GAP — Gap Type Aluminum Conductor Steel Reinforced Gap Conductor
High Temperature Thermal Resistant Alloy Conductor : Aluminum-Zirconium wires (Type-AT1 or AT3), concentrically stranded over a steel core having a small gap between the Steel core & thermal-resistant aluminum alloy layer. These combination offers best Mechanical as well as Electrical…
- Aluminium-Zirconium wires (Type-AT3 or AT-1), concentrically stranded over a steel core maintaing gap between the Steel core and…
- Basic design to:
Product Description
Application
High Temperature Thermal Resistant Alloy Conductor : Aluminum-Zirconium wires (Type-AT1 or AT3), concentrically stranded over a steel core having a small gap between the Steel core & thermal-resistant aluminum alloy layer. These combination offers best Mechanical as well as Electrical Characteristics. Extra High Strength Galvanized Steel (EST); or aluminum-claded Extra High Strength Steel (AW). Additional corrosion protection is achieved as High Temperature Grease is applied in Between GAP of Conductor.
Standard
Basic design to:
Thermal-resistant aluminium alloy wires (Type-AT3 or AT1) for overhead line conductor as per IEC 62004
- Concentric lay stranded overhead electrical conductors IEC 61089, IEC 62420
- Zinc-coated steel wires for stranded conductors IEC 888, ASTM B957 & more
- Zinc–5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire EN 50540, ASTM B802, ASTM B803 or ASTM B958.
- Aluminium Clad Steel Wires, IEC 61232, ASTM B415, EN 50540 & More
Construction
Aluminium-Zirconium wires (Type-AT3 or AT-1), concentrically stranded over a steel core maintaing gap between the Steel core and first Aluminium Layer.
Features:
- These can operate upto 210°C with specified strength loss,
- Can carry 100~150% more current as that of ACSR of the same size.
- For uprating lines, no modifications or reinforcement is required to the existing towers
- Limiting the sag increase with the increase of the temperature by the thermal expansion coefficient above knee-point related to the steel core
Construction Parameters
GTACSR & GZTACSR
| Conductor Size | Stranding | Cross-Sectional Area | Diameter of Complete Conductor | Weight | Rated Strength | DCResistance @20°C | ||||||||
| No. of Wires | Wire diameter | TAL | Steel | Total | TAL | Steel | Total with Grease | Extra High Strength | Ultra High Strength | |||||
| TAL | Steel | TAL | Steel | |||||||||||
| (mm²) | (No.) | (No.) | (mm) | (mm) | (mm²) | (mm²) | (mm²) | (mm) | (Kg/Km) | (Kg/Km) | (Kg/Km) | (KN) | (KN) | (Ω/Km) |
| 175 | 8/12 | 7 | 3.35 (TW) | 2.10 | 176.20 | 24.25 | 200.45 | 17.50 | 486.98 | 189.44 | 691.42 | 66.14 | 66.87 | 0.1668 |
| 190 | 12/16 | 7 | 2.92 (TW) | 2.30 | 187.30 | 29.08 | 216.38 | 18.20 | 517.66 | 227.24 | 761.90 | 74.44 | 75.46 | 0.1569 |
| 195 | 20/12 | 7 | 2.40(R) 2.88(TW) | 2.20 | 168.80 | 26.61 | 195.41 | 18.06 | 466.53 | 207.91 | 690.44 | 69.51 | 70.31 | 0.1741 |
| 218 | 18/12 | 7 | 2.78(R) 2.94(TW) | 2.25 | 190.50 | 27.83 | 218.33 | 19.10 | 526.51 | 217.47 | 759.98 | 74.47 | 75.31 | 0.1542 |
| 240 | 8/12 | 7 | 4.02 (TW) | 2.40 | 253.40 | 31.67 | 285.07 | 20.60 | 700.35 | 247.43 | 964.78 | 88.34 | 89.45 | 0.1159 |
| 248 | 12/8 | 7 | 3.71(TW) | 2.40 | 216.12 | 31.67 | 247.79 | 19.40 | 597.32 | 247.43 | 862.75 | 83.00 | 84.11 | 0.1360 |
| 287 | 18/12 | 7 | 3.15(R) 3.43(TW) | 2.55 | 251.00 | 35.75 | 286.75 | 21.77 | 693.72 | 279.33 | 993.04 | 94.85 | 96.10 | 0.1171 |
| 287 | 20/12 | 7 | 2.90(R) 3.55(TW) | 2.55 | 251.00 | 35.75 | 286.75 | 21.77 | 693.72 | 279.33 | 993.04 | 95.33 | 96.58 | 0.1171 |
| 310 | 16/12 | 7 | 3.90(R) 3.69(TW) | 2.80 | 319.40 | 43.10 | 362.50 | 24.40 | 882.76 | 336.78 | 1241.54 | 116.10 | 117.60 | 0.0920 |
| 400 | 18/12 | 7 | 3.90(R) 4.45(TW) | 2.80 | 401.40 | 43.10 | 444.50 | 26.90 | 1109.40 | 336.78 | 1468.18 | 129.16 | 130.67 | 0.0732 |
| 410 | 14/12 | 7 | 4.90(R) 3.99(TW) | 3.00 | 414.00 | 49.48 | 463.48 | 27.60 | 1144.22 | 386.61 | 1554.83 | 138.95 | 140.68 | 0.0710 |
| 439 | 15/12 | 7 | 4.50(R) 4.04(TW) | 2.90 | 392.50 | 46.24 | 438.74 | 26.84 | 1084.80 | 361.27 | 1469.07 | 132.44 | 134.06 | 0.0749 |
| 462 | 14/12 | 7 | 4.90(R) 3.99(TW) | 2.95 | 414.30 | 47.84 | 462.14 | 27.60 | 1145.05 | 373.83 | 1542.88 | 136.47 | 138.14 | 0.0709 |
| 540 | 24/14/10 | 7 | 3.55(R) 3.98(TW) | 3.10 | 536.20 | 52.83 | 589.03 | 31.30 | 1483.12 | 412.81 | 1920.93 | 164.15 | 166.00 | 0.0548 |
| 620 | 16/12/12 | 7 | 4.80(TW) 4.75(TW) 3.47(TW) | 3.20 | 615.70 | 56.30 | 672.00 | 31.50 | 1703.01 | 439.88 | 2168.89 | 177.96 | 179.93 | 0.0478 |
GTACSR/AW & GZTACSR/AW
| Conductor Size | Cross-Sectional Area | Stranding | Diameter of Complete Conductor | Weight | Rated Strength | DC Resistance @20°C | ||||||||
| STAL | Steel | Total | No. of STAL Wires | No. of STAL Layers | No. of Steel Wires | Dia. of Steel Wires | STAL | Steel | Total | High Strength | Extra High Strength | |||
| (mm²) | (mm²) | (mm²) | (mm²) | (No.) | (No.) | (No.) | (mm) | (mm) | (Kg/Km) | (Kg/Km) | (Kg/Km) | (KN) | (KN) | (Ω/Km) |
| 175 | 8/12 | 7 | 3.35 (TW) | 2.10 | 176.20 | 24.25 | 200.45 | 17.50 | 486.98 | 160.46 | 647.44 | 57.65 | 62.26 | 0.1593 |
| 190 | 12/16 | 7 | 2.92 (TW) | 2.30 | 187.30 | 29.08 | 216.38 | 18.20 | 517.66 | 192.48 | 710.14 | 65.28 | 69.93 | 0.1490 |
| 195 | 20/12 | 7 | 2.40(R) 2.88(TW) | 2.20 | 168.80 | 26.61 | 195.41 | 18.06 | 466.53 | 176.11 | 642.64 | 60.20 | 65.25 | 0.1652 |
| 218 | 18/12 | 7 | 2.78(R) 2.94(TW) | 2.25 | 190.50 | 27.83 | 218.33 | 19.10 | 526.51 | 184.21 | 710.72 | 64.73 | 70.02 | 0.1470 |
| 240 | 8/12 | 7 | 4.02 (TW) | 2.40 | 253.40 | 31.67 | 285.07 | 20.60 | 700.35 | 209.59 | 909.94 | 78.36 | 83.43 | 0.1112 |
| 248 | 12/8 | 7 | 3.71(TW) | 2.40 | 216.12 | 31.67 | 247.79 | 19.40 | 597.32 | 209.59 | 806.91 | 73.03 | 78.09 | 0.1295 |
| 287 | 18/12 | 7 | 3.15(R) 3.43(TW) | 2.55 | 251.00 | 35.75 | 286.75 | 21.77 | 693.72 | 236.60 | 930.32 | 83.59 | 89.31 | 0.1117 |
| 287 | 20/12 | 7 | 2.90(R) 3.55(TW) | 2.55 | 251.00 | 35.75 | 286.75 | 21.77 | 693.72 | 26.60 | 720.32 | 84.07 | 89.79 | 0.1117 |
| 310 | 16/12 | 7 | 3.90(R) 3.69(TW) | 2.80 | 319.40 | 43.10 | 362.50 | 24.40 | 882.76 | 285.27 | 1168.03 | 102.52 | 109.41 | 0.0880 |
| 400 | 18/12 | 7 | 3.90(R) 4.45(TW) | 2.80 | 401.40 | 43.10 | 444.50 | 26.90 | 1109.40 | 285.27 | 1394.67 | 115.59 | 122.48 | 0.0706 |
| 410 | 14/12 | 7 | 4.90(R) 3.99(TW) | 3.00 | 414.00 | 49.48 | 463.48 | 27.60 | 1144.22 | 327.48 | 1471.70 | 123.36 | 131.28 | 0.0682 |
| 439 | 15/12 | 7 | 4.50(R) 4.04(TW) | 2.90 | 392.50 | 46.24 | 438.74 | 26.84 | 1084.80 | 306.00 | 1390.80 | 117.87 | 125.27 | 0.0720 |
| 462 | 14/12 | 7 | 4.90(R) 3.99(TW) | 2.95 | 414.30 | 47.84 | 462.14 | 27.60 | 1145.05 | 316.65 | 1461.70 | 121.40 | 129.05 | 0.0682 |
| 540 | 24/14/10 | 7 | 3.55(R) 3.98(TW) | 3.10 | 536.20 | 52.83 | 589.03 | 31.30 | 1483.12 | 349.67 | 1832.79 | 149.36 | 156.23 | 0.0536 |
| 620 | 16/12/12 | 7 | 4.80(TW) 4.75(TW) 3.47(TW) | 3.20 | 615.70 | 56.30 | 672.00 | 31.50 | 1703.01 | 372.60 | 2075.61 | 162.19 | 169.51 | 0.0467 |
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
CCS — Copper Clad Steel Conductor
Copper clad steel wire is composed of stranded copper clad monofilament, widely applied for grounding and lightning protection, electrostatic grounding protection, protective grounding, grounding wire of electrical and petrochemical system in areas covering high-frequency coaxial cable, electrified…
AAC — All Aluminum Conductor
AAC conductor is also known as aluminium stranded conductor. It is manufactured from electrolytically refined aluminium, with a minimum purity of 99.7%.
AACSR — Aluminum Alloy Conductor Steel Reinforced
The all aluminum alloy conductor steel reinforced is used for the power transmission lines with large span length installed under various severe weather conditions like snow, ice, storms, and so on. AACSR offers optimal strength for line design. Variable steel core stranding enables the desired…
ACS — Aluminum Clad Steel Wire
The aluminum clad steel wire internationally known as Alumoweld or ACS is widely used in long-span transmission line, coastal areas and island as well as other hot and humid regions, salt fog regions and heavily polluted regions where the high corrosion resistance strand is needed.
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions