POLY AL. POLY AAC POLY ACSR
POLY AL. POLY AAC POLY ACSR
- Standards: ASTM B 231 · ASTM B 232 · ICEA S-61-402
Product Description
POLY AL. POLY AAC POLY ACSR
Polyethylene Covered Line Wire Applications
POLY AL. & POLY AAC & POLY ACSR conductors are primarily used in overhead distribution lines. Installed on insulators, otherwise treated as bare conductor.
Polyethylene Covered Line Wire Constructions
POLY AL. & POLY AAC conductors are solid 1350 – H19 aluminum and concentrically stranded according to ASTM B 231. Covered with weather resistant black polyethylene compound.
POLY ACSR conductors are concentrically stranded according to ASTM B 232. Covered with weather resistant black polyethylene compound.
Polyethylene Covered Line Wire Standards
ASTM B-231 solid 1350 – H19 aluminum and concentrically stranded Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR).
ANSI C-8.35 Specifications for Weather-Resistant Polyethylene-Covered Wire and Cable.
ICEA S-61-402 NEMA PUB NO. WC 5-1973 Standards Publication Thermoplastic insulated Wire and Cable for the Transmission and Distribution of Electrical Energy.
Polyethylene Covered Line Wire Parameter
POLY AL. & POLY AAC conductors
| Code Name | Size | Stranding | Insul. Thickness | Approx. Over-all Diameter | Rated Strength | Appox. Cable;Weight | Allowable Ampacity + (Amps )++ |
|---|---|---|---|---|---|---|---|
| AWG/ MCM | No. / mm | mm | mm | kg | Kg / km | A | |
| Apple | 6 | 4.155 | 0.76 | 5.68 | 201.85 | 46.77 | 105 |
| Pear | 4 | 5.189 | 6.71 | 321.15 | 70.38 | 135 | |
| Cherry | 2 | 6.543 | 1.14 | 8.83 | 500.32 | 116.481 | 180 |
| Plum | 6 | 7/1.56 | 0.76 | 6.20 | 229.97 | 51.37 | 105 |
| Apricot | 4 | 7/1.96 | 7.40 | 359.70 | 77.70 | 140 | |
| Peach | 2 | 7/2.47 | 1.14 | 9.70 | 551.12 | 128.44 | 180 |
| Nectarine | 1 | 7/2.78 | 10.63 | 669.51 | 158.22 | 210 | |
| Quince | 1/0 | 7/3.12 | 1.52 | 12.41 | 812.39 | 207.82 | 240 |
| Orange | 2/0 | 7/3.50 | 13.55 | 1 024.68 | 254.11 | 280 | |
| Fig | 3/0 | 7/3.93 | 14.84 | 1 241.05 | 312.21 | 320 | |
| Olive | 4/0 | 7/4.42 | 16.31 | 1 563.56 | 385.81 | 370 | |
| Pomegranate | 4/0 | 19/268 | 16.45 | 1 641.12 | 381.39 | 370 | |
| Mulberry | 266.8 | 19/3.01 | 18.10 | 2 028.95 | 471.12 | 430 | |
| An on a | 336.4 | 19/3.38 | 19.95 | 2510.67 | 583.09 | 495 | |
| Mollies | 397.5 | 19/3.67 | 2.03 | 22.41 | 2 902.58 | 711.60 | 545 |
| Huckleberry | 477.0 | 37/2.88 | 24.22 | 3 547.60 | 833.20 | 610 | |
| Pawpaw | 556.5 | 37/3.12 | 25.90 | 4 075.90 | 965.02 | 670 | |
| Breadfruit | 636.0 | 61/2.59 | 2.41 | 28.14 | 4 723.33 | 1 110.61 | 720 |
| Persimmon | 795.0 | 61/2.90 | 30.67 | 5 837.8 | 1 354.82 | 825 | |
| Grapefruit | 1 033.5 | 61/3.31 | 34.36 | 7470.79 | 1 732.41 | 970 |
POLY ACSR conductors
| Code Name | Size | Stranding No. / mm | Insul. Thick | Approx. Over-all Diameter | Rated Strength | Appox. Cable Weight | Allowable Ampacity + (Amps) ++ | |
|---|---|---|---|---|---|---|---|---|
| AWGZ MCM | Al. | Steel | mm | mm | kg | Kg/km | A | |
| Walnut | 6 | 6 /1.68 | 1.68 | 0.76 | 6.56 | 513.02 | 70.37 | 105 |
| Butternut | 4 | 6/2.12 | 2.12 | 7.88 | 801.51 | 107.36 | 135 | |
| Hickory | 4 | 7/1.96 | 2.61 | 8.01 | 1 016.97 | 126.40 | 135 | |
| Pignut | 2 | 6/2.67 | 2.67 | 1.14 | 10.30 | 1 228.35 | 175.69 | 180 |
| Beech | 2 | 7/2.47 | 3.30 | 10.53 | 1 568.55 | 207.41 | 180 | |
| Chestnut | 1 | 6/3.00 | 3.00 | 11.28 | 1 529.99 | 215.79 | 210 | |
| Almond | 1/0 | 6/3.37 | 3.37 | 1.52 | 13.16 | 1 887.43 | 282.97 | 235 |
| Pecan | 2/0 | 6/3.78 | 3.78 | 14.39 | 2 288.41 | 347.03 | 270 | |
| Filbert | 3/0 | 6/4.25 | 4.25 | 15.80 | 2 852.69 | 429.97 | 305 | |
| Buckeye | 4/0 | 6 /4.77 | 4.77 | 17.36 | 3 598.41 | 532.19 | 345 | |
| Hackberry | 266.8 | 18/3.09 | 3.09 | 18.50 | 2 964.73 | 532.34 | 435 | |
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
ANSI — Service Drop Cable
This duplexed cable is suited for supply 120 volts aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP)…
TYIR — Bundled Overhead Line Cable
TYIR / TYIR 50 OL-AL PVC Bundled Overhead Line Cable
0.61k V LV ABC Cable Aerial Bundle Conductor
The aerial bundled cables designed for overhead distribution lines have all conductors made of aluminium 1350 and insulated with XLPE. Can be used for fixed installation as overhead power lines up to 1000 V incl.
NF2X — Aerial Bundled Twisted Cable
NF2X/NFA2X Aerial Bundled Twisted Cable
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions