One-stop Solution for Wire & Cable · Since 1969
ACSR-OC, ACSR/AW-OC & ACSR/AW-TR/OC – Medium Voltage Aerial Insulated Conductors
LV & MV Aerial Cables

ACSR-OC, ACSR/AW-OC & ACSR/AW-TR/OC – Medium Voltage Aerial Insulated Conductors

ACSR-OC, ACSR/AW-OC, ACSR/AW-TR/OC, ACSR-OC cable manufacturer, ACSR/AW insulated conductor, 6.6kV aerial insulated conductor, 22.9kV overhead cable, XLPE insulated ACSR, aluminum clad steel reinforced conductor, KS C 3138, ES-6145-0021, medium voltage aerial conductor

  • 6.6 kV – 22.9 kV Overhead Distribution Networks
  • XLPE Insulation | ACSR or Aluminium-Clad Steel Core
  • Tracking-Retardant Option: ACSR/AW-TR/OC
  • Custom Specifications | Direct Factory Supply | MOQ: 10KM

Product Overview

QZ Cable supplies ACSR-OC, ACSR/AW-OC, and ACSR/AW-TR/OC aerial insulated conductors for medium-voltage overhead power distribution networks. Designed for rated voltage applications from 6.6 kV to 22.9 kV, these products combine stranded reinforced conductors with weather-resistant XLPE insulation.

The conductor designs are intended for overhead installations under normal service conditions. They must be installed using insulators and/or spacers suitable for the system voltage. Compatibility between the cable covering, insulators, spacers, and other installation components should also be considered.

The product series includes conventional ACSR reinforced conductors and ACSR/AW designs incorporating aluminum-clad steel wires. Depending on the type, the insulation system may also include a semi-conductive layer or an additional anti-tracking layer.

Product Types

1. ACSR-OC

ACSR-OC is an aluminium conductor steel reinforced overhead conductor with an XLPE weather-resistant covering.

  • Conductor: Stranded, circular compressed ACSR.
  • Conductor screen: Extruded black semi-conducting layer.
  • Insulation: Black, weather-resistant XLPE.
  • Normal operating temperature: 90°C, according to the supplied product description.

2. ACSR/AW-OC

ACSR/AW-OC uses an aluminium-clad steel reinforced conductor with an outdoor weather-resistant XLPE insulation system.

The supplied construction description identifies the following components:

  • Reinforcing wire: Stranded aluminum-clad steel (AW).
  • Conductor: Standard aluminium conductor.
  • Interior semi-conductive layer: Black semi-conductive thermosetting compound.
  • Insulation: Black, weather-resistant cross-linked polyethylene (XLPE).

3. ACSR/AW-TR/OC

ACSR/AW-TR/OC is an aluminium conductor, aluminum-clad steel reinforced outdoor XLPE insulated wire with an additional tracking-resistant layer.

The supplied construction description identifies:

  • Reinforcing wire: Stranded aluminum-clad steel (AW).
  • Conductor: Standard aluminium conductor.
  • Interior semi-conductive layer: Black semi-conductive thermosetting compound.
  • Insulation: Weather-resistant XLPE, natural color.
  • Outer layer: Black semi-conductive thermosetting compound for tracking resistance.

Applications

ACSR-OC, ACSR/AW-OC, and ACSR/AW-TR/OC are designed primarily for the distribution of electrical energy through overhead power networks.

Typical application considerations include:

  • Medium-voltage overhead distribution networks.
  • Aerial installations operating at 6.6 kV to 22.9 kV, depending on the product design.
  • Installations using voltage-rated insulators and/or spacers.
  • Outdoor environments requiring weather-resistant insulation.
  • Distribution systems where the specified conductor reinforcement and insulation construction are required.

The installation design should account for the electrical compatibility of the covering, insulators, spacers, and associated fittings.

Key Features

  • Reinforced conductor construction: Stranded ACSR or ACSR/AW conductor designs.
  • Weather-resistant XLPE: Insulation designed for outdoor overhead service.
  • Semi-conductive layer: Specified for the conductor insulation system.
  • Tracking-resistant option: ACSR/AW-TR/OC includes an additional black semi-conductive outer layer as described in the supplied construction information.
  • Multiple voltage classes: Product data covers 6.6 kV and 22.9 kV applications.
  • Different conductor sizes: Available configurations vary by product type and voltage rating.

Applicable Standards

  • KS C 3138 – Outdoor XLPE-insulated ACSR wires for the specified Korean product range.
  • ES-6145-0021 – Utility technical specification referenced for 22.9 kV ACSR/AW-TR/OC designs.
  • IEC 60228 – Conductor requirements, where applicable and specified.
  • Relevant customer or utility specifications – For conductor construction, insulation, electrical tests and acceptance criteria.

The exact standard, edition and test requirements should be confirmed for each voltage rating and product type. A 22.9 kV TR design should not automatically be described as fully covered by the 6.6 kV scope of KS C 3138.

Technical Specifications

1. 6.6 kV ACSR-OC Aerial Insulated Conductors

Nominal Size (mm²)Aluminium WiresSteel WiresConductor Diameter (mm)XLPE Insulation Thickness (mm)Cable Diameter (mm)Rated Strength (kgf)Approx. Weight (kg/km)
326/SB1/2.67.22.011.21,090185
586/SB1/3.59.72.514.71,900325
956/SB1/3.512.02.517.02,360455

2. 22.9 kV ACSR-OC Aerial Insulated Conductors

Nominal Size (mm²)Aluminium WiresSteel WiresConductor Diameter (mm)XLPE Insulation Thickness (mm)Cable Diameter (mm)Rated Strength (kgf)Approx. Weight (kg/km)
326/SB1/2.67.23.013.21,090215
586/SB1/3.59.73.015.71,900340
956/SB1/3.512.03.519.02,360540
16018/SB1/3.215.44.023.43,080740

3. 6.6 kV ACSR/AW-OC Aerial Insulated Conductors

Nominal Size (mm²)Aluminium WiresSteel WiresConductor Diameter (mm)XLPE Insulation Thickness (mm)Cable Diameter (mm)Rated Strength (kgf)Approx. Weight (kg/km)
326/SB1/2.67.22.011.21,090180
586/SB1/3.59.72.514.71,900315
956/SB1/3.512.02.517.02,360445

4. 22.9 kV ACSR/AW-OC Aerial Insulated Conductors

Nominal Size (mm²)Aluminium WiresSteel WiresConductor Diameter (mm)XLPE Insulation Thickness (mm)Cable Diameter (mm)Rated Strength (kgf)Approx. Weight (kg/km)
326/SB1/2.67.23.013.21,090210
586/SB1/3.59.73.015.71,900330
956/SB1/3.512.03.519.02,360530
16018/SB1/3.215.44.023.43,080730
24018/SB1/4.018.94.027.04,5001,040

5. 22.9 kV ACSR/AW-TR/OC Technical Data

Nominal Sectional Area (mm²)Aluminium WiresAW WiresConductor Outer Diameter (mm)XLPE Insulation Thickness (mm)Overall Diameter (mm)Max. Conductor Resistance at 20°C (Ω/km)Min. Insulation Resistance at 20°C (Ω/km)Test Voltage (kV)Min. Tensile Load (kN / kgf)Approx. Weight (kg/km)Standard Length (m)
586/SB1/3.59.73.015.70.4841,500251,900360600
956/SB1/3.512.03.519.00.3021,500252,360520600
16018/SB1/3.215.44.023.40.1831,500253,080750600
24018/SB1/4.018.94.027.00.123—————

Note: The 240 mm² ACSR/AW-TR/OC row is incomplete in the supplied source. The available conductor data and resistance value are shown; the remaining values require confirmation.

Manufacturing and Project Requirements

QZ Cable can review ACSR-OC, ACSR/AW-OC, and ACSR/AW-TR/OC requirements according to the requested voltage class, conductor size, reinforcement design, insulation construction, and applicable standard.

For project enquiries, please provide:

  • Required cable type: ACSR-OC, ACSR/AW-OC, or ACSR/AW-TR/OC
  • Rated voltage and system requirements
  • Nominal conductor cross-sectional area
  • Applicable standard and technical specification
  • Required quantity and delivery length
  • Installation conditions and any special environmental requirements

Frequently Asked Questions

1. What is ACSR-OC cable?

ACSR-OC is an aluminium conductor steel reinforced overhead conductor with an outdoor XLPE insulation covering. It is designed for overhead power distribution applications.

2. What is the difference between ACSR-OC and ACSR/AW-OC?

Both are insulated overhead conductor designs. ACSR-OC uses a conventional steel-reinforced aluminium conductor, while ACSR/AW-OC uses aluminum-clad steel reinforcement as specified in the supplied product description.

3. What is ACSR/AW-TR/OC?

ACSR/AW-TR/OC is an aluminum-clad steel reinforced overhead conductor with weather-resistant XLPE insulation and an additional tracking-resistant outer layer, according to the supplied construction description.

4. What voltage ratings are available?

The supplied technical data covers 6.6 kV and 22.9 kV designs. The applicable voltage rating should be selected according to the network and project requirements.

5. How should these conductors be installed?

These products are intended for overhead installation on insulators and/or spacers suitable for the service voltage. Installation design should also consider dielectric compatibility between the covering and associated components.

6. What standards are referenced?

The supplied information references GB/T 14049, KS C 3138, and ES-6145-0021. The exact applicable standard depends on the product type and voltage class.

Certificate Display

ISO 9001 Quality Management System
ISO 9001 Certificate (2025–2028)
ISO 9001 Certificate (NOA)
CE — Verification of Conformity
RoHS Compliance Attestation (EU)
Low Voltage Directive Attestation (EU)

Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.

Factory Tour

Why Choose Us

50+ years of experience Trusted manufacturing expertise since 1969
International standards IEC, ASTM, BS, CSA and other global standards
Strict quality control Comprehensive testing throughout production
Large production capacity Reliable supply for utility and EPC projects
Fast global delivery Efficient manufacturing and worldwide shipping
Technical support Expert assistance from inquiry to project completion

Packing & Shipping

  • Wooden, steel or steel-wood drums; drum length to customer requirement
  • Drum marking per customer / utility specification
  • Both drum ends sealed and protected for sea freight
Get in touch

Ready for Your Next Cable Project?

Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.

  • Emailinfo@qzcablegroup.com
  • WhatsApp / WeChat+86 173 3570 4553
  • Contact personChloe · Export Department
  • Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China

    The more specific the standard and size, the faster we can quote.

    Related products

    0.61k V LV ABC Cable Aerial Bundle Conductor The aerial bundled cables designed for overhead distribution lines have all conductors made of aluminium 1350 and insulated with XLPE. Can be used for fixed installation as overhead power lines up to 1000 V incl. 16mm2 Twin Conductor Wire AAC PVC Parallel Aluminum Cable 16mm2 Twin Conductor Wire AAC PVC Parallel Aluminum Cable A3CS / AAACS Cable 12/20 kV – XLPE Insulated Aluminium Cable A3CS cable, AAACS cable, A3CS cable manufacturer, AAACS cable manufacturer, 12/20 kV cable, 20 kV aluminium cable, XLPE insulated aluminium cable, medium voltage aluminium cable, SPLN 41-10 cable, Indonesia medium voltage cable SIP-3 / SIPn-3 AAsXS / AAsXSn Medium Voltage Self-Supporting Aerial Cable SIP-3 cable, SIPn-3 cable, AAsXS wire, AAsXSn wire, 20kV aerial cable, 35kV overhead cable, medium voltage insulated wire, aluminium alloy overhead conductor, XLPE insulated aerial wire, flame-retardant overhead cable Polyethylene Covered Overhead Line Wire – POLY AL, POLY AAC & POLY ACSR polyethylene covered conductor, polyethylene covered wire, POLY AL conductor, POLY AAC conductor, POLY ACSR conductor, covered overhead line wire, PE covered aluminium conductor, weather resistant overhead conductor, covered ACSR wire NF2X / NFA2X Aerial Bundled Cable – Copper & Aluminium Conductors NF2X cable, NFA2X cable, NF2X aerial cable, NFA2X aerial bundled cable, copper aerial bundled cable, aluminium ABC cable, XLPE overhead cable, low voltage aerial cable, HD 626 cable, VDE 0276-626 High Conductivity Aluminium Alloy Conductor (AAAC) – AL5, AL6, AL7, AL57, AL59 & Alloy 1120 high conductivity aluminium alloy conductor, AAAC conductor, AAAC manufacturer, AL5 conductor, AL6 conductor, AL7 conductor, AL57 conductor, AL59 conductor, Alloy 1120 conductor, high conductivity AAAC, aluminium alloy overhead conductor, overhead transmission conductor, BS EN 50182 AAAC AL7 Conductor – All Aluminium Alloy Conductor AAAC conductor, AAAC AL7, AL7 conductor, AL7 aluminium alloy conductor, all aluminium alloy conductor, aluminium alloy overhead conductor, AAAC conductor manufacturer, EN 50182 conductor, overhead transmission conductor, overhead distribution conductor AAAC (AL59) Conductor – High-Strength Aluminium Alloy Conductor AAAC conductor, AAAC AL59, AL59 conductor, aluminum alloy conductor, all aluminium alloy conductor, AAAC conductor manufacturer, SS 424 08 14, SS EN 50182, overhead alloy conductor, stranded aluminum alloy conductor, grease filled AAAC conductor AAC (AL1) – All Aluminium Conductor AAC conductor, AAC conductor manufacturer, all aluminium conductor, AL1 conductor, AAC overhead conductor, bare aluminium conductor, aluminium stranded conductor, SS EN 50182, overhead distribution conductor, aluminium power conductor AAAC — Aluminum Alloy Conductor AAAC conductor, AAAC conductor manufacturer, all aluminum alloy conductor, AAAC cable, ASTM B399 AAAC, aluminum alloy overhead conductor, overhead transmission conductor, overhead distribution conductor, AAAC 6201, bare overhead conductor AAC — All Aluminum Conductor AAC conductor, AAC conductor manufacturer, all aluminium conductor, all aluminum conductor, AAC cable, aluminum stranded conductor, aluminium stranded conductor, Aluminum 1350-H19 conductor, ASTM B230, ASTM B231, AS/NZS 1531, DIN 48201 Part 5, GOST 839-80, BS 215-1, BS EN 50182, IEC 61089, bare overhead conductor, overhead distribution conductor. ACSR — Aluminum Conductor Steel Reinforced ACSR conductor, ACSR conductor manufacturer, ACSR cable, ACSR/AW conductor, ACSR/TW conductor, aluminum conductor steel reinforced, aluminum clad steel reinforced conductor, trapezoidal wire ACSR, overhead transmission conductor, bare overhead conductor, ASTM B232, ASTM B549, ASTM B779, IEC 61089.
    Inquiry WhatsApp Email