PAS — instrumentation cables
These cables are designed to connect electrical instrumentation and communication systems in and around process plants and similar applications. Generally used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each…
- Standards: BS EN 60228 · BS EN 50290-2-23 · BS EN 50290-2-29 · BS EN 50290-2-22
Product Description
Application
These cables are designed to connect electrical instrumentation and communication systems in and around process plants and similar applications. Generally used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each pair limits the consequence of crosstalk.
Construction
| CONDUCTOR | Annealed copper, sizes: 0.5mm² mulitistranded(Class 5), 0.5 mm² and 1.0 mm² solid(Class 1), 1.5mm² or 2.5 multistranded(Class 2) to BS EN 60228 |
| INSULATION | thermoplastic PE to BS EN 50290-2-23:2002, grade L/MD or a cross-linked PE to BS EN 50290-2-29 |
| PAIRING | Two insulated conductors uniformly twisted together with a lay not exceeding 100mm, Two-pair cables without individual pair screens (quads) shall have four cores laid in quad formation round a central dummy |
| COLOUR CODE | See technical information |
| INDIVIDUAL SCREEN | Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm² |
| BINDER TAPE | Non-hygroscopic binder tape of minimum thickness 0.023 mm |
| COLLECTIVE SCREEN | Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm² |
| OUTER SHEATH | extruded sheath of a PVC compound conforming to BS EN 50290-2-22:2002, grade TM51 |
| SHEATH COLOUR | Generally black |
Electrical Properties
Temperature range: above 0˚C( fixed installation)
-15˚C to +65˚C(during operation )
| CONDUCTOR AREA SIZE | MM² | 0.5 | 0.5 | 1.0 | 1.5 | 2.5 | |
| CONDUCTOR STRANDING | NO. X MM | 1 x 0.8 | 16 x 0.2 | 1 x 1.13 | 7 x 0.53 | 7 x 0.67 | |
| CONDUCTOR RESISTANCE MAX | OHM/KM | 36.8 | 39.7 | 18.4 | 12.3 | 7.6 | |
| INSULATION RESISTANCE MIN | INDIVIDUAL CONDUCTOR | GOHM/KM | 5 | 5 | 5 | 5 | 5 |
| INDIVIDUAL SCREEN | MOHM/KM | 1 | 1 | 1 | 1 | 1 | |
| CAPACITANCE UNBALANCE AT 1 KHZ(PAIR TO PAIR SCREEN) | PF/250M | 250 | |||||
| MAX. MUTUAL CAPACITANCE @ 1 KHZ FOR NON OS OR OS CABLES (EXCEPT ONE-PAIR AND TWO-PAIRS) | PF/M | 75 | 75 | 75 | 85 | 105 | |
| MAX. MUTUAL CAPACITANCE @ 1 KHZ IS/OS CABLES (INCLUDE 1 PAIR AND 2 PAIR) |
PF/M | 115 | 115 | 115 | 120 | 140 | |
| MAX. L/R RATIO FOR ADJACENT CORES(INDUCTANCE/RESISTANCE) | ΜH/OHM | 25 | 25 | 25 | 40 | 60 | |
| TEST VOLTAGE | V | 2000 | 2000 | 2000 | 2000 | 2000 | |
| RATED VOLTAGE | V | 300/500 | 300/500 | 300/500 | 300/500 | 300/500 | |
Parameter
| NUMBER OF PAIRS |
NUMBER AND DIAMETER OF WIRES | NOMINAL CONDUCTOR CROSS- SECTIONAL AREA | NOMINAL THICKNESS OF INSULATION | NOMINAL THICKNESS OF SHEATH | NOMINAL DIAMETER OF CABLE |
| NO./MM | MM² | MM | MM | MM | |
| olid conductor 0.5mm² | |||||
| 2 | 1/0.8 | 0.5 | 0.5 | 0.9 | 8.5 |
| 5 | 1/0.8 | 0.5 | 0.5 | 0.9 | 10.9 |
| 10 | 1/0.8 | 0.5 | 0.5 | 1.1 | 15.6 |
| 15 | 1/0.8 | 0.5 | 0.5 | 1.2 | 18.1 |
| 20 | 1/0.8 | 0.5 | 0.5 | 1.3 | 20.4 |
| 30 | 1/0.8 | 0.5 | 0.5 | 1.4 | 24.2 |
| 50 | 1/0.8 | 0.5 | 0.5 | 1.7 | 31.2 |
| tranded conductor 0.5 mm² | |||||
| 2 | 16/0.2 | 0.5 | 0.6 | 0.9 | 9.7 |
| 5 | 16/0.2 | 0.5 | 0.6 | 1 | 12.6 |
| 10 | 16/0.2 | 0.5 | 0.6 | 1.2 | 18 |
| 15 | 16/0.2 | 0.5 | 0.6 | 1.3 | 20.9 |
| 20 | 16/0.2 | 0.5 | 0.6 | 1.4 | 23.6 |
| 30 | 16/0.2 | 0.5 | 0.6 | 1.6 | 28.2 |
| 50 | 16/0.2 | 0.5 | 0.6 | 1.8 | 36.1 |
| olid conductor 1.0 mm² | |||||
| 2 | 1/1.13 | 1 | 0.6 | 0.9 | 10.3 |
| 5 | 1/1.13 | 1 | 0.6 | 1 | 13.5 |
| 10 | 1/1.13 | 1 | 0.6 | 1.2 | 19.4 |
| 15 | 1/1.13 | 1 | 0.6 | 1.4 | 22.7 |
| 20 | 1/1.13 | 1 | 0.6 | 1.5 | 25.7 |
| 30 | 1/1.13 | 1 | 0.6 | 1.6 | 30.4 |
| 50 | 1/1.13 | 1 | 0.6 | 1.9 | 39.1 |
| tranded conductor 1.5 mm² | |||||
| 2 | 7/0.53 | 1.5 | 0.6 | 1 | 12.1 |
| 5 | 7/0.53 | 1.5 | 0.6 | 1.1 | 15.8 |
| 10 | 7/0.53 | 1.5 | 0.6 | 1.4 | 22.9 |
| 15 | 7/0.53 | 1.5 | 0.6 | 1.5 | 26.6 |
| 20 | 7/0.53 | 1.5 | 0.6 | 1.6 | 30.1 |
| 30 | 7/0.53 | 1.5 | 0.6 | 1.8 | 35.8 |
| 50 | 7/0.53 | 1.5 | 0.6 | 2.2 | 46.2 |
| tranded conductor 2.5 mm² | |||||
| 2 | 7/0.67 | 2.5 | 0.6 | 1 | 13.5 |
| 5 | 7/0.67 | 2.5 | 0.6 | 1.2 | 17.9 |
| 10 | 7/0.67 | 2.5 | 0.6 | 1.5 | 25.9 |
| 15 | 7/0.67 | 2.5 | 0.6 | 1.6 | 30.1 |
| 20 | 7/0.67 | 2.5 | 0.6 | 1.8 | 34.3 |
| 30 | 7/0.67 | 2.5 | 0.6 | 2 | 40.8 |
| 50 | 7/0.67 | 2.5 | 0.6 | 2.4 | 52.6 |
Applicable Standards
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
Related solutions
Power Distribution Cable Solutions
Qingzhou Cable provides low- and medium-voltage cable solutions for electrical distribution networks, supporting power delivery from substations to commercial, industrial and residential users.
Power Substation Cable Solutions
Solar & Renewable Energy Cable Solutions
Building & Infrastructure Cable Solutions
Mining Cable Solutions