BS7629-1 — Fire Resistant Instrumention Cable
The Mica+xlPe or sR Insulated & Overall screened Multicore Fire Resistant Instrumentation cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of…
- Standards: BS 5308/BS · IEC 60331-21 · BS 6387 · BS 8434-1 · BS 5839-1 · NF C32-070-2.3
Product Description
RE-2X(St)H…CI. FE 180 PH30 ( CU/MGT+XLPE/OSCR/LSZH 300/500V Class 2 )
RE-2G(St)H…CI. FE 180 PH30 ( CU/SR/OSCR/LSZH 300/500V Class 2 )
RE-2X(St)HSWAH…CI. FE 180 PH30 ( CU/MGT+XLPE/OSCR/LSZH/SWA/LSZH 300/500V Class 2 )
RE-2G(St)HSWAH…CI. FE 180 PH30 ( CU/SR/OSCR/LSZH/SWA/LSZH 300/500V Class 2 )
APPLICATION
The Mica+xlPe or sR Insulated & Overall screened Multicore Fire Resistant Instrumentation cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
STANDARDS
Basic design to BS 5308/BS 7629-1
FIRE PERFORMANCE
| CIRCUIT INTEGRITY | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
| CIRCUIT INTEGRITY WITH MECHANICAL SHOCK | EN 50200(PH30); CEI 20-36/4-0 |
| CIRCUIT INTEGRITY WITH MECHANICAL SHOCK & WATER SPRAY | EN 50200 annex E |
| SYSTEM CIRCUIT INTEGRITY | DIN 4102-12, E30 depending on lay system |
| FLAME RETARDANCE (SINGLE VERTICAL WIRE TEST) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
| REDUCED FIRE PROPAGATION (VERTICALLY-MOUNTED BUNDLED WIRES & CABLE TEST) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
| HALOGEN FREE | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
| NO CORROSIVE GAS EMISSION | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
| MINIMUM SMOKE EMISSION | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
| NO TOXIC GASES | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
300/500 V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound or fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
Overall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire.
Inner Sheath(optional):Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
Armouring(optional): Galvanized steel wire armour
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1(Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour: White with black numberings.
Sheath Colour: Orange (other colours on request).
TYPE CODE
RE- Instrumentation cable H Halogen free & zero halogen
2X XLPE 2G Silicon Rubber
(St) Static shield of aluminium tape SWA Steel Wire Armoured
FE180 Insulation integrity (950°C 180 minutes) CI Circuit integrity
PH 90 Fire Test for 90 mins at 830°C
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 6 x Overall Diameter (unarmoured cables with silicone rubber insulation)
8 x Overall Diameter (unarmoured cables with XLPE insulation)
10 x Overall Diameter (armoured cables)
Electrical PROPERTIES
| DIELECTRIC TEST: | 2000 V r.m.s. x 5′ (core/core) |
| INSULATION RESISTANCE | XLPE: ≥1000 MΩ x km (at 20°C) SR: ≥300 MΩ x km (at 20°C) |
| SHORT CIRCUIT TEMPERATURE | XLPE: 250°C SR: 350°C |
CONSTRUCTION PARAMETERS
| CONDUCTOR | RE-2X(ST)H.CI. FE 180 PH30 RE-2G(ST)H.CI. FE 180 PH30 | RE-2X(ST)HSWAH…CI. FE 180 PH30 RE-2G(ST)HSWAH…CI. FE 180 PH30 | ||||||
| NO. OF CORE X CROSS SECTION | NO./ NOMINAL DIAMETER OF STRANDS | NOMINAL INSULATION THICKNESS | UNARMOURED | ARMOURED | ||||
| NOMINAL OVERALL DIAMETER | APPROX. WEIGHT | DIAMETER UNDER ARMOUR | ARMOUR WIRE DIAMETER | NOMINAL OVERALL DIAMETER | APPROX. WEIGHT | |||
| MM2 | NO./MM | MM | MM | KG/KM | MM | MM | MM | KG/KM |
| 2 core | ||||||||
| 2×1.0 | 7/0.43 | 0.6 | 8.0 | 82 | 8.0 | 0.90 | 12.4 | 288 |
| 2×1.5 | 7/0.53 | 0.7 | 8.5 | 101 | 8.5 | 0.90 | 13.1 | 342 |
| 2×2.5 | 7/0.67 | 0.8 | 10.5 | 137 | 10.5 | 0.90 | 15.1 | 419 |
| 2×4 | 7/0.85 | 0.8 | 12.5 | 180 | 12.5 | 0.90 | 17.1 | 484 |
| 3 core | ||||||||
| 3×1.0 | 7/0.43 | 0.6 | 8.0 | 100 | 8.0 | 0.90 | 12.4 | 324 |
| 3×1.5 | 7/0.53 | 0.7 | 9.5 | 127 | 9.5 | 0.90 | 14.1 | 383 |
| 3×2.5 | 7/0.67 | 0.8 | 12.0 | 176 | 12.0 | 0.90 | 16.6 | 466 |
| 3×4 | 7/0.85 | 0.8 | 13.5 | 236 | 13.5 | 0.90 | 18.1 | 560 |
| 4 core | ||||||||
| 4×1.0 | 7/0.43 | 0.6 | 9.0 | 127 | 9.0 | 0.90 | 13.6 | 383 |
| 4×1.5 | 7/0.53 | 0.7 | 10.5 | 161 | 10.5 | 0.90 | 15.1 | 445 |
| 4×2.5 | 7/0.67 | 0.8 | 13.0 | 224 | 13.0 | 0.90 | 17.6 | 548 |
| 4×4 | 7/0.85 | 0.8 | 15.0 | 302 | 15.0 | 1.25 | 20.5 | 772 |
| 7 core | ||||||||
| 7×1.0 | 7/0.43 | 0.6 | 11.0 | 187 | 11.0 | 0.9 | 15.6 | 485 |
| 7×1.5 | 7/0.53 | 0.7 | 12.5 | 250 | 12.5 | 0.90 | 17.3 | 597 |
| 7×2.5 | 7/0.67 | 0.8 | 15.0 | 354 | 15.0 | 1.25 | 20.5 | 862 |
| 12 core | ||||||||
| 12×1.5 | 7/0.53 | 0.7 | 16.0 | 402 | 16.0 | 1.25 | 21.7 | 997 |
| 12×2.5 | 7/0.67 | 0.8 | 20.0 | 585 | 20.0 | 1.60 | 26.4 | 1421 |
| 19 core | ||||||||
| 19×1.5 | 7/0.53 | 0.7 | 19.0 | 597 | 19.0 | 1.60 | 25.6 | 1465 |
| 19×2.5 | 7/0.67 | 0.8 | 24.0 | 873 | 24.0 | 1.60 | 30.6 | 1837 |
Note : Other conductor sizes & core configurations are available upon request.
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
UL — instrumentation cables
Soft annealed bare or tinned copper conductors and PVC flame retardant insulations and jackets are the standard for 300V instrumentation installation. Constructions with heat resistant PVC/PVC that have three or more conductors and 20 AWG or larger conductors may also be used for direct burial…
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions