ABNT — 0.61k V Preassembled Cabos De Alumínio Multiplexado
ABNT NBR 8182 0.6/1kV Preassembled Cabos De Alumínio Multiplexado
- Standards: IEC 60228
Product Description
ABNT NBR 8182 0.6/1kV Preassembled Cabos De Alumínio Multiplexado
Pre-assembled Cable Insulated AluminumMultiplex Wire Application
Pre-assembled Cable is also called cabo multiplex , it is used in distribution circuits and household connections. t has advantage over bare cables, because they can be installed in wooded areas and in places where there is little physical space.
Due to the fact of being isolated, Pre assembled Cable provides greater reliability to the electrical system, avoiding disconnections due to short circuits caused by contact with trees.
Pre-assembled Cable Insulated AluminumMultiplex Wire Construction
Phase conductor: Aluminum wires 1350, stringing class 2, compact, acc. to NM 280.
Insulation: thermosetting compound of XLPE/PE polyethylene, weather resistant.
Pre-assembled Cable Insulated AluminumMultiplex Wire Identification
1 phase: black
2 phases: black and gray
3 phases: black, grey and red
Pre-assembled Cable Insulated AluminumMultiplex Wire Neutral conductor
Aluminum CA: aluminum wires 1350, hardness H19, normal round stringing.
Alloy aluminum CAL: aluminum wires with alloy 6201, hardness T81, normal round stringing, acc. to 10298.
Neutral conductor insulation: if requested, in XLPE in light blue.
Pre-assembled Cable Insulated AluminumMultiplex Wire Maximum Operating Temperatures
In continuous regime: 90°C
In overload: 130°C
In short circuit: 250°C
Pre-assembled Cable Insulated AluminumMultiplex Wire Reference Standards
ABNT NBR 8182 – Self-sustained multiplex power cables with extruded insulation of PE or XLPE, for voltages up to
0,6/1 kV – Performance requirements.
ABNT NBR NM 280 – Conductors of insulated cables (IEC 60228, MOD).
ABNT NBR 10298 – Bare cables with alloy aluminum-magnesium-silicon, for overhead lines – Specification
Pre-assembled Cable Insulated AluminumMultiplex Wire Specification
Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Isolado
| Tipo | Seção Nominal (mm²) | Condutor Fase | Condutor Neutro | Diâmetro externo aprox (mm) | Peso Líquido (kg/km) | |||||
| Diâmetro do Condutor (mm) | Espessura de Isolação (mm) | Resistência Elétrica Máxima (Ω/km) | Formação (nº fios x mm) | Espessura de Isolação (mm) | Carga de Ruptura mín (kgf) | |||||
| CA | CAL | |||||||||
| Duplex | 1×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 12,9 | 96,4 |
| 1×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 14,6 | 135 | |
| 1×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 17,8 | 207 | |
| 1×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 20,8 | 284 | |
| 1×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 23,5 | 377 | |
| Triplex | 2×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 13,8 | 142 |
| 2×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 15,6 | 199 | |
| 2×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 19,2 | 304 | |
| 2×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 22,4 | 420 | |
| 2×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 25,3 | 551 | |
| Quadruplex | 3×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 1,2 | 199 | – | 15,4 | 188 |
| 3×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 1,2 | 306 | – | 17,3 | 264 | |
| 3×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 1,4 | 455 | – | 21,3 | 403 | |
| 3×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 1,6 | 626 | 1113 | 24,8 | 555 | |
| 3×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 1,6 | 852 | 1602 | 28,0 | 726 | |
| 3×70 + 70 | 9,7 | 1,8 | 0,44 | 7×3,45 | 1,8 | 1102 | 2030 | 32,6 | 1004 | |
| 3×95 + 70 | 11,5 | 2,0 | 0,32 | 7×3,45 | 2,0 | 1102 | 2030 | 37,9 | 1270 | |
| 3×120 + 70 | 12,9 | 2,0 | 0,25 | 7×3,45 | 2,0 | 1102 | 2030 | 41,3 | 1500 | |
Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Nu
| Tipo | Seção Nominal (mm²) | Condutor Fase | Condutor Neutro | Diâmetro externo aprox (mm) | Peso Líquido (kg/km) | ||||
| Diâmetro do Condutor (mm) | Espessura de Isolação (mm) | Resistência Elétrica Máxima (Ω/km) | Formação (nº fios x mm) | Carga de Ruptura mín (kgf) | |||||
| CA | CAL | ||||||||
| Duplex | 1×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 10,5 | 74 |
| 1×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 12,2 | 109 | |
| 1×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 15,0 | 167 | |
| 1×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 17,6 | 231 | |
| 1×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 20,3 | 311 | |
| Triplex | 2×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 13,8 | 119 |
| 2×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 15,3 | 173 | |
| 2×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 18,8 | 266 | |
| 2×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 21,8 | 367 | |
| 2×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 24,4 | 485 | |
| Quadruplex | 3×10 + 10 | 4,0 | 1,2 | 3,08 | 7×1,36 | 199 | – | 15,4 | 165 |
| 3×16 + 16 | 4,7 | 1,2 | 1,91 | 7×1,70 | 306 | – | 17,0 | 238 | |
| 3×25 + 25 | 5,9 | 1,4 | 1,20 | 7×2,11 | 455 | – | 20,9 | 365 | |
| 3×35 + 35 | 6,9 | 1,6 | 0,87 | 7×2,50 | 626 | 1113 | 24,2 | 502 | |
| 3×50 + 50 | 8,1 | 1,6 | 0,64 | 7×3,00 | 852 | 1602 | 27,1 | 660 | |
| 3×70 + 70 | 9,7 | 1,8 | 0,44 | 7×3,45 | 1102 | 2030 | 31,9 | 920 | |
| 3×95 + 70 | 11,5 | 2,0 | 0,32 | 7×3,45 | 1102 | 2030 | 37,2 | 1185 | |
| 3×120 + 70 | 12,9 | 2,0 | 0,25 | 7×3,45 | 1102 | 2030 | 40,6 | 1415 | |
|
DADOS CONSTRUTIVOS Formação do cabo(mm²) |
Condutor Fase | Condutor Neutro | Diâmetro externo aproximado (mm) |
Resistência elétrica nominal C.C. a 20°C (Ω/km) |
Massa líquida aproximada (kg/km) |
|||||
|---|---|---|---|---|---|---|---|---|---|---|
| Diâmetro nominal do condutor (mm) |
Material da isolação |
Espessura nominal da isolação(mm) |
Nº de fios |
Diâmetro nominal do condutor (mm) |
Tipo(4) | |||||
| DUPLEX | 1x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 10,60 | 3,08 | 77 |
| 1x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 12,20 | 1,91 | 107 | |
| 1x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 14,70 | 1,20 | 163 | |
| 1x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 17,40 | 0,868 | 238 | |
| 1x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 20,00 | 0,641 | 331 | |
| 1x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 24,00 | 0,443 | 424 | |
| TRIPLEX | 2x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 14,00 | 3,08 | 125 |
| 2x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 15,10 | 1,91 | 169 | |
| 2x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 18,10 | 1,20 | 260 | |
| 2x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 21,40 | 0,868 | 377 | |
| 2x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 23,80 | 0,641 | 527 | |
| 2x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 29,30 | 0,443 | 679 | |
| QUADRUPLEX | 3x1x10+10 | 4,08 | XLPE 90°C | 1,2 | 7 | 4,08 | CA | 15,70 | 3,08 | 165 |
| 3x1x16+16 | 4,60 | XLPE 90°C | 1,2 | 7 | 5,12 | CA | 16,90 | 1,91 | 236 | |
| 3x1x25+25 | 5,60 | XLPE 90°C | 1,4 | 7 | 6,33 | CA | 20,30 | 1,20 | 349 | |
| 3x1x35+35 | 6,70 | XLPE 90°C | 1,6 | 7 | 7,50 | CA | 23,90 | 0,868 | 518 | |
| 3x1x50+50 | 7,80 | XLPE 90°C | 1,6 | 7 | 9,00 | CA | 26,50 | 0,641 | 724 | |
| 3x1x70+70 | 9,95 | XLPE 90°C | 1,8 | 7 | 10,40 | CA | 32,70 | 0,443 | 924 | |
| 3x1x95+70 | 11,80 | XLPE 90°C | 2,0 | 7 | 10,40 | CA | 37,60 | 0,320 | 1,148 | |
| 3x1x95+95 | 11,80 | XLPE 90°C | 2,0 | 7 | 12,33 | CA | 38,10 | 0,320 | 1,335 | |
| 3x1x120+70 | 13,40 | XLPE 90°C | 2,0 | 7 | 10,40 | CA | 40,60 | 0,253 | 1,420 | |
| 3x1x120+120 | 13,40 | XLPE 90°C | 2,0 | 19 | 14,50 | CA | 41,90 | 0,253 | 1,574 | |
(4) Condutor neutro tipo CAA (alumínio com alma de aço zincado) e CAL (alumínio liga) sob consulta.
| Parameter | Specification |
|---|---|
| (5) Duplex | composto por um condutor fase e um condutor neutro. |
| (6) Triplex | composto por dois condutores fase e um condutor neutro. |
| (7) Quadruplex | composto por três condutores fase e um condutor neutro. |
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
Cable Semiaislado o Ecológico – Medium Voltage Covered Overhead Conductor
Cable Semiaislado o Ecológico, Cable Semiaislado, Cable Ecológico Media Tensión, Conductor Cubierto de Media Tensión, Cable Cubierto para Redes Aéreas, Medium Voltage Covered Conductor, Anti-Tracking Overhead Conductor, AAC AAAC ACSR Covered Conductor
ACSR-OC, ACSR/AW-OC & ACSR/AW-TR/OC – Medium Voltage Aerial Insulated Conductors
ACSR-OC, ACSR/AW-OC, ACSR/AW-TR/OC, ACSR-OC cable manufacturer, ACSR/AW insulated conductor, 6.6kV aerial insulated conductor, 22.9kV overhead cable, XLPE insulated ACSR, aluminum clad steel reinforced conductor, KS C 3138, ES-6145-0021, medium voltage aerial conductor
Covered Aerial Medium Voltage Cable – Spacer Cable & Tree Wire
Tree Wire Cable, Spacer Cable, Medium Voltage Overhead Cable, Messenger Supported Spacer Cable, Covered Overhead Conductor, Track Resistant XLPE Cable, XLPE Covered Conductor, ICEA S-121-733, AAC Tree Wire, AAAC Spacer Cable, ACSR Tree Wire
A3CS / AAACS Cable 12/20 kV – XLPE Insulated Aluminium Cable
A3CS cable, AAACS cable, A3CS cable manufacturer, AAACS cable manufacturer, 12/20 kV cable, 20 kV aluminium cable, XLPE insulated aluminium cable, medium voltage aluminium cable, SPLN 41-10 cable, Indonesia medium voltage cable
Related solutions
Power Generation Cable Solutions
QZ Cable supplies power generation cable solutions for thermal, hydro, solar and wind power projects, including LV/MV power cables, control cables, instrumentation cables and overhead conductors.
Power Transmission Cable Solutions
QZ Cable supplies power transmission solutions, including AAC, AAAC, ACSR, ACSS, TACSR, TAAAC, OPGW and ADSS for utility, grid expansion and EPC projects worldwide.
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions