 37 1.68 16 12 1.97 1688 29 10 2.01 2329
750 61 1.89 15 10 2.22 2241 — — — —
1000 61 2.04 16 9 2.39 2754 — — — —

Primary UD EPR Insulated, Concentric Neutral 15 kV – 35 kV

Features

Low tension stripping compounds.

Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.

True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.

Application

Underground primary residential and commercial distribution circuits.

May be used in wet or dry locations, installed in underground ducts or direct burial.

Standards

ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.

AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.

Specifications

Maximum operating voltage:

• 5 kV – 46 kV, 100 and 133% IL

Maximum conductor operation temperatures:

  • Wet and dry locations
  • Normal: 105 °C
  • Emergency: 140 °C
  • Short Circuit: 250 °C

Engineering Information

1. Conductor: Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.

On request, strand filled.

Sizes: 8 AWG – 1000 kcmil.

On request, larger sizes.

2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).

On request, super-clean and super-smooth materials.

3. Insulation: Thermoset ethylene propylene rubber (EPR).

On request, amorphous EPR.

4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).

5. Concentric Neutral: Tinned coated soft annealed solid copper wires per ASTM B3 and B33, helically applied and uniformly spaced.

Full or 1/3 Neutral.

On request, a Contra-helical Wire can be applied.

Technical Data

15 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (175 mils)
2 7 0.68 6 14 0.88 485 16 14 0.88 619
1 19 0.71 7 14 0.91 566 13 12 0.95 749
1/0 19 0.75 9 14 0.95 676 16 12 0.99 896
2/0 19 0.80 11 14 1.00 806 13 10 1.07 1099
3/0 19 0.85 14 14 1.05 974 16 10 1.12 1328
4/0 19 0.90 18 14 1.10 1186 16 9 1.20 1627
250 37 0.96 13 12 1.19 1362 — — — —
350 37 1.06 18 12 1.32 1840 — — — —
500 37 1.19 17 10 1.49 2551 — — — —
750 61 1.38 20 9 1.71 3681 — — — —
1000 61 1.53 26 9 1.89 4813 — — — —
Aluminum 100% Insulation Level (175 mils)
2 1 0.65 6 14 0.85 325 10 14 0.85 379
2 7 0.67 6 14 0.87 340 10 14 0.87 393
1 19 0.71 6 14 0.91 370 13 14 0.91 464
1/0 1 0.72 6 14 0.91 386 16 14 0.91 520
1/0 19 0.75 6 14 0.95 406 16 14 0.95 540
2/0 19 0.80 7 14 0.99 464 13 12 1.03 647
3/0 19 0.85 9 14 1.04 543 16 12 1.08 763
4/0 19 0.90 11 14 1.10 634 13 10 1.18 927
250 37 0.96 13 14 1.16 719 16 10 1.23 1086
350 37 1.06 18 14 1.28 942 16 9 1.38 1383
500 37 1.19 16 12 1.44 1235 29 10 1.49 1876
750 61 1.40 15 10 1.69 1734 — — — —
1000 61 1.54 16 9 1.90 2248 — — — —

15 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 133% Insulation Level (220 mils)
2 7 0.77 6 14 0.97 545 16 14 0.97 679
1 19 0.81 7 14 1.01 629 13 12 1.04 812
1/0 19 0.85 9 14 1.05 743 16 12 1.08 963
2/0 19 0.89 11 14 1.09 876 13 10 1.17 1168
3/0 19 0.94 14 14 1.14 1047 16 10 1.22 1401
4/0 19 1.00 18 14 1.20 1264 16 9 1.30 1705
250 37 1.05 13 12 1.31 1465 — — — —
350 37 1.16 18 12 1.41 1932 — — — —
500 37 1.28 17 10 1.58 2652 — — — —
750 61 1.47 20 9 1.80 3796 — — — —
1000 61 1.62 26 9 1.98 4942 — — — —
Aluminum 133% Insulation Level (220 mils)
2 1 0.74 6 14 0.94 382 10 14 0.94 436
2 7 0.76 6 14 0.96 399 10 14 0.96 453
1 19 0.80 6 14 1.00 432 13 14 1.00 526
1/0 1 0.81 6 14 1.00 448 16 14 1.00 583
1/0 19 0.84 6 14 1.04 471 16 14 1.04 606
2/0 19 0.89 7 14 1.08 532 13 12 1.12 715
3/0 19 0.94 9 14 1.13 615 16 12 1.17 835
4/0 19 0.99 11 14 1.19 711 13 10 1.27 1004
250 37 1.05 13 14 1.27 820 16 10 1.35 1187
350 37 1.15 18 14 1.37 1032 16 9 1.47 1473
500 37 1.28 16 12 1.53 1335 29 10 1.58 1976
750 61 1.49 15 10 1.78 1849 — — — —
1000 61 1.64 16 9 1.99 2377 — — — —

25 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lbs/kft AWG in lbs/kft
Copper 100% Insulation Level (260 mils)
1 19 0.89 7 14 1.09 691 13 12 1.12 874
1/0 19 0.93 9 14 1.13 807 16 12 1.16 1027
2/0 19 0.97 11 14 1.17 943 13 10 1.25 1236
3/0 19 1.02 14 14 1.24 1139 16 10 1.32 1493
4/0 19 1.08 18 14 1.30 1360 16 9 1.40 1801
250 37 1.13 13 12 1.39 1545 — — — —
350 37 1.24 18 12 1.49 2019 — — — —
500 37 1.37 17 10 1.66 2748 — — — —
750 61 1.56 20 9 1.91 3947 — — — —
1000 61 1.70 26 9 2.06 5063 — — — —
Aluminum 100% Insulation Level (260 mils)
1 19 0.88 6 14 1.08 493 13 14 1.08 587
1/0 1 0.89 6 14 1.08 510 16 14 1.08 644
1/0 19 0.92 6 14 1.12 535 16 14 1.12 669
2/0 19 0.97 7 14 1.17 599 13 12 1.20 782
3/0 19 1.02 9 14 1.24 705 16 12 1.27 925
4/0 19 1.07 11 14 1.29 805 13 10 1.37 1098
250 37 1.13 13 14 1.35 899 16 10 1.43 1266
350 37 1.23 18 14 1.45 1118 16 9 1.55 1559
500 37 1.36 16 12 1.62 1429 29 10 1.66 2071
750 61 1.57 15 10 1.89 1998 — — — —
1000 61 1.72 16 9 2.07 2497 — — — —

25 kV EPR Insulated

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kdt AWG in lb/kit
Copper 133% Insulation Level (320 mils)
1 19 1.01 7 14 1.21 795 13 12 1.24 977
1/0 19 1.05 9 14 1.27 936 16 12 1.31 1155
2/0 19 1.09 11 14 1.32 1077 13 10 1.39 1369
3/0 19 1.14 14 14 1.37 1258 16 10 1.44 1612
4/0 19 1.20 18 14 1.42 1485 16 9 1.52 1926
250 37 1.26 13 12 1.51 1676 — — — —
350 37 1.36 18 12 1.62 2160 — — — —
500 37 1.49 17 10 1.79 2902 — — — —
750 61 1.68 20 9 2.03 4123 — — — —
1000 61 1.83 26 9 2.18 5254 — — — —
Aluminum 133% Insulation Level (320 mils)
1/0 19 1.05 6 14 1.27 661 16 14 1.27 795
2/0 19 1.09 7 14 1.31 730 13 12 1.34 913
3/0 19 1.14 9 14 1.36 822 16 12 1.39 1042
4/0 19 1.20 11 14 1.42 928 13 10 1.49 1221
250 37 1.25 13 14 1.47 1027 16 10 1.55 1395
350 37 1.35 18 14 1.57 1256 16 9 1.67 1698
500 37 1.48 16 12 1.74 1581 29 10 1.78 2223
750 61 1.69 15 10 2.01 2174 — — — —
1000 61 1.84 16 9 2.19 2688 — — — —

35 kV ERP Insulation

Size AWG or kcmil Number of Strands Nominal OD Over Insulation 1/3 Neutral Full Neutral
Number of Wires Size Approximate Outside Diameter Approximate Net Weight Number of Wires Size Approximate Outside Diameter Approximate Net Weight
in AWG in lb/kft AWG in lb/kft
Copper 100% Insulation Level (345 mils)
1/0 19 1.10 9 14 1.32 985 16 12 1.36 1205
2/0 19 1.15 11 14 1.37 1128 13 10 1.44 1421
3/0 19 1.20 14 14 1.42 1311 16 10 1.49 1665
4/0 19 1.25 18 14 1.47 1540 16 9 1.57 1982
250 37 1.31 13 12 1.56 1734 — — — —
350 37 1.41 18 12 1.67 2222 — — — —
500 37 1.54 17 10 1.87 3012 — — — —
750 61 1.73 20 9 2.08 4200 — — — —
1000 61 1.88 26 9 2.23 5338 — — — —
Aluminum 100% Insulation Level (345 mils)
1/0 1 1.06 6 14 1.28 678 16 14 1.28 812
1/0 19 1.10 6 14 1.32 709 16 14 1.32 844
2/0 19 1.14 7 14 1.36 780 13 12 1.39 963
3/0 19 1.19 9 14 1.41 875 16 12 1.44 1095
4/0 19 1.25 11 14 1.47 983 13 10 1.54 1276
250 37 1.30 13 14 1.52 1085 16 10 1.60 1452
350 37 1.40 18 14 1.62 1318 16 9 1.73 1759
500 37 1.53 16 12 1.82 1688 29 10 1.86 2329
750 61 1.74 15 10 2.07 2251 — — — —
1000 61 1.89 16 9 2.24 2771 — — — —
Copper 133% Insulation Level (420 mils)
1/0 19 1.25 9 14 1.48 1146 16 12 1.51 1366
2/0 19 1.30 11 14 1.52 1295 13 10 1.60 1587
3/0 19 1.35 14 14 1.57 1484 16 10 1.65 1838
4/0 19 1.40 18 14 1.63 1721 16 9 1.73 2162
250 37 1.46 13 12 1.72 1921 — — — —
350 37 1.56 18 12 1.85 2464 — — — —
500 37 1.69 17 10 2.02 3232 — — — —
750 61 1.88 20 9 2.24 4445 — — — —
1000 61 2.03 26 9 2.39 5601 — — — —
Aluminum 133% Insulation Level (420 mils)
1/0 19 1.25 6 14 1.47 868 16 14 1.47 1002
2/0 19 1.29 7 14 1.51 944 13 12 1.54 1127
3/0 19 1.34 9 14 1.56 1045 16 12 1.59 1265
4/0 19 1.40 11 14 1.62 1160 13 10 1.69 1453
250 37 1.45 13 14 1.67 1269 16 10 1.75 1636
350 37 1.56 18 14 1.81 1556 16 9 1.91 1997
500 37 1.68 16 12 1.97 1905 29 10 2.01 2546
750 61 1.89 15 10 2.22 2493 — — — —
1000 61 2.04 16 9 2.39 3032 — — — —

Certificate Display

ISO 9001 Quality Management System
ISO 9001 Certificate (2025–2028)
ISO 9001 Certificate (NOA)
CE — Verification of Conformity
RoHS Compliance Attestation (EU)
Low Voltage Directive Attestation (EU)

Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.

Factory Tour

Why Choose Us

50+ years of experience Trusted manufacturing expertise since 1969
International standards IEC, ASTM, BS, CSA and other global standards
Strict quality control Comprehensive testing throughout production
Large production capacity Reliable supply for utility and EPC projects
Fast global delivery Efficient manufacturing and worldwide shipping
Technical support Expert assistance from inquiry to project completion

Packing & Shipping

  • Wooden, steel or steel-wood drums; drum length to customer requirement
  • Drum marking per customer / utility specification
  • Both drum ends sealed and protected for sea freight
Get in touch

Ready for Your Next Cable Project?

Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.

  • Emailinfo@qzcablegroup.com
  • WhatsApp / WeChat+86 173 3570 4553
  • Contact personChloe · Export Department
  • Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China

    The more specific the standard and size, the faster we can quote.
    Inquiry WhatsApp Email