Bare Copper Conductor
Bare Copper Conductor Stranded
- ASTM B8 · BS 7884 · IEC 60228
Product Description
Bare Copper Conductor Stranded
Hard, Medium-Hard, or Soft-Drawn
Used for grounding purposes in accordance with the National Electrical Code (NEC). Soft-drawn solid or stranded conductors are used for grounding connections in circuits, machinery, equipment, and counterpoise grounding systems. Hard-drawn conductors are suitable for overhead transmission and distribution lines and specified grounding applications. Also available tinned.
Physical Data
| Bare Copper Conductors Stranded | ||||||||
|---|---|---|---|---|---|---|---|---|
| Size | Area | Class A | Class B | Net Weight | dc Resistance* | |||
| AWG | kcmil | cmil | Number of | OD | Number of | OD | lb/kft | |
| Strands | in | Strands | in | 20 °C | ||||
| 14 | — | 4110 | — | — | 7 | 0.0726 | 13 | 2.58 |
| 12 | — | 6530 | — | — | 7 | 0.0915 | 20 | 1.63 |
| 10 | — | 10380 | — | — | 7 | 0.116 | 32 | 1.02 |
| 8 | — | 16510 | — | — | 7 | 0.146 | 51 | 0.64 |
| 6 | — | 26240 | — | — | 7 | 0.184 | 81 | 0.403 |
| 4 | — | 41740 | 7 | 0.232 | 7 | 0.232 | 129 | 0.253 |
| 3 | — | 52620 | 7 | 0.26 | 7 | 0.26 | 163 | 0.201 |
| 2 | — | 66360 | 7 | 0.292 | 7 | 0.292 | 205 | 0.159 |
| 1 | — | 83690 | 7 | 0.328 | 19 | 0.332 | 258 | 0.127 |
| 1/0 | — | 105600 | 7 | 0.368 | 19 | 0.373 | 326 | 0.1 |
| 2/0 | — | 133100 | 7 | 0.414 | 19 | 0.419 | 411 | 0.795 |
| 3/0 | — | 167800 | 7 | 0.464 | 19 | 0.47 | 518 | 0.063 |
| 4/0 | — | 211600 | 7 | 0.522 | 19 | 0.528 | 653 | 0.05 |
| — | 250 | 250000 | 19 | 0.574 | 37 | 0.575 | 772 | 0.0423 |
| — | 300 | 300000 | 19 | 0.629 | 37 | 0.63 | 926 | 0.0353 |
| — | 350 | 350000 | 19 | 0.679 | 37 | 0.681 | 1081 | 0.0302 |
| — | 400 | 400000 | 19 | 0.726 | 37 | 0.728 | 1235 | 0.0264 |
| — | 450 | 450000 | 37 | 0.772 | 37 | 0.772 | 1389 | 0.0235 |
| — | 500 | 500000 | 37 | 0.813 | 37 | 0.813 | 1544 | 0.0192 |
| — | 600 | 600000 | 37 | 0.891 | 61 | 0.893 | 1883 | 0.0177 |
| — | 750 | 750000 | 61 | 0.998 | 61 | 0.998 | 2316 | 0.0141 |
| — | 1000 | 100000 | 61 | 1.152 | 61 | 1.152 | 3088 | 0.0106 |
| — | 1250 | 125000 | 61 | 1.288 | 91 | 1.289 | 3859 | 0.0085 |
| — | 1500 | 150000 | 61 | 1.411 | 91 | 1.412 | 4631 | 0.0071 |
| — | 1750 | 175000 | 91 | 1.526 | 127 | 1.526 | 5403 | 0.006 |
| — | 2000 | 200000 | 91 | 1.63 | 127 | 1.632 | 6175 | 0.0053 |
| The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors and accessories should be verified using actual dimensions of the product. Other sizes available upon request. *Direct current resistances apply to Class B, C, and D stranding. | ||||||||
| Bare Copper Conductors Stranded (cont.) | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Breaking Strength | |||||||||
| Size | Strands | Hard Drawn Rated Strength |
dc Resistance @ 20 °C |
Medium-Hard Drawn Rated Strength |
dc Resistance @ 20 °C |
Soft Drawn (Annealed) Rated Strength |
dc Resistance @ 20 °C |
Allowable Ampacity † |
|
| AWG | kcmil | lb | Ω/kft | lb | Ω/kft | lb | Ω/kft | ||
| 14 | — | 7 | 197 | 2.679 | 158 | 2.665 | — | — | — |
| 12 | — | 7 | 311 | 1.685 | 248 | 1.676 | — | — | — |
| 10 | — | 7 | 492 | 1.06 | 389 | 1.054 | — | — | — |
| 8 | — | 7 | 777 | 0.6663 | 610 | 0.6629 | 499 | 0.6408 | 98 |
| 6 | — | 7 | 1228 | 0.4191 | 959 | 0.4169 | 794 | 0.403 | 124 |
| 4 | — | 7 | 1938 | 0.2636 | 1505 | 0.2622 | 1320 | 0.2534 | 155 |
| 3 | — | 7 | 2433 | 0.209 | 1885 | 0.2079 | 1670 | 0.201 | — |
| 2 | — | 7 | 3050 | 0.166 | 2360 | 0.165 | 2110 | 0.1578 | 209 |
| 1 | — | 7 | 3801 | 0.1316 | 2955 | 0.1309 | 2552 | 0.1252 | — |
| 1/0 | — | 7 | 4752 | 0.1042 | 3705 | 0.1037 | 3221 | 0.1002 | 282 |
| 2/0 | — | 7 | 5926 | 0.08267 | 4640 | 0.08224 | 4062 | 0.07949 | 329 |
| 3/0 | — | 7 | 7366 | 0.06556 | 5812 | 0.06522 | 5118 | 0.06304 | 382 |
| 4/0 | — | 7 | 9154 | 0.05199 | 7278 | 0.05172 | 6459 | 0.04999 | 444 |
| 4/0 | — | 19 | 9617 | 0.05199 | 7479 | 0.05172 | 6453 | 0.04999 | 444 |
| — | 250 | 19 | 11360 | 0.044 | 8836 | 0.04378 | 7627 | 0.04231 | 494 |
| — | 250 | 37 | 11600 | 0.044 | 8952 | 0.04378 | 7940 | 0.04231 | 494 |
| — | 300 | 19 | 13510 | 0.03667 | 10530 | 0.03648 | 9160 | 0.03526 | 556 |
| — | 350 | 19 | 15590 | 0.03143 | 12200 | 0.03127 | 10680 | 0.03022 | — |
| — | 500 | 37 | 22510 | 0.022 | 17550 | 0.02189 | 15240 | 0.02116 | 773 |
| — | 600 | 37 | 27020 | 0.01834 | 21060 | 0.01825 | 18300 | 0.01763 | — |
| — | 750 | 61 | 34090 | 0.01467 | 26510 | 0.01459 | 22890 | 0.0141 | 1000 |
| — | 1000 | 61 | 45030 | 0.011 | 35100 | 0.01094 | 30500 | 0.01058 | 1193 |
| † Ampacity per NEC table 310.15 (B) (21) based on 80°C Conductor Temperature, 40°C Ambient Temperature, 2ft/s Wind in Sun. | |||||||||
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
GSW — Galvanized Stay Wire
The galvanized steel wire strand is used for overhead ground lines or electrical power transmission lines. Stay or guy wire strands are produced for use with poles, towers, or any other form of guying.
TACSR — Thermal-Resistant Aluminum Conductor Steel Reinforced
The TACSR (thermal resistant aluminum-alloy conductor steel reinforced) could withstand high tensile load to be used mainly for overhead transmission lines, overhead distribution wires.
ACSR — Aluminum Conductor Steel Reinforced
Aluminium Conductors, Aluminium Clad Steel Reinforced (ACSR/AS or ACSR/AW) are c concentrically stranded conductors with one or more layers of hard drawn 1350-H19 aluminium wires on Aluminium Clad steel wire core. The core can be single wire or stranded depending on the size.
TAAAC — Thermal-Resistant All Aluminum Alloy Conductor
TAAAC - The full name: Thermal Resistant Aluminum-alloy Conductors. Urban network capacity transformation, substation, power plant construction and general lines