One-stop Solution for Wire & Cable · Since 1969
Pre-Assembled Aluminum Multiplex Cable – ABNT NBR 8182, 0.6/1 kV
LV & MV Aerial Cables

Pre-Assembled Aluminum Multiplex Cable – ABNT NBR 8182, 0.6/1 kV

ABNT NBR 8182 0.6/1kV Preassembled Cabos De Alumínio Multiplexado

  • Standards: IEC 60228

Product Overview

Pre-Assembled Aluminum Multiplex Cable, also known as Cabo Multiplexado, is designed for low-voltage overhead distribution networks and service connections. It is commonly used in distribution circuits and household electrical connections.

Compared with bare overhead conductors, insulated multiplex cables offer improved protection against accidental phase-to-phase contact and contact with nearby vegetation. They are particularly suitable for wooded areas, locations with limited installation space, and rural electrification projects.

Manufactured with 1350 aluminium phase conductors and PE or XLPE insulation, the cable is available in Duplex, Triplex, and Quadruplex configurations. The neutral conductor can be supplied in aluminium (CA), aluminium alloy (CAL), or other specified constructions according to project requirements.

Rated Voltage: 0.6/1 kV
Applicable Standard: ABNT NBR 8182

Applications

  • Low-voltage overhead power distribution networks
  • Residential and household service connections
  • Rural electrification and village distribution projects
  • Overhead distribution routes in wooded areas
  • Installations where underground cable networks are costly
  • Distribution networks with limited physical installation space

Cable Construction

Phase Conductor
  • Material: Aluminium 1350
  • Conductor class: Class 2, stranded and compacted
  • Conductor standard: ABNT NBR NM 280
Phase Insulation
  • Material: Cross-linked polyethylene (XLPE) or polyethylene (PE), according to the specified design
  • Weather-resistant insulation
  • XLPE insulation with a nominal operating temperature of 90°C in the supplied construction data
Neutral Conductor

CA – Aluminium Neutral

  • Aluminium 1350 wires
  • H19 temper
  • Conventional round-stranded construction

CAL – Aluminium Alloy Neutral

  • Aluminium alloy 6201 wires
  • T81 temper
  • Conventional round-stranded construction
  • According to ABNT NBR 10298
Neutral Conductor Insulation
  • Available with XLPE insulation in light blue when specified
  • Bare neutral conductor configurations are also available

Cable Configurations

ConfigurationConstruction
DuplexOne phase conductor and one neutral conductor
TriplexTwo phase conductors and one neutral conductor
QuadruplexThree phase conductors and one neutral conductor

Conductor Identification

The phase conductors are identified by insulation color:

  • Single-phase: Black
  • Two-phase: Black and grey
  • Three-phase: Black, grey, and red

For insulated-neutral configurations, the neutral conductor insulation can be supplied in light blue when requested.

Maximum Operating Temperatures

Operating ConditionMaximum Temperature
Continuous operation90°C
Overload130°C
Short circuit250°C

Reference Standards

  • ABNT NBR 8182: Self-supporting multiplex power cables with extruded PE or XLPE insulation for voltages up to 0.6/1 kV – Performance requirements.
  • ABNT NBR NM 280: Conductors of insulated cables (IEC 60228, MOD).
  • ABNT NBR 10298: Bare cables with aluminium-magnesium-silicon alloy for overhead lines – Specification.

Manufacturing and Customization

Pre-assembled aluminium multiplex cables can be supplied in Duplex, Triplex, and Quadruplex configurations, with insulated or bare neutral conductors.

Conductor cross-sections, neutral conductor materials, insulation options, and cable configurations can be selected according to the applicable standard, technical specification, and project requirements.

Technical Data – XLPE, Insulated Neutral

Technical Data – XLPE, Bare Neutral

Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Isolado

TipoSeção Nominal (mm²)Condutor FaseCondutor NeutroDiâmetro externo aprox (mm)Peso Líquido (kg/km)
Diâmetro do Condutor (mm)Espessura de Isolação (mm)Resistência Elétrica Máxima (Ω/km)Formação (nº fios x mm)Espessura de Isolação (mm)Carga de Ruptura mín (kgf)
CACAL
Duplex1×10 + 104,01,23,087×1,361,2199–12,996,4
1×16 + 164,71,21,917×1,701,2306–14,6135
1×25 + 255,91,41,207×2,111,4455–17,8207
1×35 + 356,91,60,877×2,501,6626111320,8284
1×50 + 508,11,60,647×3,001,6852160223,5377
Triplex2×10 + 104,01,23,087×1,361,2199–13,8142
2×16 + 164,71,21,917×1,701,2306–15,6199
2×25 + 255,91,41,207×2,111,4455–19,2304
2×35 + 356,91,60,877×2,501,6626111322,4420
2×50 + 508,11,60,647×3,001,6852160225,3551
Quadruplex3×10 + 104,01,23,087×1,361,2199–15,4188
3×16 + 164,71,21,917×1,701,2306–17,3264
3×25 + 255,91,41,207×2,111,4455–21,3403
3×35 + 356,91,60,877×2,501,6626111324,8555
3×50 + 508,11,60,647×3,001,6852160228,0726
3×70 + 709,71,80,447×3,451,81102203032,61004
3×95 + 7011,52,00,327×3,452,01102203037,91270
3×120 + 7012,92,00,257×3,452,01102203041,31500

Cabo Multiplexado AL XLPE 0,6/1kV – Neutro Nu

TipoSeção Nominal (mm²)Condutor FaseCondutor NeutroDiâmetro externo aprox (mm)Peso Líquido (kg/km)
Diâmetro do Condutor (mm)Espessura de Isolação (mm)Resistência Elétrica Máxima (Ω/km)Formação (nº fios x mm)Carga de Ruptura mín (kgf)
CACAL
Duplex1×10 + 104,01,23,087×1,36199–10,574
1×16 + 164,71,21,917×1,70306–12,2109
1×25 + 255,91,41,207×2,11455–15,0167
1×35 + 356,91,60,877×2,50626111317,6231
1×50 + 508,11,60,647×3,00852160220,3311
Triplex2×10 + 104,01,23,087×1,36199–13,8119
2×16 + 164,71,21,917×1,70306–15,3173
2×25 + 255,91,41,207×2,11455–18,8266
2×35 + 356,91,60,877×2,50626111321,8367
2×50 + 508,11,60,647×3,00852160224,4485
Quadruplex3×10 + 104,01,23,087×1,36199–15,4165
3×16 + 164,71,21,917×1,70306–17,0238
3×25 + 255,91,41,207×2,11455–20,9365
3×35 + 356,91,60,877×2,50626111324,2502
3×50 + 508,11,60,647×3,00852160227,1660
3×70 + 709,71,80,447×3,451102203031,9920
3×95 + 7011,52,00,327×3,451102203037,21185
3×120 + 7012,92,00,257×3,451102203040,61415
DADOS CONSTRUTIVOSFormação do cabo(mm²)Condutor FaseCondutor NeutroDiâmetro externo
aproximado (mm)
Resistência
elétrica nominal
C.C. a 20°C
(Ω/km)
Massa líquida
aproximada
(kg/km)
Diâmetro nominal
do condutor (mm)
Material
da isolação
Espessura nominal
da isolação(mm)
Nº de
fios
Diâmetro nominal do
condutor (mm)
Tipo(4)
DUPLEX1x1x10+104,08XLPE 90°C1,274,08CA10,603,0877
1x1x16+164,60XLPE 90°C1,275,12CA12,201,91107
1x1x25+255,60XLPE 90°C1,476,33CA14,701,20163
1x1x35+356,70XLPE 90°C1,677,50CA17,400,868238
1x1x50+507,80XLPE 90°C1,679,00CA20,000,641331
1x1x70+709,95XLPE 90°C1,8710,40CA24,000,443424
TRIPLEX2x1x10+104,08XLPE 90°C1,274,08CA14,003,08125
2x1x16+164,60XLPE 90°C1,275,12CA15,101,91169
2x1x25+255,60XLPE 90°C1,476,33CA18,101,20260
2x1x35+356,70XLPE 90°C1,677,50CA21,400,868377
2x1x50+507,80XLPE 90°C1,679,00CA23,800,641527
2x1x70+709,95XLPE 90°C1,8710,40CA29,300,443679
QUADRUPLEX3x1x10+104,08XLPE 90°C1,274,08CA15,703,08165
3x1x16+164,60XLPE 90°C1,275,12CA16,901,91236
3x1x25+255,60XLPE 90°C1,476,33CA20,301,20349
3x1x35+356,70XLPE 90°C1,677,50CA23,900,868518
3x1x50+507,80XLPE 90°C1,679,00CA26,500,641724
3x1x70+709,95XLPE 90°C1,8710,40CA32,700,443924
3x1x95+7011,80XLPE 90°C2,0710,40CA37,600,3201,148
3x1x95+9511,80XLPE 90°C2,0712,33CA38,100,3201,335
3x1x120+7013,40XLPE 90°C2,0710,40CA40,600,2531,420
3x1x120+12013,40XLPE 90°C2,01914,50CA41,900,2531,574

(4) Condutor neutro tipo CAA (alumínio com alma de aço zincado) e CAL (alumínio liga) sob consulta.

ParameterSpecification
(5) Duplexcomposto por um condutor fase e um condutor neutro.
(6) Triplexcomposto por dois condutores fase e um condutor neutro.
(7) Quadruplexcomposto por três condutores fase e um condutor neutro.

Frequently Asked Questions

1. What is a pre-assembled aluminum multiplex cable?

It is an insulated overhead cable used in low-voltage power distribution networks and household service connections. It is also known as Cabo Multiplexado.

2. What is the rated voltage?

The specified rated voltage is 0.6/1 kV.

3. What are Duplex, Triplex, and Quadruplex configurations?

Duplex contains one phase conductor and one neutral conductor. Triplex contains two phase conductors and one neutral conductor. Quadruplex contains three phase conductors and one neutral conductor.

4. Which conductor material is used for the phase conductors?

The phase conductors are made of aluminium 1350, stranded and compacted according to the supplied construction description and ABNT NBR NM 280.

5. What neutral conductor options are available?

The neutral conductor can be supplied in aluminium 1350 (CA), aluminium alloy 6201 (CAL), or other specified constructions. CAA, with a galvanized steel core, is also mentioned in the supplied construction notes as an option upon request.

6. Is the neutral conductor insulated?

Both insulated-neutral and bare-neutral configurations are included in the supplied technical data. For insulated-neutral versions, light-blue XLPE insulation can be requested.

7. What is the maximum operating temperature?

The supplied data specifies 90°C in continuous operation, 130°C under overload, and 250°C under short-circuit conditions.

8. Which standards apply to this cable?

The reference standards are ABNT NBR 8182, ABNT NBR NM 280, and ABNT NBR 10298.

9. Where is multiplex cable commonly used?

It is used in low-voltage overhead distribution, residential service connections, rural electrification, and locations where underground cable installation is costly or where space is limited.

Applicable Standards

IEC 60228

Certificate Display

ISO 9001 Quality Management System
ISO 9001 Certificate (2025–2028)
ISO 9001 Certificate (NOA)
CE — Verification of Conformity
RoHS Compliance Attestation (EU)
Low Voltage Directive Attestation (EU)

Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.

Factory Tour

Why Choose Us

50+ years of experience Trusted manufacturing expertise since 1969
International standards IEC, ASTM, BS, CSA and other global standards
Strict quality control Comprehensive testing throughout production
Large production capacity Reliable supply for utility and EPC projects
Fast global delivery Efficient manufacturing and worldwide shipping
Technical support Expert assistance from inquiry to project completion

Packing & Shipping

  • Wooden, steel or steel-wood drums; drum length to customer requirement
  • Drum marking per customer / utility specification
  • Both drum ends sealed and protected for sea freight
Get in touch

Ready for Your Next Cable Project?

Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.

  • Emailinfo@qzcablegroup.com
  • WhatsApp / WeChat+86 173 3570 4553
  • Contact personChloe · Export Department
  • Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China

    The more specific the standard and size, the faster we can quote.
    Inquiry WhatsApp Email