STACIR — Steel Reinforced Aluminum Conductor Invar Reinforced Trapezoidal Wire
Super Thermal Alloy Conductor Invar Reinforced (STACIR) conductor has outer layers composed of Super Thermal Aluminium (STAL) alloy wires that can operate up to 210°C (410°F). The inner core is composed of aluminium clad INVAR wires. INVAR is a metal alloy with 36% Ni in steel.
- Core Wire (INVAR) : Aluminum-clad INVAR Wire/High Tensile Strength Aluminum-clad INVAR Wire Conductor (STAl) : Super Thermal…
- Basic design to IEC, ASTM, JCS 1405 standard
Product Description
Application
Super Thermal Alloy Conductor Invar Reinforced (STACIR) conductor has outer layers composed of Super Thermal Aluminium (STAL) alloy wires that can operate up to 210°C (410°F). The inner core is composed of aluminium clad INVAR wires. INVAR is a metal alloy with 36% Ni in steel.
STACIR/AW conductors are suited for re-conductoring applications. The capacity of existing transmission line can be enhanced by simply replacing the existing conductor without any modification to the tower.
Hi-STACIR/AW, STACIR/AW is normally used to up-rate an existing transmission line by simply replacing the exisitng conductor without tower modification or reinforcement.
Standard
Basic design to IEC, ASTM, JCS 1405 standard
Construction
Core Wire (INVAR) : Aluminum-clad INVAR Wire/High Tensile Strength Aluminum-clad INVAR Wire
Conductor (STAl) : Super Thermal Resistant Aluminum Alloy Wire used for continuous allowable temperature up to 210℃
Benefits
Can carry 100% more current than that of ACSR of the same size, while maximum sag and maximum working tension remain the same as that of ACSR.
No modification or reinforcement is required to existing towers for uprating transmission and distribution lines.
Construction Parameters
SUPER THERMAL RESISTANT ALUMINUM ALLOY CONDUCTOR, ALUMINUM CLAD INVAR REINFORCED (STACIR)
| Conductor Size | Stranding | Cross-Sectional Area | Diameter of Complete Conductor | Weight | Rated Strength |
DC Resistance @ 20°C |
Current Capacity | |||||||||
| No. of Wires | Wire diameter | STAL | Invar | Total | STAL | Steel | Total | |||||||||
| STAL | Invar | STAL | Invar | @ 85°C | @ 150°C | @ 210°C | ||||||||||
| (mm²) | (No.) | (No.) | (mm) | (mm) | (mm²) | (mm²) | (mm²) | (mm) | (Kg/Km) | (Kg/Km) | (Kg/Km) | (KN) | (Ω/Km) | (Ampere) | (Ampere) | (Ampere) |
| 200 | 30 | 7 | 2.60 | 2.60 | 159.28 | 37.17 | 196.44 | 18.20 | 439.31 | 265.01 | 704.32 | 65.38 | 0.1746 | 403 | 690 | 850 |
| 240 | 30 | 7 | 2.90 | 2.90 | 198.16 | 46.24 | 244.39 | 20.30 | 546.54 | 329.69 | 876.23 | 79.92 | 0.1403 | 460 | 794 | 980 |
| 300 | 30 | 7 | 3.20 | 3.20 | 241.27 | 56.30 | 297.57 | 22.40 | 665.47 | 401.43 | 1066.90 | 94.82 | 0.1153 | 518 | 901 | 1114 |
| 300 | 30 | 7 | 3.20 | 3.20 | 241.27 | 56.30 | 297.57 | 22.40 | 665.47 | 401.43 | 1066.90 | 94.82 | 0.1153 | 518 | 901 | 1114 |
| 380 | 26 | 7 | 4.00 | 3.10 | 326.73 | 52.83 | 379.56 | 25.30 | 902.22 | 376.73 | 1278.95 | 104.26 | 0.0866 | 612 | 1076 | 1335 |
| 380 | 26 | 7 | 4.00 | 3.10 | 326.73 | 52.83 | 379.56 | 25.30 | 902.22 | 376.73 | 1278.95 | 104.26 | 0.0866 | 612 | 1076 | 1335 |
| 480 | 26 | 7 | 4.50 | 3.50 | 413.51 | 67.35 | 480.86 | 28.50 | 1141.87 | 480.23 | 1622.10 | 132.42 | 0.0684 | 704 | 1253 | 1559 |
| 480 | 26 | 7 | 4.50 | 3.50 | 413.51 | 67.35 | 480.86 | 28.50 | 1141.87 | 480.23 | 1622.10 | 132.42 | 0.0684 | 704 | 1253 | 1559 |
| 520 | 45 | 7 | 3.70 | 2.47 | 483.85 | 33.54 | 517.39 | 29.61 | 1337.00 | 239.17 | 1576.17 | 113.10 | 0.0597 | 748 | 1336 | 1665 |
| 520 | 45 | 7 | 3.70 | 2.47 | 483.85 | 33.54 | 517.39 | 29.61 | 1337.00 | 239.17 | 1576.17 | 113.10 | 0.0597 | 748 | 1336 | 1665 |
| 590 | 54 | 7 | 3.50 | 3.50 | 519.54 | 67.35 | 586.89 | 31.50 | 1437.04 | 480.23 | 1917.27 | 150.84 | 0.0549 | 790 | 1419 | 1771 |
| 600 | 54 | 7 | 3.53 | 3.53 | 528.49 | 68.51 | 596.99 | 31.77 | 1461.78 | 488.50 | 1950.28 | 152.20 | 0.0540 | 797 | 1434 | 1791 |
| 630 | 54 | 19 | 3.63 | 2.18 | 558.85 | 70.92 | 629.77 | 32.68 | 1545.78 | 507.40 | 2053.17 | 163.93 | 0.0511 | 824 | 1486 | 1857 |
| 690 | 54 | 7 | 3.80 | 3.80 | 612.42 | 79.39 | 691.81 | 34.20 | 1693.95 | 566.08 | 2260.03 | 176.38 | 0.0466 | 869 | 1576 | 1972 |
| 710 | 54 | 19 | 3.85 | 2.31 | 628.65 | 79.63 | 708.27 | 34.65 | 1738.82 | 569.72 | 2308.54 | 182.37 | 0.0454 | 883 | 1602 | 2006 |
| 730 | 45 | 7 | 4.40 | 2.90 | 684.24 | 46.24 | 730.48 | 35.10 | 1890.75 | 329.69 | 2220.44 | 155.82 | 0.0423 | 914 | 1663 | 2084 |
| 770 | 54 | 7 | 4.00 | 4.00 | 678.59 | 87.96 | 766.55 | 36.00 | 1876.95 | 627.24 | 2504.19 | 193.40 | 0.0421 | 922 | 1682 | 2108 |
| 800 | 54 | 19 | 4.09 | 2.45 | 709.47 | 89.57 | 799.04 | 36.79 | 1962.37 | 640.86 | 2603.23 | 205.51 | 0.0403 | 946 | 1729 | 2169 |
| 900 | 54 | 19 | 4.34 | 2.61 | 798.85 | 101.65 | 900.50 | 39.09 | 2209.60 | 727.30 | 2936.90 | 230.40 | 0.0357 | 1014 | 1868 | 2348 |
SUPER THERMAL RESISTANT ALUMINUM ALLOY CONDUCTOR, ALUMINUM CLAD INVAR REINFORCED (STACIR/TW)
| Conductor Size | Cross-Sectional Area | Stranding | Diameter of Complete Conductor | Weight | Rated Strength |
DC Resistance @ 20°C |
Current Capacity | |||||||||
| STAL | Invar | Total |
No. of STAL Wires |
No. of STAL Layers |
No. of Invar Wires |
Dia. of Invar Wires |
STAL | Invar | Total | |||||||
| @ 85°C | @ 150°C | @ 210°C | ||||||||||||||
| (mm²) | (mm²) | (mm²) | (mm²) | (No.) | (No.) | (No.) | (mm) | (mm) | (Kg/Km) | (Kg/Km) | (Kg/Km) | (KN) | (Ω/Km) | (Ampere) | (Ampere) | (Ampere) |
| 320 | 322.26 | 52.49 | 374.75 | 20 | 2 | 7 | 3.09 | 22.88 | 888.49 | 374.31 | 1262.80 | 100.95 | 0.0876 | 596 | 1039 | 1287 |
| 340 | 336.85 | 54.90 | 391.75 | 20 | 2 | 7 | 3.16 | 23.38 | 928.73 | 391.46 | 1320.19 | 105.55 | 0.0838 | 612 | 1069 | 1324 |
| 390 | 389.25 | 50.81 | 440.06 | 20 | 2 | 7 | 3.04 | 24.72 | 1073.18 | 362.29 | 1435.47 | 109.47 | 0.0731 | 662 | 1163 | 1442 |
| 405 | 402.83 | 52.15 | 454.98 | 20 | 2 | 7 | 3.08 | 25.14 | 1110.62 | 371.89 | 1482.51 | 112.86 | 0.0706 | 676 | 1189 | 1475 |
| 480 | 479.69 | 47.20 | 526.89 | 35 | 3 | 7 | 2.93 | 26.98 | 1329.03 | 336.55 | 1665.58 | 123.00 | 0.0600 | 733 | 1298 | 1613 |
| 490 | 489.57 | 63.55 | 553.13 | 24 | 2 | 7 | 3.40 | 27.70 | 1349.78 | 453.18 | 1802.96 | 136.19 | 0.0581 | 759 | 1347 | 1676 |
| 525 | 523.67 | 26.85 | 550.53 | 30 | 3 | 7 | 2.21 | 27.50 | 1450.88 | 191.47 | 1642.35 | 107.39 | 0.0556 | 763 | 1354 | 1685 |
| 590 | 586.76 | 41.28 | 628.03 | 33 | 3 | 7 | 2.74 | 29.40 | 1625.66 | 294.31 | 1919.97 | 131.16 | 0.0494 | 820 | 1464 | 1825 |
| 625 | 625.07 | 79.63 | 704.69 | 38 | 3 | 19 | 2.31 | 31.32 | 1731.79 | 569.72 | 2301.51 | 177.43 | 0.0458 | 862 | 1549 | 1935 |
| 640 | 636.97 | 44.03 | 681.00 | 35 | 3 | 7 | 2.83 | 30.60 | 1764.78 | 313.97 | 2078.75 | 141.60 | 0.0455 | 860 | 1542 | 1925 |
| 680 | 676.24 | 85.95 | 762.20 | 39 | 3 | 19 | 2.40 | 32.58 | 1873.58 | 614.97 | 2488.55 | 191.75 | 0.0423 | 903 | 1630 | 2037 |
| 690 | 688.96 | 47.52 | 736.48 | 36 | 3 | 7 | 2.94 | 31.80 | 1908.82 | 338.85 | 2247.67 | 151.77 | 0.0421 | 899 | 1620 | 2024 |
| 725 | 725.09 | 91.78 | 816.87 | 39 | 3 | 19 | 2.48 | 33.72 | 2008.91 | 656.66 | 2665.57 | 205.21 | 0.0395 | 940 | 1703 | 2131 |
| 730 | 726.41 | 91.78 | 818.19 | 39 | 3 | 19 | 2.48 | 33.75 | 2012.56 | 656.66 | 2669.22 | 205.41 | 0.0394 | 941 | 1705 | 2134 |
| 740 | 737.40 | 51.14 | 788.54 | 36 | 3 | 7 | 3.05 | 32.92 | 2043.02 | 364.68 | 2407.70 | 162.72 | 0.0393 | 936 | 1692 | 2117 |
| 780 | 776.92 | 98.56 | 875.49 | 39 | 3 | 19 | 2.57 | 34.90 | 2152.52 | 705.18 | 2857.70 | 218.33 | 0.0368 | 979 | 1780 | 2231 |
| 790 | 789.13 | 54.55 | 843.69 | 36 | 3 | 7 | 3.15 | 34.05 | 2186.36 | 388.98 | 2575.34 | 173.95 | 0.0367 | 973 | 1767 | 2213 |
| 820 | 821.87 | 108.79 | 930.65 | 39 | 3 | 19 | 2.70 | 36.00 | 2277.05 | 778.33 | 3055.38 | 235.56 | 0.0348 | 1012 | 1847 | 2316 |
| 840 | 839.80 | 58.07 | 897.88 | 36 | 3 | 7 | 3.25 | 35.14 | 2326.74 | 414.07 | 2740.81 | 185.14 | 0.0345 | 1008 | 1837 | 2304 |
| 880 | 876.90 | 111.22 | 988.11 | 42 | 3 | 19 | 2.73 | 37.10 | 2429.50 | 795.72 | 3225.22 | 246.40 | 0.0326 | 1050 | 1923 | 2414 |
| 890 | 891.08 | 61.70 | 952.78 | 42 | 3 | 7 | 3.35 | 36.18 | 2468.81 | 439.95 | 2908.76 | 195.42 | 0.0325 | 1043 | 1907 | 2394 |
| 900 | 901.93 | 73.54 | 975.47 | 42 | 3 | 19 | 2.22 | 36.70 | 2498.85 | 526.19 | 3025.04 | 213.21 | 0.0320 | 1054 | 1931 | 2425 |
| 980 | 976.36 | 123.77 | 1100.13 | 42 | 3 | 19 | 2.88 | 39.12 | 2705.08 | 885.56 | 3590.64 | 274.28 | 0.0293 | 1115 | 2056 | 2587 |
| 990 | 987.86 | 68.90 | 1056.76 | 42 | 3 | 7 | 3.54 | 38.10 | 2736.95 | 491.27 | 3228.22 | 217.12 | 0.0293 | 1105 | 2035 | 2560 |
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
CCS — Copper Clad Steel Conductor
Copper clad steel wire is composed of stranded copper clad monofilament, widely applied for grounding and lightning protection, electrostatic grounding protection, protective grounding, grounding wire of electrical and petrochemical system in areas covering high-frequency coaxial cable, electrified…
TAAAC — Thermal-Resistant All Aluminum Alloy Conductor
TAAAC - The full name: Thermal Resistant Aluminum-alloy Conductors. Urban network capacity transformation, substation, power plant construction and general lines
ZTACSR & ZTACSRTW
Super thermal-resistant aluminum-alloy conductors, Aluminum-clad invar reinforced
ACS — Aluminum Clad Steel Wire
The aluminum clad steel wire internationally known as Alumoweld or ACS is widely used in long-span transmission line, coastal areas and island as well as other hot and humid regions, salt fog regions and heavily polluted regions where the high corrosion resistance strand is needed.
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions