Pre-Assembled Aluminum Multiplex Cable – ABNT NBR 8182, 0.6/1 kV
ABNT NBR 8182 0.6/1kV Preassembled Cabos De Alumínio Multiplexado
- Standards: IEC 60228
Product Overview
Pre-Assembled Aluminum Multiplex Cable, also known as Cabo Multiplexado, is designed for low-voltage overhead distribution networks and service connections. It is commonly used in distribution circuits and household electrical connections.
Compared with bare overhead conductors, insulated multiplex cables offer improved protection against accidental phase-to-phase contact and contact with nearby vegetation. They are particularly suitable for wooded areas, locations with limited installation space, and rural electrification projects.
Manufactured with 1350 aluminium phase conductors and PE or XLPE insulation, the cable is available in Duplex, Triplex, and Quadruplex configurations. The neutral conductor can be supplied in aluminium (CA), aluminium alloy (CAL), or other specified constructions according to project requirements.
Rated Voltage: 0.6/1 kV
Applicable Standard: ABNT NBR 8182
Applications
- Low-voltage overhead power distribution networks
- Residential and household service connections
- Rural electrification and village distribution projects
- Overhead distribution routes in wooded areas
- Installations where underground cable networks are costly
- Distribution networks with limited physical installation space
Cable Construction
Phase Conductor
- Material: Aluminium 1350
- Conductor class: Class 2, stranded and compacted
- Conductor standard: ABNT NBR NM 280
Phase Insulation
- Material: Cross-linked polyethylene (XLPE) or polyethylene (PE), according to the specified design
- Weather-resistant insulation
- XLPE insulation with a nominal operating temperature of 90°C in the supplied construction data
Neutral Conductor
CA – Aluminium Neutral
- Aluminium 1350 wires
- H19 temper
- Conventional round-stranded construction
CAL – Aluminium Alloy Neutral
- Aluminium alloy 6201 wires
- T81 temper
- Conventional round-stranded construction
- According to ABNT NBR 10298
Neutral Conductor Insulation
- Available with XLPE insulation in light blue when specified
- Bare neutral conductor configurations are also available
Cable Configurations
| Configuration | Construction |
|---|---|
| Duplex | One phase conductor and one neutral conductor |
| Triplex | Two phase conductors and one neutral conductor |
| Quadruplex | Three phase conductors and one neutral conductor |
Conductor Identification
The phase conductors are identified by insulation color:
- Single-phase: Black
- Two-phase: Black and grey
- Three-phase: Black, grey, and red
For insulated-neutral configurations, the neutral conductor insulation can be supplied in light blue when requested.
Maximum Operating Temperatures
| Operating Condition | Maximum Temperature |
|---|---|
| Continuous operation | 90°C |
| Overload | 130°C |
| Short circuit | 250°C |
Reference Standards
- ABNT NBR 8182: Self-supporting multiplex power cables with extruded PE or XLPE insulation for voltages up to 0.6/1 kV – Performance requirements.
- ABNT NBR NM 280: Conductors of insulated cables (IEC 60228, MOD).
- ABNT NBR 10298: Bare cables with aluminium-magnesium-silicon alloy for overhead lines – Specification.
Manufacturing and Customization
Pre-assembled aluminium multiplex cables can be supplied in Duplex, Triplex, and Quadruplex configurations, with insulated or bare neutral conductors.
Conductor cross-sections, neutral conductor materials, insulation options, and cable configurations can be selected according to the applicable standard, technical specification, and project requirements.
Technical Data – XLPE, Insulated Neutral
Technical Data – XLPE, Bare Neutral
Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Isolado
| Tipo | Seção Nominal (mm²) | Condutor Fase | Condutor Neutro | Diâmetro externo aprox (mm) | Peso Líquido (kg/km) | |||||
| Diâmetro do Condutor (mm) | Espessura de Isolação (mm) | Resistência Elétrica Máxima (Ω/km) | Formação (nº fios x mm) | Espessura de Isolação (mm) | Carga de Ruptura mín (kgf) | |||||
| CA | CAL | |||||||||
| Duplex | 1×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 12,9 | 96,4 |
| 1×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 14,6 | 135 | |
| 1×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 17,8 | 207 | |
| 1×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 20,8 | 284 | |
| 1×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 23,5 | 377 | |
| Triplex | 2×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 13,8 | 142 |
| 2×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 15,6 | 199 | |
| 2×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 19,2 | 304 | |
| 2×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 22,4 | 420 | |
| 2×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 25,3 | 551 | |
| Quadruplex | 3×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 15,4 | 188 |
| 3×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 17,3 | 264 | |
| 3×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 21,3 | 403 | |
| 3×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 24,8 | 555 | |
| 3×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 28,0 | 726 | |
| 3×70 + 70 | 9,7 | 1,8 | 0,44 | 7×3,45 | 1,8 | 1102 | 2030 | 32,6 | 1004 | |
| 3×95 + 70 | 11,5 | 2,0 | 0,32 | 7×3,45 | 2,0 | 1102 | 2030 | 37,9 | 1270 | |
| 3×120 + 70 | 12,9 | 2,0 | 0,25 | 7×3,45 | 2,0 | 1102 | 2030 | 41,3 | 1500 | |
Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Nu
| Tipo | Seção Nominal (mm²) | Condutor Fase | Condutor Neutro | Diâmetro externo aprox (mm) | Peso Líquido (kg/km) | ||||
| Diâmetro do Condutor (mm) | Espessura de Isolação (mm) | Resistência Elétrica Máxima (Ω/km) | Formação (nº fios x mm) | Carga de Ruptura mín (kgf) | |||||
| CA | CAL | ||||||||
| Duplex | 1×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 10,5 | 74 |
| 1×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 12,2 | 109 | |
| 1×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 15,0 | 167 | |
| 1×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 17,6 | 231 | |
| 1×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 20,3 | 311 | |
| Triplex | 2×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 13,8 | 119 |
| 2×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 15,3 | 173 | |
| 2×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 18,8 | 266 | |
| 2×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 21,8 | 367 | |
| 2×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 24,4 | 485 | |
| Quadruplex | 3×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 15,4 | 165 |
| 3×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 17,0 | 238 | |
| 3×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 20,9 | 365 | |
| 3×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 24,2 | 502 | |
| 3×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 27,1 | 660 | |
| 3×70 + 70 | 9,7 | 1,8 | 0,44 | 7×3,45 | 1102 | 2030 | 31,9 | 920 | |
| 3×95 + 70 | 11,5 | 2,0 | 0,32 | 7×3,45 | 1102 | 2030 | 37,2 | 1185 | |
| 3×120 + 70 | 12,9 | 2,0 | 0,25 | 7×3,45 | 1102 | 2030 | 40,6 | 1415 | |
| DADOS CONSTRUTIVOSFormação do cabo(mm²) | Condutor Fase | Condutor Neutro | Diâmetro externo aproximado (mm) | Resistência elétrica nominal C.C. a 20°C (Ω/km) | Massa líquida aproximada (kg/km) | |||||
| Diâmetro nominal do condutor (mm) | Material da isolação | Espessura nominal da isolação(mm) | Nº de fios | Diâmetro nominal do condutor (mm) | Tipo(4) | |||||
| DUPLEX | 1x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 10,60 | 3,08 | 77 |
| 1x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 12,20 | 1,91 | 107 | |
| 1x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 14,70 | 1,20 | 163 | |
| 1x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 17,40 | 0,868 | 238 | |
| 1x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 20,00 | 0,641 | 331 | |
| 1x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 24,00 | 0,443 | 424 | |
| TRIPLEX | 2x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 14,00 | 3,08 | 125 |
| 2x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 15,10 | 1,91 | 169 | |
| 2x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 18,10 | 1,20 | 260 | |
| 2x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 21,40 | 0,868 | 377 | |
| 2x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 23,80 | 0,641 | 527 | |
| 2x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 29,30 | 0,443 | 679 | |
| QUADRUPLEX | 3x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 15,70 | 3,08 | 165 |
| 3x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 16,90 | 1,91 | 236 | |
| 3x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 20,30 | 1,20 | 349 | |
| 3x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 23,90 | 0,868 | 518 | |
| 3x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 26,50 | 0,641 | 724 | |
| 3x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 32,70 | 0,443 | 924 | |
| 3x1x95+70 | 11,80 | XLPE 90°C | 2,0 | 7 | 10,40 | CA | 37,60 | 0,320 | 1,148 | |
| 3x1x95+95 | 11,80 | XLPE 90°C | 2,0 | 7 | 12,33 | CA | 38,10 | 0,320 | 1,335 | |
| 3x1x120+70 | 13,40 | XLPE 90°C | 2,0 | 7 | 10,40 | CA | 40,60 | 0,253 | 1,420 | |
| 3x1x120+120 | 13,40 | XLPE 90°C | 2,0 | 19 | 14,50 | CA | 41,90 | 0,253 | 1,574 | |
(4) Condutor neutro tipo CAA (alumínio com alma de aço zincado) e CAL (alumínio liga) sob consulta.
| Parameter | Specification |
|---|---|
| (5) Duplex | composto por um condutor fase e um condutor neutro. |
| (6) Triplex | composto por dois condutores fase e um condutor neutro. |
| (7) Quadruplex | composto por três condutores fase e um condutor neutro. |
Frequently Asked Questions
1. What is a pre-assembled aluminum multiplex cable?
It is an insulated overhead cable used in low-voltage power distribution networks and household service connections. It is also known as Cabo Multiplexado.
2. What is the rated voltage?
The specified rated voltage is 0.6/1 kV.
3. What are Duplex, Triplex, and Quadruplex configurations?
Duplex contains one phase conductor and one neutral conductor. Triplex contains two phase conductors and one neutral conductor. Quadruplex contains three phase conductors and one neutral conductor.
4. Which conductor material is used for the phase conductors?
The phase conductors are made of aluminium 1350, stranded and compacted according to the supplied construction description and ABNT NBR NM 280.
5. What neutral conductor options are available?
The neutral conductor can be supplied in aluminium 1350 (CA), aluminium alloy 6201 (CAL), or other specified constructions. CAA, with a galvanized steel core, is also mentioned in the supplied construction notes as an option upon request.
6. Is the neutral conductor insulated?
Both insulated-neutral and bare-neutral configurations are included in the supplied technical data. For insulated-neutral versions, light-blue XLPE insulation can be requested.
7. What is the maximum operating temperature?
The supplied data specifies 90°C in continuous operation, 130°C under overload, and 250°C under short-circuit conditions.
8. Which standards apply to this cable?
The reference standards are ABNT NBR 8182, ABNT NBR NM 280, and ABNT NBR 10298.
9. Where is multiplex cable commonly used?
It is used in low-voltage overhead distribution, residential service connections, rural electrification, and locations where underground cable installation is costly or where space is limited.
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
AER Cable – 0.6/1kV PE insulated aerial power cables with aluminium conductor
AER cable, aerial bundled cable, AER aerial cable, low voltage ABC cable, 0.6/1 kV aerial cable, aluminium aerial cable, SFS 2200 cable, HD 626 S1 cable, rural electrification cable
CCSX (BLX) Covered Overhead Line Conductor – 10–52 kV
CCSX cable, BLX covered conductor, CCSX conductor manufacturer, 10–52 kV covered conductor, water-blocked overhead conductor, EN 50397-1 cable, Al7 conductor, FeAl conductor
T2X — Bundle Assembled Aerial Cables XLPE-insulated
T2X cable, T2X aerial cable, XLPE bundled aerial cable, XLPE overhead cable, 0.6/1 kV aerial cable, aluminium aerial cable, steel-aluminium neutral conductor, TIX 2 cable
A3CS / AAACS Cable 12/20 kV – XLPE Insulated Aluminium Cable
A3CS cable, AAACS cable, A3CS cable manufacturer, AAACS cable manufacturer, 12/20 kV cable, 20 kV aluminium cable, XLPE insulated aluminium cable, medium voltage aluminium cable, SPLN 41-10 cable, Indonesia medium voltage cable
Related solutions
Power Generation Cable Solutions
QZ Cable supplies power generation cable solutions for thermal, hydro, solar and wind power projects, including LV/MV power cables, control cables, instrumentation cables and overhead conductors.
Power Transmission Cable Solutions
QZ Cable supplies power transmission solutions, including AAC, AAAC, ACSR, ACSS, TACSR, TAAAC, OPGW and ADSS for utility, grid expansion and EPC projects worldwide.
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions