AAAC — Aluminum Alloy Conductor
AAAC- The full name: All aluminium alloy conductor. AAAC contains a small percentage (about 0.6%) of silicon and magnesium elements. It provides several benefits for overhead lines.
- Standards: Basic design to: AS 1531
- AAAC cable bvconsists of aluminum alloy wires.
- Basic design to: AS 1531
Product Description
Application
AAAC- The full name: All aluminium alloy conductor. AAAC contains a small percentage (about 0.6%) of silicon and magnesium elements. It provides several benefits for overhead lines.
7 and 19 strand construction is suitable for bare overhead reticulation of medium spans, normally at low and medium voltages. 37 and 61 strand construction is suitable for transmission and sub transmission lines where homogeneous construction can reduce line losses and improve corrosion resistance in conductors with similar strength to ACSR types.
Standard
Construction
AAAC cable bvconsists of aluminum alloy wires. The aluminum alloy wires are concentrically stranded.
This section deals with heat-treatable magnesium silicon type aluminium alloys to the applicable International Standard, the electrical and mechanical properties of which all fall within the values suggested by relevant standard.
Conductors to all other recognized specifications can also be supplied. The alloys referred to have higher strength but lower conductivity than pure aluminium.
Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR; Having lower breaking loads than the later, their use becomes particularly favourable when ice and wind loadings are low.
Electrical Properties
| Density@20ºC | 2.70 kg/dm |
| Temperature Coefficient@20°C | 0.00360 (°C) |
| Resistivity@20°C | 0.0326 Ohms mm²/m |
| Linear Expansivity | 23 x10-6(°C) |
Service Conditions
| Ambient Temperature | -5°C – 50°C |
| Wind Pressure | 80 – 130kg/m² |
| Seismic Acceleration | 0.12 – 0.05g |
| Isokeraunic Level | 10 – 18 |
| Relative Humidity | 5 – 100% |
Construction Parameters
Technical Data
IEC 61089
| CODE | AL NOMINAL AREA | MAXIMUM RESISTANCE DC AT 20º | CURRENT RATING | ||
| TEMPERATE | TROPICAL | ||||
| MM² | Ω / KM | Ω / 1000FT | AMP | AMP | |
| – | – | 2.87 | 0.873 | 90 | 73 |
| Box | – | 1.79 | 0.544 | 121 | 98 |
| Acacia | – | 1.4 | 0.426 | 140 | 114 |
| Almond | 25 | 1.11 | 0.339 | 162 | 131 |
| Ceda | 30 | 0.944 | 0.288 | 180 | 145 |
| – | 40 | 0.794 | 0.242 | 200 | 162 |
| Fir | 50 | 0.7 | 0.213 | 217 | 175 |
| Hazel | 100 | 0.559 | 0.17 | 250 | 201 |
| Pine | – | 0.467 | 0.142 | 279 | 224 |
| – | – | 0.398 | 0.121 | 309 | 247 |
| Willow | 150 | 0.373 | 0.114 | 322 | 258 |
| – | 175 | 0.347 | 0.106 | 337 | 270 |
| – | 300 | 0.308 | 0.0938 | 343 | 290 |
| Oak | – | 0.282 | 0.0859 | 384 | 307 |
| – | – | 0.282 | 0.086 | 385 | 307 |
| Mulberry | – | 0.222 | 0.0676 | 448 | 356 |
| Ash | – | 0.185 | 0.0565 | 501 | 398 |
| Elm | – | 0.159 | 0.048 | 553 | 438 |
| Poplar | – | 0.14 | 0.0427 | 598 | 473 |
| – | – | 0.124 | 0.0337 | 647 | 511 |
| Sycamore | – | 0.111 | 0.0377 | 694 | 547 |
| Upas | – | 0.0925 | 0.0282 | 776 | 610 |
| – | – | 0.0794 | 0.0242 | 854 | 669 |
| Yew | – | 0.0698 | 0.0213 | 925 | 723 |
ASTM
| CODE | AL NOMINAL AREA | MAXIMUM RESISTANCE DC AT 20º | CURRENT RATING | ||
| TEMPERATE | TROPICAL | ||||
| MM² | Ω / KM | Ω / 1000FT | AMP | AMP | |
| – | – | 2.87 | 0.873 | 90 | 73 |
| Box | – | 1.79 | 0.544 | 121 | 98 |
| Acacia | – | 1.4 | 0.426 | 140 | 114 |
| Almond | 25 | 1.11 | 0.339 | 162 | 131 |
| Ceda | 30 | 0.944 | 0.288 | 180 | 145 |
| – | 40 | 0.794 | 0.242 | 200 | 162 |
| Fir | 50 | 0.7 | 0.213 | 217 | 175 |
| Hazel | 100 | 0.559 | 0.17 | 250 | 201 |
| Pine | – | 0.467 | 0.142 | 279 | 224 |
| – | – | 0.398 | 0.121 | 309 | 247 |
| Willow | 150 | 0.373 | 0.114 | 322 | 258 |
| – | 175 | 0.347 | 0.106 | 337 | 270 |
| – | 300 | 0.308 | 0.0938 | 343 | 290 |
| Oak | – | 0.282 | 0.0859 | 384 | 307 |
| – | – | 0.282 | 0.086 | 385 | 307 |
| Mulberry | – | 0.222 | 0.0676 | 448 | 356 |
| Ash | – | 0.185 | 0.0565 | 501 | 398 |
| Elm | – | 0.159 | 0.048 | 553 | 438 |
| Poplar | – | 0.14 | 0.0427 | 598 | 473 |
| – | – | 0.124 | 0.0337 | 647 | 511 |
| Sycamore | – | 0.111 | 0.0377 | 694 | 547 |
| Upas | – | 0.0925 | 0.0282 | 776 | 610 |
| – | – | 0.0794 | 0.0242 | 854 | 669 |
| Yew | – | 0.0698 | 0.0213 | 925 | 723 |
BS EN 50182
| CODE | AL NOMINAL AREA | MAXIMUM RESISTANCE DC AT 20º | CURRENT RATING | ||
| TEMPERATE | TROPICAL | ||||
| MM² | Ω / KM | Ω / 1000FT | AMP | AMP | |
| – | – | 2.87 | 0.873 | 90 | 73 |
| Box | – | 1.79 | 0.544 | 121 | 98 |
| Acacia | – | 1.4 | 0.426 | 140 | 114 |
| Almond | 25 | 1.11 | 0.339 | 162 | 131 |
| Ceda | 30 | 0.944 | 0.288 | 180 | 145 |
| – | 40 | 0.794 | 0.242 | 200 | 162 |
| Fir | 50 | 0.7 | 0.213 | 217 | 175 |
| Hazel | 100 | 0.559 | 0.17 | 250 | 201 |
| Pine | – | 0.467 | 0.142 | 279 | 224 |
| – | – | 0.398 | 0.121 | 309 | 247 |
| Willow | 150 | 0.373 | 0.114 | 322 | 258 |
| – | 175 | 0.347 | 0.106 | 337 | 270 |
| – | 300 | 0.308 | 0.0938 | 343 | 290 |
| Oak | – | 0.282 | 0.0859 | 384 | 307 |
| – | – | 0.282 | 0.086 | 385 | 307 |
| Mulberry | – | 0.222 | 0.0676 | 448 | 356 |
| Ash | – | 0.185 | 0.0565 | 501 | 398 |
| Elm | – | 0.159 | 0.048 | 553 | 438 |
| Poplar | – | 0.14 | 0.0427 | 598 | 473 |
| – | – | 0.124 | 0.0337 | 647 | 511 |
| Sycamore | – | 0.111 | 0.0377 | 694 | 547 |
| Upas | – | 0.0925 | 0.0282 | 776 | 610 |
| – | – | 0.0794 | 0.0242 | 854 | 669 |
| Yew | – | 0.0698 | 0.0213 | 925 | 723 |
DIN 48201
| CODE | AL NOMINAL AREA | MAXIMUM RESISTANCE DC AT 20º | CURRENT RATING | ||
| TEMPERATE | TROPICAL | ||||
| MM² | Ω / KM | Ω / 1000FT | AMP | AMP | |
| – | – | 2.87 | 0.873 | 90 | 73 |
| Box | – | 1.79 | 0.544 | 121 | 98 |
| Acacia | – | 1.4 | 0.426 | 140 | 114 |
| Almond | 25 | 1.11 | 0.339 | 162 | 131 |
| Ceda | 30 | 0.944 | 0.288 | 180 | 145 |
| – | 40 | 0.794 | 0.242 | 200 | 162 |
| Fir | 50 | 0.7 | 0.213 | 217 | 175 |
| Hazel | 100 | 0.559 | 0.17 | 250 | 201 |
| Pine | – | 0.467 | 0.142 | 279 | 224 |
| – | – | 0.398 | 0.121 | 309 | 247 |
| Willow | 150 | 0.373 | 0.114 | 322 | 258 |
| – | 175 | 0.347 | 0.106 | 337 | 270 |
| – | 300 | 0.308 | 0.0938 | 343 | 290 |
| Oak | – | 0.282 | 0.0859 | 384 | 307 |
| – | – | 0.282 | 0.086 | 385 | 307 |
| Mulberry | – | 0.222 | 0.0676 | 448 | 356 |
| Ash | – | 0.185 | 0.0565 | 501 | 398 |
| Elm | – | 0.159 | 0.048 | 553 | 438 |
| Poplar | – | 0.14 | 0.0427 | 598 | 473 |
| – | – | 0.124 | 0.0337 | 647 | 511 |
| Sycamore | – | 0.111 | 0.0377 | 694 | 547 |
| Upas | – | 0.0925 | 0.0282 | 776 | 610 |
| – | – | 0.0794 | 0.0242 | 854 | 669 |
| Yew | – | 0.0698 | 0.0213 | 925 | 723 |
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
GAP — Gap Type Aluminum Conductor Steel Reinforced Gap Conductor
High Temperature Thermal Resistant Alloy Conductor : Aluminum-Zirconium wires (Type-AT1 or AT3), concentrically stranded over a steel core having a small gap between the Steel core & thermal-resistant aluminum alloy layer. These combination offers best Mechanical as well as Electrical…
AAC — All Aluminum Conductor
AAC conductor is also known as aluminium stranded conductor. It is manufactured from electrolytically refined aluminium, with a minimum purity of 99.7%.
ACS — Aluminum Clad Steel Wire
The aluminum clad steel wire internationally known as Alumoweld or ACS is widely used in long-span transmission line, coastal areas and island as well as other hot and humid regions, salt fog regions and heavily polluted regions where the high corrosion resistance strand is needed.
STACIR — Steel Reinforced Aluminum Conductor Invar Reinforced Trapezoidal Wire
Super Thermal Alloy Conductor Invar Reinforced (STACIR) conductor has outer layers composed of Super Thermal Aluminium (STAL) alloy wires that can operate up to 210°C (410°F). The inner core is composed of aluminium clad INVAR wires. INVAR is a metal alloy with 36% Ni in steel.
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions