Primary UD
† Ampacities are based on the following: Copper: Three shielded single insulated Copper conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835). Aluminum: Three shielded single insulated Aluminum conductors in…
- Low tension stripping compounds. RUS U-1 (15 kV & 25 kV). True triple extrusion system and closed handling raw materials system…
Product Description
Ampacity – Primary UD Cables – Copper and Aluminum
Primary UD TR-XLPE / LLDPE, Concentric Neutral
Primary UD EPR / LLDPE, Concentric Neutral
Primary UD TR-XLPE / PVC, Concentric Neutral
Primary UD EPR / PVC, Concentric Neutral
Primary UD PILC Replacement, EPR/PE
Primary UD TR-XLPE Insulated, Concentric Neutral
Primary UD EPR Insulated, Concentric Neutral
Ampacity – Primary UD Cables – Copper and Aluminum
Ampacity 100% and 133% Insulation Levels
| Size AWG or kcmil | Copper | Aluminum | ||||||
|---|---|---|---|---|---|---|---|---|
| 5 – 15 kV | 25 – 46 kV | 5 –15 kV | 25 – 46 kV | |||||
| 1/3 Neutral | Full Neutral | 1/3 Neutral | Full Neutral | 1/3 Neutral | Full Neutral | 1/3 Neutral | Full Neutral | |
| amp | amp | amp | amp | |||||
| 2 | 160 | 160 | – | – | 125 | 125 | – | – |
| 1 | 187 | 185 | 189 | 188 | 146 | 145 | 147 | 147 |
| 1/0 | 212 | 210 | 214 | 212 | 166 | 165 | 167 | 167 |
| 2/0 | 241 | 238 | 248 | 245 | 189 | 188 | 194 | 193 |
| 3/0 | 273 | 268 | 281 | 276 | 214 | 213 | 220 | 218 |
| 4/0 | 309 | 300 | 317 | 309 | 244 | 241 | 250 | 247 |
| 250 | 336 | – | 344 | – | 266 | – | 273 | – |
| 350 | 398 | – | 407 | – | 320 | – | 326 | – |
| 500 | 476 | – | 476 | – | 394 | – | 392 | – |
| 750 | 547 | – | 555 | – | 476 | – | 486 | – |
| 1000 | 620 | – | 625 | – | 550 | – | 556 | – |
| 1/6 Neutral | Full Neutral | 1/6 Neutral | Full Neutral | 1/6 Neutral | Full Neutral | 1/6 Neutral | Full Neutral | |
| 1000 | 658 | – | 658 | – | 580 | – | 573 | – |
† Ampacities are based on the following:
Copper: Three shielded single insulated Copper conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835).
Aluminum: Three shielded single insulated Aluminum conductors in buried ducts,single circuit,25 °C ambient earth temperature,75% load factor,90 RHO and 90 °C conductor temperature (IEEE Std. 835).
Primary UD TR-XLPE / LLDPE, Concentric Neutral
Features
Low tension stripping compounds.
RUS U-1 (15 kV & 25 kV).
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
On request, sealed conductor with strand filled compound passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
When requested, strand filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.
On request, dual sealed cable (strand filled on conductor + WSP on neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.
On request, can be UL Listed as MV90 for use in accordance with Article 328 of the NEC.
On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.
Specifications
Maximum operating voltage:
• 5 kV – 46 kV, 100 and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
| Parameter | Specification |
|---|---|
| 1. Conductor | Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231. |
| On request | strand filled. |
| Sizes | 8 AWG – 1000 kcmil. |
| On request | larger sizes. |
| 2. Conductor Shield | Semi conducting cross-linked polyethylene (XLPE). |
| On request | super-clean and super-smooth materials. |
-
Insulation: Thermoset tree-retardant crosslinked polyethylene (TR-XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Concentric Neutral: Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced.
Full or 1/3 Neutral.
| Parameter | Specification |
|---|---|
| On request options | alternate neutral constructions, Water Swellable Powder (WSP), and ripcords. |
| 6. Jacket | Extruded to fill (Encapsulated) Black sunlight resistant linear low density polyethylene (LLDPE), with three Red Stripes. |
| On request | semiconducting PE or Black HDPE. |
Configuration Options:
On request, Triplex or Paralleled configurations.
5 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | mil | in | lb/kft | AWG | mil | in | lb/m.ft | ||||
| Copper 100% Insulation Level (90 mil) | ||||||||||||
| 2 | 7 | 0.50 | 6 | 14 | 50 | 0.81 | 469 | 16 | 14 | 50 | 0.81 | 589 |
| 1 | 19 | 0.54 | 7 | 14 | 50 | 0.84 | 547 | 13 | 12 | 50 | 0.88 | 730 |
| 1/0 | 19 | 0.58 | 9 | 14 | 50 | 0.88 | 653 | 16 | 12 | 50 | 0.92 | 870 |
| 2/0 | 19 | 0.63 | 11 | 14 | 50 | 0.93 | 779 | 13 | 10 | 50 | 1.00 | 1089 |
| 3/0 | 19 | 0.68 | 14 | 14 | 50 | 0.98 | 941 | 16 | 10 | 50 | 1.05 | 1309 |
| 4/0 | 19 | 0.73 | 18 | 14 | 50 | 1.03 | 1146 | 16 | 9 | 50 | 1.14 | 1613 |
| 250 | 37 | 0.79 | 13 | 12 | 50 | 1.12 | 1340 | — | — | — | — | — |
| 350 | 37 | 0.89 | 18 | 12 | 50 | 1.23 | 1785 | — | — | — | — | — |
| 500 | 37 | 1.02 | 17 | 10 | 50 | 1.42 | 2535 | — | — | — | — | — |
| 750 | 61 | 1.21 | 20 | 9 | 80 | 1.70 | 3731 | — | — | — | — | — |
| 1000 | 61 | 1.36 | 26 | 9 | 80 | 1.85 | 4807 | — | — | — | — | — |
| Aluminum 100% Insulation Level (90 mil) | ||||||||||||
| 2 | 1 | 0.48 | 6 | 14 | 50 | 0.78 | 311 | 10 | 14 | 50 | 0.78 | 360 |
| 2 | 7 | 0.50 | 6 | 14 | 50 | 0.81 | 325 | 10 | 14 | 50 | 0.81 | 374 |
| 1 | 19 | 0.54 | 6 | 14 | 50 | 0.84 | 355 | 13 | 14 | 50 | 0.84 | 439 |
| 1/0 | 1 | 0.54 | 6 | 14 | 50 | 0.85 | 370 | 16 | 14 | 50 | 0.85 | 491 |
| 1/0 | 19 | 0.58 | 6 | 14 | 50 | 0.88 | 389 | 16 | 14 | 50 | 0.88 | 510 |
| 2/0 | 19 | 0.62 | 7 | 14 | 50 | 0.93 | 444 | 13 | 12 | 50 | 0.96 | 629 |
| 3/0 | 19 | 0.67 | 9 | 14 | 50 | 0.98 | 519 | 16 | 12 | 50 | 1.01 | 738 |
| 4/0 | 19 | 0.73 | 11 | 14 | 50 | 1.03 | 606 | 13 | 10 | 50 | 1.11 | 921 |
| 250 | 37 | 0.79 | 13 | 14 | 50 | 1.09 | 686 | 16 | 10 | 50 | 1.17 | 1071 |
| 350 | 37 | 0.89 | 18 | 14 | 50 | 1.19 | 879 | 16 | 9 | 50 | 1.29 | 1356 |
| 500 | 37 | 1.02 | 16 | 12 | 50 | 1.38 | 1208 | 29 | 10 | 50 | 1.42 | 1823 |
| 750 | 61 | 1.22 | 15 | 10 | 80 | 1.69 | 1798 | — | — | — | — | — |
| 1000 | 61 | 1.37 | 16 | 9 | 80 | 1.86 | 2292 | — | — | — | — | — |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities: Refer to beginning of section.
8 kV TR-XLPE Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
| Copper 100% Insulation Level (115 mil) | ||||||||||||
| 2 | 7 | 0.55 | 6 | 14 | 50 | 0.86 | 496 | 16 | 14 | 50 | 0.86 | 616 |
| 1 | 19 | 0.59 | 7 | 14 | 50 | 0.90 | 576 | 13 | 12 | 50 | 0.93 | 760 |
| 1/0 | 19 | 0.63 | 9 | 14 | 50 | 0.94 | 683 | 16 | 12 | 50 | 0.97 | 901 |
| 2/0 | 19 | 0.68 | 11 | 14 | 50 | 0.98 | 810 | 13 | 10 | 50 | 1.06 | 1123 |
| 3/0 | 19 | 0.73 | 14 | 14 | 50 | 1.03 | 974 | 16 | 10 | 50 | 1.11 | 1344 |
| 4/0 | 19 | 0.78 | 18 | 14 | 50 | 1.09 | 1180 | 16 | 9 | 50 | 1.19 | 1651 |
| 250 | 37 | 0.84 | 13 | 12 | 50 | 1.18 | 1377 | 25 | 10 | 50 | 1.22 | 1923 |
| 350 | 37 | 0.94 | 18 | 12 | 50 | 1.28 | 1826 | 22 | 8 | 50 | 1.37 | 2628 |
| 500 | 37 | 1.07 | 17 | 10 | 50 | 1.47 | 2582 | 31 | 8 | 50 | 1.53 | 3617 |
| 750 | 61 | 1.26 | 20 | 9 | 80 | 1.75 | 3787 | — | — | — | — | — |
| 1000 | 61 | 1.41 | 26 | 9 | 80 | 1.90 | 4868 | — | — | — | — | — |
| Aluminum 100% Insulation Level (115 mil) | ||||||||||||
| 2 | 1 | 0.53 | 6 | 14 | 50 | 0.83 | 337 | 10 | 14 | 50 | 0.83 | 386 |
| 2 | 7 | 0.55 | 6 | 14 | 50 | 0.86 | 352 | 10 | 14 | 50 | 0.86 | 401 |
| 1 | 19 | 0.59 | 6 | 14 | 50 | 0.89 | 383 | 13 | 14 | 50 | 0.89 | 467 |
| 1/0 | 1 | 0.59 | 6 | 14 | 50 | 0.90 | 399 | 16 | 14 | 50 | 0.90 | 519 |
| 1/0 | 19 | 0.63 | 6 | 14 | 50 | 0.93 | 419 | 16 | 14 | 50 | 0.93 | 540 |
| 2/0 | 19 | 0.68 | 7 | 14 | 50 | 0.98 | 475 | 13 | 12 | 50 | 1.01 | 661 |
| 3/0 | 19 | 0.73 | 9 | 14 | 50 | 1.03 | 552 | 16 | 12 | 50 | 1.06 | 772 |
| 4/0 | 19 | 0.78 | 11 | 14 | 50 | 1.08 | 640 | 13 | 10 | 50 | 1.16 | 958 |
| 250 | 37 | 0.84 | 13 | 14 | 50 | 1.14 | 722 | 16 | 10 | 50 | 1.22 | 1110 |
| 350 | 37 | 0.94 | 18 | 14 | 50 | 1.24 | 918 | 16 | 9 | 50 | 1.34 | 1398 |
| 500 | 37 | 1.07 | 16 | 12 | 50 | 1.43 | 1253 | 29 | 10 | 50 | 1.47 | 1869 |
| 750 | 61 | 1.27 | 15 | 10 | 80 | 1.74 | 1853 | — | — | — | — | — |
| 1000 | 61 | 1.42 | 16 | 9 | 80 | 1.91 | 2353 | — | — | — | — | — |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities: Refer to beginning of section.
15 kV TR-XLPE Insulated
| 1/3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lbs/Mt | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lbs/Mt |
| Copper 100% Insulation Level (175 mil) | |||||||||||||||
| 2 | 7 | 0.68 | 6 | 14 | 50 | 0.98 | 568 | 2 | 7 | 0.68 | 16 | 14 | 50 | 0.98 | 689 |
| 1 | 19 | 0.71 | 7 | 14 | 50 | 1.02 | 651 | 1 | 19 | 0.71 | 13 | 12 | 50 | 1.05 | 837 |
| 1/0 | 19 | 0.75 | 9 | 14 | 50 | 1.06 | 761 | 1/0 | 19 | 0.75 | 25 | 14 | 50 | 1.06 | 954 |
| 2/0 | 19 | 0.80 | 11 | 14 | 50 | 1.10 | 892 | 1/0 | 19 | 0.75 | 16 | 12 | 50 | 1.09 | 982 |
| 3/0 | 19 | 0.85 | 14 | 14 | 50 | 1.15 | 1059 | 2/0 | 19 | 0.80 | 32 | 14 | 50 | 1.10 | 1145 |
| 4/0 | 19 | 0.90 | 18 | 14 | 50 | 1.21 | 1270 | 2/0 | 19 | 0.80 | 20 | 12 | 50 | 1.14 | 1166 |
| 250 | 37 | 0.96 | 21 | 14 | 50 | 1.26 | 1451 | 2/0 | 19 | 0.80 | 13 | 10 | 50 | 1.18 | 1210 |
| 250 | 37 | 0.96 | 13 | 12 | 50 | 1.30 | 1474 | 3/0 | 19 | 0.85 | 16 | 10 | 50 | 1.23 | 1435 |
| 350 | 37 | 1.06 | 29 | 14 | 50 | 1.39 | 1930 | 4/0 | 19 | 0.90 | 32 | 12 | 50 | 1.24 | 1692 |
| 350 | 37 | 1.06 | 18 | 12 | 50 | 1.42 | 1955 | 4/0 | 19 | 0.90 | 20 | 10 | 50 | 1.28 | 1722 |
| 500 | 37 | 1.19 | 26 | 12 | 50 | 1.55 | 2640 | 4/0 | 19 | 0.90 | 16 | 9 | 50 | 1.31 | 1748 |
| 500 | 37 | 1.19 | 17 | 10 | 50 | 1.59 | 2702 | 250 | 37 | 0.96 | 25 | 10 | 50 | 1.34 | 2022 |
| 750 | 61 | 1.38 | 25 | 10 | 80 | 1.85 | 3892 | 350 | 37 | 1.06 | 22 | 8 | 50 | 1.52 | 2766 |
| 750 | 61 | 1.38 | 20 | 9 | 80 | 1.87 | 3928 | 500 | 37 | 1.19 | 31 | 8 | 80 | 1.71 | 3808 |
| 1000 | 61 | 1.53 | 26 | 9 | 80 | 2.05 | 5069 | — | — | — | — | — | — | — | — |
| Aluminum 100% Insulation Level (175 mil) | |||||||||||||||
| 2 | 1 | 0.65 | 6 | 14 | 50 | 0.95 | 407 | 2 | 1 | 0.65 | 10 | 14 | 50 | 0.95 | 455 |
| 2 | 7 | 0.67 | 6 | 14 | 50 | 0.98 | 424 | 2 | 7 | 0.67 | 10 | 14 | 50 | 0.98 | 472 |
| 1 | 19 | 0.71 | 6 | 14 | 50 | 1.02 | 457 | 1 | 19 | 0.71 | 13 | 14 | 50 | 1.02 | 541 |
| 1/0 | 1 | 0.72 | 6 | 14 | 50 | 1.02 | 473 | 1/0 | 1 | 0.72 | 16 | 14 | 50 | 1.02 | 594 |
| 1/0 | 19 | 0.75 | 6 | 14 | 50 | 1.06 | 496 | 1/0 | 19 | 0.75 | 16 | 14 | 50 | 1.06 | 617 |
| 2/0 | 19 | 0.80 | 7 | 14 | 50 | 1.10 | 555 | 2/0 | 19 | 0.80 | 20 | 14 | 50 | 1.10 | 712 |
| 3/0 | 19 | 0.85 | 9 | 14 | 50 | 1.15 | 636 | 2/0 | 19 | 0.80 | 13 | 12 | 50 | 1.13 | 744 |
| 4/0 | 19 | 0.90 | 11 | 14 | 50 | 1.21 | 729 | 3/0 | 19 | 0.85 | 25 | 14 | 50 | 1.15 | 829 |
| 250 | 37 | 0.96 | 13 | 14 | 50 | 1.26 | 815 | 3/0 | 19 | 0.85 | 16 | 12 | 50 | 1.18 | 859 |
| 350 | 37 | 1.06 | 18 | 14 | 50 | 1.39 | 1042 | 4/0 | 19 | 0.90 | 32 | 14 | 50 | 1.21 | 982 |
| 350 | 37 | 1.06 | 11 | 12 | 50 | 1.42 | 1066 | 4/0 | 19 | 0.90 | 20 | 12 | 50 | 1.24 | 1006 |
| 500 | 37 | 1.19 | 25 | 14 | 50 | 1.52 | 1331 | 4/0 | 19 | 0.90 | 13 | 10 | 50 | 1.28 | 1052 |
| 500 | 37 | 1.19 | 16 | 12 | 50 | 1.55 | 1368 | 250 | 37 | 0.96 | 25 | 12 | 50 | 1.30 | 1164 |
| 750 | 61 | 1.40 | 24 | 12 | 80 | 1.82 | 1945 | 250 | 37 | 0.96 | 16 | 10 | 50 | 1.34 | 1208 |
| 750 | 61 | 1.40 | 15 | 10 | 80 | 1.86 | 1992 | 350 | 37 | 1.06 | 32 | 12 | 50 | 1.42 | 1468 |
| 1000 | 61 | 1.54 | 31 | 12 | 80 | 2.00 | 2446 | 350 | 37 | 1.06 | 20 | 10 | 50 | 1.46 | 1503 |
| 1000 | 61 | 1.54 | 20 | 10 | 80 | 2.04 | 2516 | 350 | 37 | 1.06 | 16 | 9 | 50 | 1.49 | 1532 |
| — | — | — | — | — | — | — | — | 500 | 37 | 1.19 | 29 | 10 | 50 | 1.59 | 1988 |
| — | — | — | — | — | — | — | — | 750 | 61 | 1.40 | 28 | 8 | 80 | 1.91 | 2956 |
| — | — | — | — | — | — | — | — | 1000 | 61 | 1.54 | 37 | 8 | 80 | 2.09 | 3770 |
15 kV TR-XLPE Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft |
| Copper 133% Insulation Level (220 mil) | |||||||
| 2 | 7 | 0.77 | 6 | 14 | 50 | 1.07 | 628 |
| 1 | 19 | 0.81 | 7 | 14 | 50 | 1.11 | 713 |
| 1/0 | 19 | 0.85 | 9 | 14 | 50 | 1.15 | 826 |
| 2/0 | 19 | 0.89 | 11 | 14 | 50 | 1.19 | 959 |
| 3/0 | 19 | 0.94 | 14 | 14 | 50 | 1.24 | 1129 |
| 4/0 | 19 | 1.00 | 18 | 14 | 50 | 1.30 | 1343 |
| 250 | 37 | 1.05 | 21 | 14 | 50 | 1.38 | 1552 |
| 250 | 37 | 1.05 | 13 | 12 | 50 | 1.41 | 1577 |
| 300 | 37 | 1.13 | 25 | 14 | 50 | 1.45 | 1794 |
| 300 | 37 | 1.13 | 16 | 12 | 50 | 1.49 | 1831 |
| 350 | 37 | 1.16 | 29 | 14 | 50 | 1.48 | 2015 |
| 350 | 37 | 1.16 | 18 | 12 | 50 | 1.52 | 2042 |
| 500 | 37 | 1.28 | 26 | 12 | 80 | 1.71 | 2799 |
| 500 | 37 | 1.28 | 17 | 10 | 80 | 1.75 | 2866 |
| 750 | 61 | 1.47 | 25 | 10 | 80 | 1.94 | 4003 |
| 750 | 61 | 1.47 | 20 | 9 | 80 | 1.96 | 4040 |
| 1000 | 61 | 1.62 | 26 | 9 | 80 | 2.14 | 5192 |
| Aluminum 133% Insulation Level (220 mil) | |||||||
| 2 | 1 | 0.74 | 6 | 14 | 50 | 1.04 | 465 |
| 2 | 7 | 0.76 | 6 | 14 | 50 | 1.07 | 483 |
| 1 | 19 | 0.80 | 6 | 14 | 50 | 1.11 | 519 |
| 1/0 | 1 | 0.81 | 6 | 14 | 50 | 1.11 | 535 |
| 1/0 | 19 | 0.84 | 6 | 14 | 50 | 1.15 | 560 |
| 2/0 | 19 | 0.89 | 7 | 14 | 50 | 1.19 | 622 |
| 3/0 | 19 | 0.94 | 9 | 14 | 50 | 1.24 | 705 |
| 4/0 | 19 | 0.99 | 11 | 14 | 50 | 1.30 | 801 |
| 250 | 37 | 1.05 | 13 | 14 | 50 | 1.38 | 914 |
| 350 | 37 | 1.15 | 18 | 14 | 50 | 1.48 | 1125 |
| 500 | 37 | 1.28 | 25 | 14 | 50 | 1.61 | 1421 |
| 500 | 37 | 1.28 | 16 | 12 | 80 | 1.70 | 1528 |
| 750 | 61 | 1.49 | 24 | 12 | 80 | 1.91 | 2053 |
| 750 | 61 | 1.49 | 15 | 10 | 80 | 1.95 | 2102 |
| 1000 | 61 | 1.64 | 31 | 12 | 80 | 2.09 | 2565 |
| 1000 | 61 | 1.64 | 20 | 10 | 80 | 2.13 | 2637 |
| 1000 | 61 | 1.64 | 16 | 9 | 80 | 2.16 | 2676 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation In | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft |
| Copper 133% Insulation Level (220 mil) | |||||||
| 2 | 7 | 0.77 | 16 | 14 | 50 | 1.07 | 749 |
| 1 | 19 | 0.81 | 13 | 12 | 50 | 1.14 | 902 |
| 1/0 | 19 | 0.85 | 25 | 14 | 50 | 1.15 | 1019 |
| 1/0 | 19 | 0.85 | 16 | 12 | 50 | 1.18 | 1049 |
| 2/0 | 19 | 0.89 | 32 | 14 | 50 | 1.19 | 1212 |
| 2/0 | 19 | 0.89 | 20 | 12 | 50 | 1.23 | 1235 |
| 2/0 | 19 | 0.89 | 13 | 10 | 50 | 1.27 | 1282 |
| 3/0 | 19 | 0.94 | 16 | 10 | 50 | 1.32 | 1510 |
| 4/0 | 19 | 1.00 | 32 | 12 | 50 | 1.33 | 1767 |
| 4/0 | 19 | 1.00 | 20 | 10 | 50 | 1.38 | 1800 |
| 4/0 | 19 | 1.00 | 16 | 9 | 50 | 1.40 | 1827 |
| 250 | 37 | 1.05 | 25 | 10 | 50 | 1.46 | 2129 |
| 300 | 37 | 1.13 | 18 | 8 | 50 | 1.58 | 2489 |
| 350 | 37 | 1.16 | 22 | 8 | 50 | 1.61 | 2858 |
| 500 | 37 | 1.28 | 31 | 8 | 80 | 1.80 | 3910 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (220 mil) | |||||||
| 2 | 1 | 0.74 | 10 | 14 | 50 | 1.04 | 513 |
| 2 | 7 | 0.76 | 10 | 14 | 50 | 1.07 | 531 |
| 1 | 19 | 0.80 | 13 | 14 | 50 | 1.11 | 603 |
| 1/0 | 1 | 0.81 | 16 | 14 | 50 | 1.11 | 655 |
| 1/0 | 19 | 0.84 | 16 | 14 | 50 | 1.15 | 681 |
| 2/0 | 19 | 0.89 | 20 | 14 | 50 | 1.19 | 779 |
| 2/0 | 19 | 0.89 | 13 | 12 | 50 | 1.22 | 812 |
| 3/0 | 19 | 0.94 | 25 | 14 | 50 | 1.24 | 898 |
| 3/0 | 19 | 0.94 | 16 | 12 | 50 | 1.27 | 930 |
| 4/0 | 19 | 0.99 | 32 | 14 | 50 | 1.30 | 1055 |
| 4/0 | 19 | 0.99 | 20 | 12 | 50 | 1.33 | 1080 |
| 4/0 | 19 | 0.99 | 13 | 10 | 50 | 1.37 | 1129 |
| 250 | 37 | 1.05 | 25 | 12 | 50 | 1.41 | 1266 |
| 250 | 37 | 1.05 | 16 | 10 | 50 | 1.45 | 1313 |
| 350 | 37 | 1.15 | 32 | 12 | 50 | 1.51 | 1553 |
| 350 | 37 | 1.15 | 20 | 10 | 50 | 1.55 | 1591 |
| 350 | 37 | 1.15 | 16 | 9 | 50 | 1.58 | 1620 |
| 500 | 37 | 1.28 | 29 | 10 | 80 | 1.75 | 2152 |
| 750 | 61 | 1.49 | 28 | 8 | 80 | 2.01 | 3069 |
| 1000 | 61 | 1.64 | 37 | 8 | 80 | 2.18 | 3894 |
25 kV TR-XLPE Insulated
| 1/3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft |
| Copper 100% Insulation Level (260 mil) | |||||||||||||||
| 1 | 19 | 0.89 | 7 | 14 | 50 | 1.19 | 773 | 1 | 19 | 0.89 | 13 | 12 | 50 | 1.23 | 963 |
| 1/0 | 19 | 0.93 | 9 | 14 | 50 | 1.23 | 888 | 1/0 | 19 | 0.93 | 25 | 14 | 50 | 1.23 | 1081 |
| 2/0 | 19 | 0.97 | 11 | 14 | 50 | 1.28 | 1023 | 1/0 | 19 | 0.93 | 16 | 12 | 50 | 1.27 | 1113 |
| 3/0 | 19 | 1.02 | 14 | 14 | 50 | 1.35 | 1220 | 2/0 | 19 | 0.97 | 13 | 10 | 50 | 1.35 | 1350 |
| 4/0 | 19 | 1.08 | 18 | 14 | 50 | 1.40 | 1438 | 3/0 | 19 | 1.02 | 16 | 10 | 50 | 1.42 | 1605 |
| 250 | 37 | 1.13 | 21 | 14 | 50 | 1.46 | 1626 | 4/0 | 19 | 1.08 | 32 | 12 | 50 | 1.44 | 1864 |
| 250 | 37 | 1.13 | 13 | 12 | 50 | 1.49 | 1653 | 4/0 | 19 | 1.08 | 20 | 10 | 50 | 1.48 | 1900 |
| 350 | 37 | 1.24 | 29 | 14 | 50 | 1.56 | 2094 | 4/0 | 19 | 1.08 | 16 | 9 | 50 | 1.51 | 1928 |
| 350 | 37 | 1.24 | 18 | 12 | 50 | 1.60 | 2123 | 250 | 37 | 1.13 | 25 | 10 | 50 | 1.54 | 2207 |
| 500 | 37 | 1.37 | 17 | 10 | 80 | 1.83 | 2959 | 350 | 37 | 1.24 | 22 | 8 | 80 | 1.75 | 3012 |
| 750 | 61 | 1.56 | 25 | 10 | 80 | 2.05 | 4155 | 500 | 37 | 1.37 | 31 | 8 | 80 | 1.88 | 4006 |
| 750 | 61 | 1.56 | 20 | 9 | 80 | 2.08 | 4194 | — | — | — | — | — | — | — | |
| 1000 | 61 | 1.70 | 26 | 9 | 80 | 2.23 | 5306 | — | — | — | — | — | — | — | |
| 1000 | 61 | 1.70 | 21 | 8 | 80 | 2.25 | 5365 | — | — | — | — | — | — | — | |
| Aluminum 100% Insulation Level (260 mil) | |||||||||||||||
| 1 | 19 | 0.88 | 6 | 14 | 50 | 1.19 | 578 | 1 | 19 | 0.88 | 13 | 14 | 50 | 1.19 | 662 |
| 1/0 | 1 | 0.89 | 6 | 14 | 50 | 1.19 | 594 | 1/0 | 1 | 0.89 | 16 | 14 | 50 | 1.19 | 715 |
| 1/0 | 19 | 0.92 | 6 | 14 | 50 | 1.23 | 621 | 1/0 | 19 | 0.92 | 16 | 14 | 50 | 1.23 | 742 |
| 2/0 | 19 | 0.97 | 7 | 14 | 50 | 1.27 | 685 | 2/0 | 19 | 0.97 | 20 | 14 | 50 | 1.27 | 842 |
| 3/0 | 19 | 1.02 | 9 | 14 | 50 | 1.34 | 794 | 2/0 | 19 | 0.97 | 13 | 12 | 50 | 1.30 | 877 |
| 4/0 | 19 | 1.07 | 11 | 14 | 50 | 1.40 | 894 | 3/0 | 19 | 1.02 | 25 | 14 | 50 | 1.34 | 987 |
| 250 | 37 | 1.13 | 13 | 14 | 50 | 1.46 | 987 | 3/0 | 19 | 1.02 | 16 | 12 | 50 | 1.38 | 1021 |
| 350 | 37 | 1.23 | 18 | 14 | 50 | 1.56 | 1204 | 4/0 | 19 | 1.07 | 32 | 14 | 50 | 1.40 | 1147 |
| 500 | 37 | 1.36 | 25 | 14 | 80 | 1.75 | 1575 | 4/0 | 19 | 1.07 | 20 | 12 | 50 | 1.43 | 1175 |
| 500 | 37 | 1.36 | 16 | 12 | 80 | 1.78 | 1618 | 4/0 | 19 | 1.07 | 13 | 10 | 50 | 1.48 | 1227 |
| 750 | 61 | 1.57 | 24 | 12 | 80 | 2.02 | 2200 | 250 | 37 | 1.13 | 25 | 12 | 50 | 1.49 | 1341 |
| 750 | 61 | 1.57 | 15 | 10 | 80 | 2.06 | 2252 | 250 | 37 | 1.13 | 16 | 10 | 50 | 1.53 | 1390 |
| 1000 | 61 | 1.72 | 31 | 12 | 80 | 2.17 | 2674 | 350 | 37 | 1.23 | 32 | 12 | 50 | 1.59 | 1633 |
| 1000 | 61 | 1.72 | 20 | 10 | 80 | 2.21 | 2748 | 350 | 37 | 1.23 | 20 | 10 | 80 | 1.70 | 1740 |
| 1000 | 61 | 1.72 | 16 | 9 | 80 | 2.24 | 2789 | 350 | 37 | 1.23 | 16 | 9 | 80 | 1.72 | 1772 |
| — | — | — | — | — | — | — | — | 500 | 37 | 1.36 | 29 | 10 | 80 | 1.83 | 2244 |
| — | — | — | — | — | — | — | — | 750 | 61 | 1.57 | 28 | 8 | 80 | 2.12 | 3223 |
| — | — | — | — | — | — | — | — | 1000 | 61 | 1.72 | 37 | 8 | 80 | 2.27 | 4008 |
25 kV TR-XLPE Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| Copper 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 9 | 14 | 50 | 1.38 | 1013 |
| 2/0 | 19 | 1.09 | 11 | 14 | 50 | 1.42 | 1152 |
| 3/0 | 19 | 1.14 | 14 | 14 | 50 | 1.47 | 1330 |
| 4/0 | 19 | 1.20 | 18 | 14 | 50 | 1.53 | 1552 |
| 250 | 37 | 1.26 | 13 | 12 | 50 | 1.62 | 1775 |
| 350 | 37 | 1.36 | 18 | 12 | 80 | 1.78 | 2321 |
| 500 | 37 | 1.49 | 17 | 10 | 80 | 1.95 | 3106 |
| 750 | 61 | 1.68 | 20 | 9 | 80 | 2.20 | 4361 |
| 1000 | 61 | 1.83 | 26 | 9 | 80 | 2.35 | 5484 |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 1 | 1.01 | 6 | 14 | 50 | 1.31 | 691 |
| 1/0 | 19 | 1.05 | 6 | 14 | 50 | 1.37 | 744 |
| 2/0 | 19 | 1.09 | 7 | 14 | 50 | 1.42 | 812 |
| 3/0 | 19 | 1.14 | 9 | 14 | 50 | 1.47 | 903 |
| 4/0 | 19 | 1.20 | 11 | 14 | 50 | 1.52 | 1007 |
| 250 | 37 | 1.25 | 13 | 14 | 50 | 1.58 | 1105 |
| 350 | 37 | 1.35 | 18 | 14 | 80 | 1.74 | 1398 |
| 500 | 37 | 1.48 | 25 | 14 | 80 | 1.87 | 1715 |
| 500 | 37 | 1.48 | 16 | 12 | 80 | 1.91 | 1760 |
| 750 | 61 | 1.69 | 24 | 12 | 80 | 2.14 | 2361 |
| 750 | 61 | 1.69 | 15 | 10 | 80 | 2.18 | 2417 |
| 1000 | 61 | 1.84 | 31 | 12 | 80 | 2.29 | 2846 |
| 1000 | 61 | 1.84 | 20 | 10 | 80 | 2.33 | 2924 |
| 1000 | 61 | 1.84 | 16 | 9 | 80 | 2.36 | 2966 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| Copper 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 16 | 12 | 50 | 1.41 | 1241 |
| 2/0 | 19 | 1.09 | 13 | 10 | 50 | 1.50 | 1486 |
| 3/0 | 19 | 1.14 | 16 | 10 | 50 | 1.55 | 1721 |
| 4/0 | 19 | 1.20 | 16 | 9 | 80 | 1.69 | 2116 |
| 250 | 37 | 1.26 | 25 | 10 | 80 | 1.72 | 2398 |
| 350 | 37 | 1.36 | 22 | 8 | 80 | 1.88 | 3153 |
| 500 | 37 | 1.49 | 31 | 8 | 80 | 2.01 | 4157 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 1 | 1.01 | 16 | 14 | 50 | 1.31 | 811 |
| 1/0 | 19 | 1.05 | 16 | 14 | 50 | 1.37 | 865 |
| 2/0 | 19 | 1.09 | 20 | 14 | 50 | 1.42 | 969 |
| 2/0 | 19 | 1.09 | 13 | 12 | 50 | 1.45 | 1007 |
| 3/0 | 19 | 1.14 | 25 | 14 | 50 | 1.47 | 1096 |
| 3/0 | 19 | 1.14 | 16 | 12 | 50 | 1.50 | 1132 |
| 4/0 | 19 | 1.20 | 32 | 14 | 50 | 1.52 | 1260 |
| 4/0 | 19 | 1.20 | 20 | 12 | 50 | 1.55 | 1290 |
| 4/0 | 19 | 1.20 | 13 | 10 | 50 | 1.60 | 1346 |
| 250 | 37 | 1.25 | 25 | 12 | 50 | 1.61 | 1461 |
| 250 | 37 | 1.25 | 16 | 10 | 80 | 1.72 | 1581 |
| 350 | 37 | 1.35 | 32 | 12 | 80 | 1.78 | 1831 |
| 350 | 37 | 1.35 | 20 | 10 | 80 | 1.82 | 1876 |
| 350 | 37 | 1.35 | 16 | 9 | 80 | 1.84 | 1910 |
| 500 | 37 | 1.48 | 29 | 10 | 80 | 1.95 | 2389 |
| 750 | 61 | 1.69 | 28 | 8 | 80 | 2.24 | 3391 |
| 1000 | 61 | 1.84 | 37 | 8 | 80 | 2.39 | 4188 |
35 kV TR-XLPE Insulated
| 1/3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| Copper 100% Insulation Level (345 mil) | |||||||||||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 50 | 1.43 | 1059 | 1/0 | 19 | 1.10 | 25 | 14 | 50 | 1.43 | 1252 |
| 2/0 | 19 | 1.15 | 11 | 14 | 50 | 1.47 | 1200 | 1/0 | 19 | 1.10 | 16 | 12 | 50 | 1.46 | 1287 |
| 3/0 | 19 | 1.20 | 14 | 14 | 50 | 1.52 | 1379 | 2/0 | 19 | 1.15 | 32 | 14 | 50 | 1.47 | 1453 |
| 4/0 | 19 | 1.25 | 18 | 14 | 50 | 1.58 | 1603 | 2/0 | 19 | 1.15 | 20 | 12 | 50 | 1.51 | 1482 |
| 250 | 37 | 1.31 | 21 | 14 | 80 | 1.70 | 1863 | 2/0 | 19 | 1.15 | 13 | 10 | 50 | 1.55 | 1536 |
| 250 | 37 | 1.31 | 13 | 12 | 80 | 1.73 | 1895 | 3/0 | 19 | 1.20 | 16 | 10 | 50 | 1.60 | 1773 |
| 350 | 37 | 1.41 | 29 | 14 | 80 | 1.80 | 2346 | 4/0 | 19 | 1.25 | 32 | 12 | 50 | 1.61 | 2033 |
| 350 | 37 | 1.41 | 18 | 12 | 80 | 1.83 | 2380 | 4/0 | 19 | 1.25 | 20 | 10 | 80 | 1.72 | 2140 |
| 500 | 37 | 1.54 | 17 | 10 | 80 | 2.04 | 3219 | 4/0 | 19 | 1.25 | 16 | 9 | 80 | 1.74 | 2172 |
| 750 | 61 | 1.73 | 25 | 10 | 80 | 2.22 | 4391 | 250 | 37 | 1.31 | 25 | 10 | 80 | 1.77 | 2455 |
| 750 | 61 | 1.73 | 20 | 9 | 80 | 2.25 | 4433 | 350 | 37 | 1.41 | 22 | 8 | 80 | 1.93 | 3215 |
| 1000 | 61 | 1.88 | 26 | 9 | 80 | 2.40 | 5561 | 500 | 37 | 1.54 | 31 | 8 | 80 | 2.09 | 4273 |
| Aluminum 100% Insulation Level (345 mil) | |||||||||||||||
| 1/0 | 1 | 1.06 | 6 | 14 | 50 | 1.38 | 757 | 1/0 | 1 | 1.06 | 16 | 14 | 50 | 1.38 | 878 |
| 1/0 | 19 | 1.10 | 6 | 14 | 50 | 1.42 | 789 | 1/0 | 19 | 1.10 | 16 | 14 | 50 | 1.42 | 910 |
| 2/0 | 19 | 1.14 | 7 | 14 | 50 | 1.47 | 859 | 2/0 | 19 | 1.14 | 20 | 14 | 50 | 1.47 | 1016 |
| 3/0 | 19 | 1.19 | 9 | 14 | 50 | 1.52 | 951 | 2/0 | 19 | 1.14 | 13 | 12 | 50 | 1.50 | 1055 |
| 4/0 | 19 | 1.25 | 11 | 14 | 50 | 1.57 | 1057 | 3/0 | 19 | 1.19 | 25 | 14 | 50 | 1.52 | 1144 |
| 250 | 37 | 1.30 | 13 | 14 | 80 | 1.69 | 1223 | 3/0 | 19 | 1.19 | 16 | 12 | 50 | 1.55 | 1181 |
| 350 | 37 | 1.40 | 18 | 14 | 80 | 1.79 | 1454 | 4/0 | 19 | 1.25 | 32 | 14 | 50 | 1.57 | 1310 |
| 500 | 37 | 1.53 | 25 | 14 | 80 | 1.95 | 1822 | 4/0 | 19 | 1.25 | 20 | 12 | 50 | 1.61 | 1341 |
| 500 | 37 | 1.53 | 16 | 12 | 80 | 1.99 | 1868 | 4/0 | 19 | 1.25 | 13 | 10 | 80 | 1.71 | 1465 |
| 750 | 61 | 1.74 | 24 | 12 | 80 | 2.19 | 2431 | 250 | 37 | 1.30 | 25 | 12 | 80 | 1.73 | 1582 |
| 750 | 61 | 1.74 | 15 | 10 | 80 | 2.24 | 2488 | 250 | 37 | 1.30 | 16 | 10 | 80 | 1.77 | 1637 |
| 1000 | 61 | 1.89 | 31 | 12 | 80 | 2.34 | 2921 | 350 | 37 | 1.40 | 32 | 12 | 80 | 1.83 | 1889 |
| 1000 | 61 | 1.89 | 20 | 10 | 80 | 2.38 | 3000 | 350 | 37 | 1.40 | 20 | 10 | 80 | 1.87 | 1935 |
| 1000 | 61 | 1.89 | 16 | 9 | 80 | 2.41 | 3043 | 350 | 37 | 1.40 | 16 | 9 | 80 | 1.89 | 1970 |
| — | — | — | — | — | — | — | — | 500 | 37 | 1.53 | 29 | 10 | 80 | 2.03 | 2500 |
| — | — | — | — | — | — | — | — | 750 | 61 | 1.74 | 28 | 8 | 80 | 2.29 | 3464 |
| — | — | — | — | — | — | — | — | 1000 | 61 | 1.89 | 37 | 8 | 80 | 2.44 | 4265 |
35 kV TR-XLPE Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Site AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| Copper 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 50 | 1.58 | 1206 |
| 2/0 | 19 | 1.30 | 11 | 14 | 50 | 1.63 | 1351 |
| 3/0 | 19 | 1.35 | 14 | 14 | 80 | 1.74 | 1602 |
| 4/0 | 19 | 1.40 | 18 | 14 | 80 | 1.79 | 1834 |
| 250 | 37 | 1.46 | 13 | 12 | 80 | 1.88 | 2071 |
| 350 | 37 | 1.56 | 18 | 12 | 80 | 2.02 | 2614 |
| 500 | 37 | 1.69 | 17 | 10 | 80 | 2.19 | 3425 |
| 750 | 61 | 1.88 | 20 | 9 | 80 | 2.40 | 4660 |
| 1000 | 61 | 2.03 | 26 | 9 | 80 | 2.55 | 5802 |
| Aluminum 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 50 | 1.57 | 934 |
| 2/0 | 19 | 1.29 | 7 | 14 | 50 | 1.62 | 1008 |
| 3/0 | 19 | 1.34 | 9 | 14 | 80 | 1.73 | 1173 |
| 4/0 | 19 | 1.40 | 11 | 14 | 80 | 1.79 | 1287 |
| 250 | 37 | 1.45 | 13 | 14 | 80 | 1.84 | 1394 |
| 350 | 37 | 1.56 | 18 | 14 | 80 | 1.98 | 1681 |
| 500 | 37 | 1.68 | 25 | 14 | 80 | 2.11 | 2018 |
| 500 | 37 | 1.68 | 16 | 12 | 80 | 2.14 | 2068 |
| 750 | 61 | 1.89 | 24 | 12 | 80 | 2.34 | 2650 |
| 750 | 61 | 1.89 | 15 | 10 | 80 | 2.39 | 2710 |
| 1000 | 61 | 2.04 | 16 | 9 | 80 | 2.56 | 3282 |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Site AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| Copper 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 16 | 12 | 50 | 1.61 | 1438 |
| 2/0 | 19 | 1.30 | 13 | 10 | 80 | 1.76 | 1763 |
| 3/0 | 19 | 1.35 | 16 | 10 | 80 | 1.81 | 2006 |
| 4/0 | 19 | 1.40 | 16 | 9 | 80 | 1.89 | 2349 |
| 250 | 37 | 1.46 | 25 | 10 | 80 | 1.95 | 2635 |
| 350 | 37 | 1.56 | 22 | 8 | 80 | 2.11 | 3461 |
| 500 | 37 | 1.69 | 31 | 8 | 80 | 2.24 | 4484 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 50 | 1.57 | 934 |
| 2/0 | 19 | 1.29 | 7 | 14 | 50 | 1.62 | 1008 |
| 3/0 | 19 | 1.34 | 9 | 14 | 80 | 1.73 | 1173 |
| 4/0 | 19 | 1.40 | 11 | 14 | 80 | 1.79 | 1287 |
| 250 | 37 | 1.45 | 13 | 14 | 80 | 1.84 | 1394 |
| 350 | 37 | 1.56 | 18 | 14 | 80 | 1.98 | 1681 |
| 500 | 37 | 1.68 | 25 | 14 | 80 | 2.11 | 2018 |
| 500 | 37 | 1.68 | 16 | 12 | 80 | 2.14 | 2068 |
| 750 | 61 | 1.89 | 24 | 12 | 80 | 2.34 | 2650 |
| 750 | 61 | 1.89 | 15 | 10 | 80 | 2.39 | 2710 |
| 1000 | 61 | 2.04 | 16 | 9 | 80 | 2.56 | 3282 |
Primary UD EPR / LLDPE, Concentric Neutral 5 kV – 46 kV
Features
Low tension stripping compounds.
True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
On request, Sealed conductor with strand filled compound passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
When requested, Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.
On request, Dual sealed cable (Strand Filled on conductor + WSP on Neutral wires) meets the water penetration requirements in accordance with ICEA-T-34-664.
On request, can be UL Listed as MV90 for use in accordance with Article 328 of the NEC.
On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.
Specifications
Maximum operating voltage:
• 5 kV – 46 kV 100% and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
| Parameter | Specification |
|---|---|
| 1. Conductor | Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231. |
| On request | strand filled. |
| Sizes | 8 AWG – 1000 kcmil. |
| On request | larger sizes available. |
| 2. Conductor Shield | Semi conducting cross-linked polyethylene (XLPE). |
On request, super clean and super smooth materials.
| Parameter | Specification |
|---|---|
| 3. Insulation | Thermoset ethylene propylene rubber (EPR). |
| On request | amorphous EPR. |
| 4. Insulation Shield | Semi conducting cross-linked polyethylene (XLPE). |
| 5. Concentric Neutral | Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced. |
Full or 1/3 Neutral.
| Parameter | Specification |
|---|---|
| On request options | alternate neutral constructions, Water Swellable Powder (WSP), and ripcords. |
| 6. Jacket | Extruded to fill (Encapsulated) Black sunlight resistant linear low density polyethylene (LLDPE), with three Red Stripes. |
| On request | semiconducting PE or Black HDPE. |
Configuration Options:
On request: Triplex or Paralleled configurations.
Technical Data
5 kV EPR Insulated
| 1⁄3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| In | AWG | mil | in | lb/Aft | in | AWG | mil | in | lb/Aft | ||||||
| Copper 100% Insulation Level (90 mil) | |||||||||||||||
| 2 | 7 | 0.50 | 6 | 14 | 50 | 0.81 | 484 | 2 | 7 | 0.50 | 16 | 14 | 50 | 0.81 | 604 |
| 1 | 19 | 0.54 | 7 | 14 | 50 | 0.84 | 564 | 1 | 19 | 0.54 | 13 | 12 | 50 | 0.88 | 747 |
| 1/0 | 19 | 0.58 | 9 | 14 | 50 | 0.88 | 672 | 1/0 | 19 | 0.58 | 16 | 12 | 50 | 0.92 | 889 |
| 2/0 | 19 | 0.63 | 11 | 14 | 50 | 0.93 | 799 | 2/0 | 19 | 0.63 | 13 | 10 | 50 | 1.00 | 1109 |
| 3/0 | 19 | 0.68 | 14 | 14 | 50 | 0.98 | 963 | 3/0 | 19 | 0.68 | 16 | 10 | 50 | 1.05 | 1331 |
| 4/0 | 19 | 0.73 | 18 | 14 | 50 | 1.03 | 1170 | 4/0 | 19 | 0.73 | 16 | 9 | 50 | 1.14 | 1637 |
| 250 | 37 | 0.79 | 13 | 12 | 50 | 1.12 | 1366 | 250 | 37 | 0.79 | 25 | 10 | 50 | 1.17 | 1910 |
| 350 | 37 | 0.89 | 18 | 12 | 50 | 1.23 | 1815 | 350 | 37 | 0.89 | 22 | 8 | 50 | 1.32 | 2614 |
| 500 | 37 | 1.02 | 17 | 10 | 50 | 1.42 | 2569 | 500 | 37 | 1.02 | 31 | 8 | 50 | 1.47 | 3603 |
| 750 | 61 | 1.21 | 20 | 9 | 80 | 1.70 | 3773 | — | — | — | — | — | — | — | — |
| 1000 | 61 | 1.36 | 26 | 9 | 80 | 1.85 | 4854 | — | — | — | — | — | — | — | — |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities: Refer to beginning of section.
8 kV EPR Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| AWG | mil | in | lb/kft | ||||
| Copper 100% Insulation Level (115 mil) | |||||||
| 2 | 7 | 0.55 | 6 | 14 | 50 | 0.86 | 517 |
| 1 | 19 | 0.59 | 7 | 14 | 50 | 0.90 | 598 |
| 1/0 | 19 | 0.63 | 9 | 14 | 50 | 0.94 | 708 |
| 2/0 | 19 | 0.68 | 11 | 14 | 50 | 0.98 | 837 |
| 3/0 | 19 | 0.73 | 14 | 14 | 50 | 1.03 | 1003 |
| 4/0 | 19 | 0.78 | 18 | 14 | 50 | 1.09 | 1212 |
| 250 | 37 | 0.84 | 13 | 12 | 50 | 1.18 | 1412 |
| 350 | 37 | 0.94 | 18 | 12 | 50 | 1.28 | 1865 |
| 500 | 37 | 1.07 | 17 | 10 | 50 | 1.47 | 2627 |
| 750 | 61 | 1.26 | 20 | 9 | 80 | 1.75 | 3841 |
| 1000 | 61 | 1.41 | 26 | 9 | 80 | 1.90 | 4929 |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| AWG | mil | in | lb/kft | ||||
| Copper 100% Insulation Level (115 mil) | |||||||
| 2 | 7 | 0.55 | 16 | 14 | 50 | 0.86 | 637 |
| 1 | 19 | 0.59 | 13 | 12 | 50 | 0.93 | 782 |
| 1/0 | 19 | 0.63 | 16 | 12 | 50 | 0.97 | 925 |
| 2/0 | 19 | 0.68 | 13 | 10 | 50 | 1.06 | 1149 |
| 3/0 | 19 | 0.73 | 16 | 10 | 50 | 1.11 | 1373 |
| 4/0 | 19 | 0.78 | 16 | 9 | 50 | 1.19 | 1682 |
| 250 | 37 | 0.84 | 25 | 10 | 50 | 1.22 | 1957 |
| 350 | 37 | 0.94 | 22 | 8 | 50 | 1.37 | 2667 |
| 500 | 37 | 1.07 | 31 | 8 | 50 | 1.53 | 3663 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
15 kV EPR Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 100% Insulation Level (175 mil) | |||||||
| 2 | 7 | 0.68 | 6 | 14 | 50 | 0.98 | 604 |
| 1 | 19 | 0.71 | 7 | 14 | 50 | 1.02 | 689 |
| 1/0 | 19 | 0.75 | 9 | 14 | 50 | 1.06 | 803 |
| 2/0 | 19 | 0.80 | 11 | 14 | 50 | 1.10 | 937 |
| 3/0 | 19 | 0.85 | 14 | 14 | 50 | 1.15 | 1108 |
| 4/0 | 19 | 0.90 | 18 | 14 | 50 | 1.21 | 1323 |
| 250 | 37 | 0.96 | 13 | 12 | 50 | 1.30 | 1537 |
| 350 | 37 | 1.06 | 18 | 12 | 50 | 1.42 | 2019 |
| 500 | 37 | 1.19 | 17 | 10 | 50 | 1.59 | 2775 |
| 750 | 61 | 1.38 | 20 | 9 | 80 | 1.87 | 4015 |
| 1000 | 61 | 1.53 | 26 | 9 | 80 | 2.05 | 5167 |
| Aluminum 100% Insulation Level (175 mil) | |||||||
| 2 | 1 | 0.65 | 6 | 14 | 50 | 0.95 | 441 |
| 2 | 7 | 0.67 | 6 | 14 | 50 | 0.98 | 459 |
| 1 | 19 | 0.71 | 6 | 14 | 50 | 1.02 | 495 |
| 1/0 | 1 | 0.72 | 6 | 14 | 50 | 1.02 | 512 |
| 1/0 | 19 | 0.75 | 6 | 14 | 50 | 1.06 | 537 |
| 2/0 | 19 | 0.80 | 7 | 14 | 50 | 1.10 | 600 |
| 3/0 | 19 | 0.85 | 9 | 14 | 50 | 1.15 | 684 |
| 4/0 | 19 | 0.90 | 11 | 14 | 50 | 1.21 | 781 |
| 250 | 37 | 0.96 | 13 | 14 | 50 | 1.26 | 871 |
| 300 | 37 | 1.01 | 15 | 14 | 50 | 1.34 | 994 |
| 350 | 37 | 1.06 | 18 | 14 | 50 | 1.39 | 1106 |
| 500 | 37 | 1.19 | 25 | 14 | 50 | 1.52 | 1403 |
| 500 | 37 | 1.19 | 16 | 12 | 50 | 1.55 | 1441 |
| 750 | 61 | 1.40 | 24 | 12 | 80 | 1.82 | 2033 |
| 750 | 61 | 1.40 | 15 | 10 | 80 | 1.86 | 2079 |
| 1000 | 61 | 1.54 | 31 | 12 | 80 | 2.00 | 2544 |
| 1000 | 61 | 1.54 | 20 | 10 | 80 | 2.04 | 2614 |
| 1000 | 61 | 1.54 | 16 | 9 | 80 | 2.07 | 2651 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 100% Insulation Level (175 mil) | |||||||
| 2 | 7 | 0.68 | 16 | 14 | 50 | 0.98 | 725 |
| 1 | 19 | 0.71 | 13 | 12 | 50 | 1.05 | 876 |
| 1/0 | 19 | 0.75 | 16 | 12 | 50 | 1.09 | 1024 |
| 2/0 | 19 | 0.80 | 13 | 10 | 50 | 1.18 | 1255 |
| 3/0 | 19 | 0.85 | 16 | 10 | 50 | 1.23 | 1484 |
| 4/0 | 19 | 0.90 | 16 | 9 | 50 | 1.31 | 1801 |
| 250 | 37 | 0.96 | 25 | 10 | 50 | 1.34 | 2079 |
| 350 | 37 | 1.06 | 22 | 8 | 50 | 1.52 | 2830 |
| 500 | 37 | 1.19 | 31 | 8 | 80 | 1.71 | 3881 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 100% Insulation Level (175 mil) | |||||||
| 2 | 1 | 0.65 | 10 | 14 | 50 | 0.95 | 489 |
| 2 | 7 | 0.67 | 10 | 14 | 50 | 0.98 | 507 |
| 1 | 19 | 0.71 | 13 | 14 | 50 | 1.02 | 580 |
| 1/0 | 1 | 0.72 | 16 | 14 | 50 | 1.02 | 632 |
| 1/0 | 19 | 0.75 | 16 | 14 | 50 | 1.06 | 658 |
| 2/0 | 19 | 0.80 | 20 | 14 | 50 | 1.10 | 757 |
| 2/0 | 19 | 0.80 | 13 | 12 | 50 | 1.13 | 788 |
| 3/0 | 19 | 0.85 | 25 | 14 | 50 | 1.15 | 877 |
| 3/0 | 19 | 0.85 | 16 | 12 | 50 | 1.18 | 907 |
| 4/0 | 19 | 0.90 | 32 | 14 | 50 | 1.21 | 1034 |
| 4/0 | 19 | 0.90 | 20 | 12 | 50 | 1.24 | 1058 |
| 4/0 | 19 | 0.90 | 13 | 10 | 50 | 1.28 | 1104 |
| 250 | 37 | 0.96 | 25 | 12 | 50 | 1.30 | 1220 |
| 250 | 37 | 0.96 | 16 | 10 | 50 | 1.34 | 1264 |
| 350 | 37 | 1.06 | 32 | 12 | 50 | 1.42 | 1532 |
| 350 | 37 | 1.06 | 20 | 10 | 50 | 1.46 | 1567 |
| 350 | 37 | 1.06 | 16 | 9 | 50 | 1.49 | 1595 |
| 500 | 37 | 1.19 | 29 | 10 | 50 | 1.59 | 2060 |
| 750 | 61 | 1.40 | 28 | 8 | 80 | 1.91 | 3043 |
| 1000 | 61 | 1.54 | 37 | 8 | 80 | 2.09 | 3868 |
15 kV EPR Insulated
| 1⁄3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| In | AWG | mil | in | lb/Mt | In | AWG | mil | in | lb/Mt | ||||||
| Copper 133% Insulation Level (220 mil) | |||||||||||||||
| 2 | 7 | 0.77 | 6 | 14 | 50 | 1.07 | 678 | 2 | 7 | 0.77 | 16 | 14 | 50 | 1.07 | 798 |
| 1 | 19 | 0.81 | 7 | 14 | 50 | 1.11 | 766 | 1 | 19 | 0.81 | 13 | 12 | 50 | 1.14 | 955 |
| 1/0 | 19 | 0.85 | 9 | 14 | 50 | 1.15 | 883 | 1/0 | 19 | 0.85 | 16 | 12 | 50 | 1.18 | 1105 |
| 2/0 | 19 | 0.89 | 11 | 14 | 50 | 1.19 | 1020 | 2/0 | 19 | 0.89 | 13 | 10 | 50 | 1.27 | 1342 |
| 3/0 | 19 | 0.94 | 14 | 14 | 50 | 1.24 | 1195 | 3/0 | 19 | 0.94 | 16 | 10 | 50 | 1.32 | 1575 |
| 4/0 | 19 | 1.00 | 18 | 14 | 50 | 1.30 | 1414 | 4/0 | 19 | 1.00 | 16 | 9 | 50 | 1.40 | 1898 |
| 250 | 37 | 1.05 | 13 | 12 | 50 | 1.41 | 1653 | 250 | 37 | 1.05 | 25 | 10 | 50 | 1.46 | 2204 |
| 350 | 37 | 1.16 | 18 | 12 | 50 | 1.52 | 2126 | 350 | 37 | 1.16 | 22 | 8 | 50 | 1.61 | 2942 |
| 500 | 37 | 1.28 | 17 | 10 | 80 | 1.75 | 2962 | 500 | 37 | 1.28 | 31 | 8 | 80 | 1.80 | 4007 |
| 750 | 61 | 1.47 | 20 | 9 | 80 | 1.96 | 4154 | — | — | — | — | — | — | — | — |
| 1000 | 61 | 1.62 | 26 | 9 | 80 | 2.14 | 5320 | — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (220 mil) | |||||||||||||||
| 2 | 1 | 0.74 | 6 | 14 | 50 | 1.04 | 511 | 2 | 1 | 0.74 | 10 | 14 | 50 | 1.04 | 560 |
| 2 | 7 | 0.76 | 6 | 14 | 50 | 1.07 | 532 | 2 | 7 | 0.76 | 10 | 14 | 50 | 1.07 | 580 |
| 1 | 19 | 0.80 | 6 | 14 | 50 | 1.11 | 571 | 1 | 19 | 0.80 | 13 | 14 | 50 | 1.11 | 655 |
| 1/0 | 1 | 0.81 | 6 | 14 | 50 | 1.11 | 588 | 1/0 | 1 | 0.81 | 16 | 14 | 50 | 1.11 | 708 |
| 1/0 | 19 | 0.84 | 6 | 14 | 50 | 1.16 | 629 | 1/0 | 19 | 0.84 | 16 | 14 | 50 | 1.15 | 737 |
| 2/0 | 19 | 0.89 | 7 | 14 | 50 | 1.19 | 682 | 2/0 | 19 | 0.89 | 20 | 14 | 50 | 1.19 | 839 |
| 3/0 | 19 | 0.94 | 9 | 14 | 50 | 1.24 | 770 | 2/0 | 19 | 0.89 | 13 | 12 | 50 | 1.22 | 872 |
| 4/0 | 19 | 0.99 | 11 | 14 | 50 | 1.30 | 871 | 3/0 | 19 | 0.94 | 25 | 14 | 50 | 1.24 | 963 |
| 250 | 37 | 1.05 | 13 | 14 | 50 | 1.38 | 989 | 3/0 | 19 | 0.94 | 16 | 12 | 50 | 1.27 | 994 |
| 350 | 37 | 1.15 | 18 | 14 | 50 | 1.48 | 1209 | 4/0 | 19 | 0.99 | 32 | 14 | 50 | 1.30 | 1124 |
| 500 | 37 | 1.28 | 25 | 14 | 50 | 1.61 | 1517 | 4/0 | 19 | 0.99 | 20 | 12 | 50 | 1.33 | 1149 |
| 500 | 37 | 1.28 | 16 | 12 | 80 | 1.70 | 1623 | 4/0 | 19 | 0.99 | 13 | 10 | 50 | 1.37 | 1199 |
| 750 | 61 | 1.49 | 24 | 12 | 80 | 1.91 | 2167 | 250 | 37 | 1.05 | 25 | 12 | 50 | 1.41 | 1341 |
| 750 | 61 | 1.49 | 15 | 10 | 80 | 1.95 | 2216 | 250 | 37 | 1.05 | 16 | 10 | 50 | 1.45 | 1388 |
| 1000 | 61 | 1.64 | 31 | 12 | 80 | 2.09 | 2692 | 350 | 37 | 1.15 | 32 | 12 | 50 | 1.51 | 1637 |
| 1000 | 61 | 1.64 | 20 | 10 | 80 | 2.13 | 2764 | 350 | 37 | 1.15 | 20 | 10 | 50 | 1.55 | 1674 |
| 1000 | 61 | 1.64 | 16 | 9 | 80 | 2.16 | 2803 | 350 | 37 | 1.15 | 16 | 9 | 50 | 1.58 | 1704 |
| — | — | — | — | — | — | — | — | 500 | 37 | 1.28 | 29 | 10 | 80 | 1.75 | 2247 |
| — | — | — | — | — | — | — | — | 750 | 61 | 1.49 | 28 | 8 | 80 | 2.01 | 3183 |
| — | — | — | — | — | — | — | — | 1000 | 61 | 1.64 | 37 | 8 | 80 | 2.18 | 4021 |
25 kV EPR Insulated
| 1⁄3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/Kft |
| Copper 100% Insulation Level (260 mil) | |||||||
| 1 | 19 | 0.89 | 7 | 14 | 50 | 1.19 | 840 |
| 1/0 | 19 | 0.93 | 9 | 14 | 50 | 1.23 | 959 |
| 2/0 | 19 | 0.97 | 11 | 14 | 50 | 1.28 | 1099 |
| 3/0 | 19 | 1.02 | 14 | 14 | 50 | 1.35 | 1301 |
| 4/0 | 19 | 1.08 | 18 | 14 | 50 | 1.40 | 1525 |
| 250 | 37 | 1.13 | 13 | 12 | 50 | 1.49 | 1747 |
| 350 | 37 | 1.24 | 18 | 12 | 50 | 1.60 | 2227 |
| 500 | 37 | 1.37 | 17 | 10 | 80 | 1.83 | 3077 |
| 750 | 61 | 1.56 | 20 | 9 | 80 | 2.08 | 4333 |
| 1000 | 61 | 1.70 | 26 | 9 | 80 | 2.23 | 5461 |
| Aluminum 100% Insulation Level (260 mil) | |||||||
| 1 | 19 | 0.88 | 6 | 14 | 50 | 1.19 | 644 |
| 1/0 | 1 | 0.89 | 6 | 14 | 50 | 1.19 | 661 |
| 1/0 | 19 | 0.92 | 6 | 14 | 50 | 1.23 | 692 |
| 2/0 | 19 | 0.97 | 7 | 14 | 50 | 1.27 | 760 |
| 3/0 | 19 | 1.02 | 9 | 14 | 50 | 1.34 | 875 |
| 4/0 | 19 | 1.07 | 11 | 14 | 50 | 1.40 | 981 |
| 250 | 37 | 1.13 | 13 | 14 | 50 | 1.46 | 1080 |
| 350 | 37 | 1.23 | 18 | 14 | 50 | 1.56 | 1307 |
| 500 | 37 | 1.36 | 25 | 14 | 80 | 1.75 | 1692 |
| 500 | 37 | 1.36 | 16 | 12 | 80 | 1.78 | 1735 |
| 750 | 61 | 1.57 | 24 | 12 | 80 | 2.02 | 2340 |
| 750 | 61 | 1.57 | 15 | 10 | 80 | 2.06 | 2392 |
| 1000 | 61 | 1.72 | 31 | 12 | 80 | 2.17 | 2829 |
| 1000 | 61 | 1.72 | 20 | 10 | 80 | 2.21 | 2903 |
| 1000 | 61 | 1.72 | 16 | 9 | 80 | 2.24 | 2944 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/Kft |
| Copper 100% Insulation Level (260 mil) | |||||||
| 1 | 19 | 0.89 | 13 | 12 | 50 | 1.23 | 1030 |
| 1/0 | 19 | 0.93 | 16 | 12 | 50 | 1.27 | 1184 |
| 2/0 | 19 | 0.97 | 13 | 10 | 50 | 1.35 | 1426 |
| 3/0 | 19 | 1.02 | 16 | 10 | 50 | 1.42 | 1687 |
| 4/0 | 19 | 1.08 | 16 | 9 | 50 | 1.51 | 2016 |
| 250 | 37 | 1.13 | 25 | 10 | 50 | 1.54 | 2300 |
| 350 | 37 | 1.24 | 22 | 8 | 80 | 1.75 | 3116 |
| 500 | 37 | 1.37 | 31 | 8 | 80 | 1.88 | 4124 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 100% Insulation Level (260 mil) | |||||||
| 1 | 19 | 0.88 | 13 | 14 | 50 | 1.19 | 728 |
| 1/0 | 1 | 0.89 | 16 | 14 | 50 | 1.19 | 781 |
| 1/0 | 19 | 0.92 | 16 | 14 | 50 | 1.23 | 812 |
| 2/0 | 19 | 0.97 | 20 | 14 | 50 | 1.27 | 917 |
| 2/0 | 19 | 0.97 | 13 | 12 | 50 | 1.30 | 952 |
| 3/0 | 19 | 1.02 | 25 | 14 | 50 | 1.34 | 1068 |
| 3/0 | 19 | 1.02 | 16 | 12 | 50 | 1.38 | 1102 |
| 4/0 | 19 | 1.07 | 32 | 14 | 50 | 1.40 | 1234 |
| 4/0 | 19 | 1.07 | 20 | 12 | 50 | 1.43 | 1261 |
| 4/0 | 19 | 1.07 | 13 | 10 | 50 | 1.48 | 1313 |
| 250 | 37 | 1.13 | 25 | 12 | 50 | 1.49 | 1433 |
| 250 | 37 | 1.13 | 16 | 10 | 50 | 1.53 | 1482 |
| 350 | 37 | 1.23 | 32 | 12 | 50 | 1.59 | 1736 |
| 350 | 37 | 1.23 | 20 | 10 | 80 | 1.70 | 1843 |
| 350 | 37 | 1.23 | 16 | 9 | 80 | 1.72 | 1875 |
| 500 | 37 | 1.36 | 29 | 10 | 80 | 1.83 | 2361 |
| 750 | 61 | 1.57 | 28 | 8 | 80 | 2.12 | 3362 |
| 1000 | 61 | 1.72 | 37 | 8 | 80 | 2.27 | 4163 |
25 kV EPR Insulated
| 1⁄3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 133% Insulation Level (320 mil) | |||||||
| 1 | 19 | 1.01 | 7 | 14 | 50 | 1.31 | 961 |
| 1/0 | 19 | 1.05 | 9 | 14 | 50 | 1.38 | 1109 |
| 2/0 | 19 | 1.09 | 11 | 14 | 50 | 1.42 | 1254 |
| 3/0 | 19 | 1.14 | 14 | 14 | 50 | 1.47 | 1439 |
| 4/0 | 19 | 1.20 | 18 | 14 | 50 | 1.53 | 1668 |
| 250 | 37 | 1.26 | 13 | 12 | 50 | 1.62 | 1898 |
| 350 | 37 | 1.36 | 18 | 12 | 80 | 1.78 | 2458 |
| 500 | 37 | 1.49 | 17 | 10 | 80 | 1.95 | 3260 |
| 750 | 61 | 1.68 | 20 | 9 | 80 | 2.20 | 4540 |
| 1000 | 61 | 1.83 | 26 | 9 | 80 | 2.35 | 5683 |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 6 | 14 | 50 | 1.37 | 839 |
| 2/0 | 19 | 1.09 | 7 | 14 | 50 | 1.42 | 913 |
| 3/0 | 19 | 1.14 | 9 | 14 | 50 | 1.47 | 1010 |
| 4/0 | 19 | 1.20 | 11 | 14 | 50 | 1.52 | 1122 |
| 250 | 37 | 1.25 | 13 | 14 | 50 | 1.58 | 1226 |
| 350 | 37 | 1.35 | 18 | 14 | 80 | 1.74 | 1533 |
| 500 | 37 | 1.48 | 25 | 14 | 80 | 1.87 | 1867 |
| 500 | 37 | 1.48 | 16 | 12 | 80 | 1.91 | 1912 |
| 750 | 61 | 1.69 | 24 | 12 | 80 | 2.14 | 2540 |
| 750 | 61 | 1.69 | 15 | 10 | 80 | 2.18 | 2596 |
| 1000 | 61 | 1.84 | 31 | 12 | 80 | 2.29 | 3045 |
| 1000 | 61 | 1.84 | 20 | 10 | 80 | 2.33 | 3123 |
| 1000 | 61 | 1.84 | 16 | 9 | 80 | 2.36 | 3165 |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 133% Insulation Level (320 mil) | |||||||
| 1 | 19 | 1.01 | 13 | 12 | 50 | 1.35 | 1154 |
| 1/0 | 19 | 1.05 | 16 | 12 | 50 | 1.41 | 1337 |
| 2/0 | 19 | 1.09 | 13 | 10 | 50 | 1.50 | 1588 |
| 3/0 | 19 | 1.14 | 16 | 10 | 50 | 1.55 | 1830 |
| 4/0 | 19 | 1.20 | 16 | 9 | 80 | 1.69 | 2232 |
| 250 | 37 | 1.26 | 25 | 10 | 80 | 1.72 | 2522 |
| 350 | 37 | 1.36 | 22 | 8 | 80 | 1.88 | 3290 |
| 500 | 37 | 1.49 | 31 | 8 | 80 | 2.01 | 4311 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 16 | 14 | 50 | 1.37 | 959 |
| 2/0 | 19 | 1.09 | 20 | 14 | 50 | 1.42 | 1070 |
| 2/0 | 19 | 1.09 | 13 | 12 | 50 | 1.45 | 1108 |
| 3/0 | 19 | 1.14 | 25 | 14 | 50 | 1.47 | 1203 |
| 3/0 | 19 | 1.14 | 16 | 12 | 50 | 1.50 | 1239 |
| 4/0 | 19 | 1.20 | 32 | 14 | 50 | 1.52 | 1375 |
| 4/0 | 19 | 1.20 | 20 | 12 | 50 | 1.55 | 1405 |
| 4/0 | 19 | 1.20 | 13 | 10 | 50 | 1.60 | 1460 |
| 250 | 37 | 1.25 | 25 | 12 | 50 | 1.61 | 1583 |
| 250 | 37 | 1.25 | 16 | 10 | 80 | 1.72 | 1703 |
| 350 | 37 | 1.35 | 32 | 12 | 80 | 1.78 | 1966 |
| 350 | 37 | 1.35 | 20 | 10 | 80 | 1.82 | 2011 |
| 350 | 37 | 1.35 | 16 | 9 | 80 | 1.84 | 2045 |
| 500 | 37 | 1.48 | 29 | 10 | 80 | 1.95 | 2541 |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.
35 kV EPR Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft |
| in | |||||||
| Copper 100% Insulation Level (345 mil) | |||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 50 | 1.43 | 1166 |
| 2/0 | 19 | 1.15 | 11 | 14 | 50 | 1.47 | 1313 |
| 3/0 | 19 | 1.20 | 14 | 14 | 50 | 1.52 | 1499 |
| 4/0 | 19 | 1.25 | 18 | 14 | 50 | 1.58 | 1731 |
| 250 | 37 | 1.31 | 13 | 12 | 80 | 1.73 | 2032 |
| 350 | 37 | 1.41 | 18 | 12 | 80 | 1.83 | 2531 |
| 500 | 37 | 1.54 | 17 | 10 | 80 | 2.04 | 3388 |
| 750 | 61 | 1.73 | 20 | 9 | 80 | 2.25 | 4630 |
| 1000 | 61 | 1.88 | 26 | 9 | 80 | 2.40 | 5779 |
| Aluminum 100% Insulation Level (345 mil) | |||||||
| 1/0 | 1 | 1.06 | 6 | 14 | 50 | 1.38 | 858 |
| 1/0 | 19 | 1.10 | 6 | 14 | 50 | 1.42 | 895 |
| 2/0 | 19 | 1.14 | 7 | 14 | 50 | 1.47 | 971 |
| 3/0 | 19 | 1.19 | 9 | 14 | 50 | 1.52 | 1070 |
| 4/0 | 19 | 1.25 | 11 | 14 | 50 | 1.57 | 1184 |
| 250 | 37 | 1.30 | 13 | 14 | 80 | 1.69 | 1358 |
| 350 | 37 | 1.40 | 18 | 14 | 80 | 1.79 | 1604 |
| 500 | 37 | 1.53 | 25 | 14 | 80 | 1.95 | 1989 |
| 500 | 37 | 1.53 | 16 | 12 | 80 | 1.99 | 2036 |
| 750 | 61 | 1.74 | 24 | 12 | 80 | 2.19 | 2628 |
| 750 | 61 | 1.74 | 15 | 10 | 80 | 2.24 | 2684 |
| 1000 | 61 | 1.89 | 31 | 12 | 80 | 2.34 | 3139 |
| 1000 | 61 | 1.89 | 20 | 10 | 80 | 2.38 | 3217 |
| 1000 | 61 | 1.89 | 16 | 9 | 80 | 2.41 | 3260 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 100% Insulation Level (345 mil) | |||||||
| 1/0 | 19 | 1.10 | 16 | 12 | 50 | 1.46 | 1395 |
| 2/0 | 19 | 1.15 | 13 | 10 | 50 | 1.55 | 1649 |
| 3/0 | 19 | 1.20 | 16 | 10 | 50 | 1.60 | 1893 |
| 4/0 | 19 | 1.25 | 16 | 9 | 80 | 1.74 | 2301 |
| 250 | 37 | 1.31 | 25 | 10 | 80 | 1.77 | 2592 |
| 350 | 37 | 1.41 | 22 | 8 | 80 | 1.93 | 3366 |
| 500 | 37 | 1.54 | 31 | 8 | 80 | 2.09 | 4443 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 100% Insulation Level (345 mil) | |||||||
| 1/0 | 1 | 1.06 | 16 | 14 | 50 | 1.38 | 979 |
| 1/0 | 19 | 1.10 | 16 | 14 | 50 | 1.42 | 1015 |
| 2/0 | 19 | 1.14 | 20 | 14 | 50 | 1.47 | 1127 |
| 2/0 | 19 | 1.14 | 13 | 12 | 50 | 1.50 | 1167 |
| 3/0 | 19 | 1.19 | 25 | 14 | 50 | 1.52 | 1263 |
| 3/0 | 19 | 1.19 | 16 | 12 | 50 | 1.55 | 1300 |
| 4/0 | 19 | 1.25 | 32 | 14 | 50 | 1.57 | 1437 |
| 4/0 | 19 | 1.25 | 20 | 12 | 50 | 1.61 | 1468 |
| 4/0 | 19 | 1.25 | 13 | 10 | 80 | 1.71 | 1592 |
| 250 | 37 | 1.30 | 25 | 12 | 80 | 1.73 | 1716 |
| 250 | 37 | 1.30 | 16 | 10 | 80 | 1.77 | 1772 |
| 350 | 37 | 1.40 | 32 | 12 | 80 | 1.83 | 2038 |
| 350 | 37 | 1.40 | 20 | 10 | 80 | 1.87 | 2084 |
| 350 | 37 | 1.40 | 16 | 9 | 80 | 1.89 | 2119 |
| 500 | 37 | 1.53 | 29 | 10 | 80 | 2.03 | 2667 |
| 750 | 61 | 1.74 | 28 | 8 | 80 | 2.29 | 3661 |
| 1000 | 61 | 1.89 | 37 | 8 | 80 | 2.44 | 4483 |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.
35 kV EPR Insulated
| 1⁄3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 50 | 1.58 | 1349 |
| 2/0 | 19 | 1.30 | 11 | 14 | 50 | 1.63 | 1502 |
| 3/0 | 19 | 1.35 | 14 | 14 | 80 | 1.74 | 1762 |
| 4/0 | 19 | 1.40 | 18 | 14 | 80 | 1.79 | 2004 |
| 250 | 37 | 1.46 | 13 | 12 | 80 | 1.88 | 2251 |
| 350 | 37 | 1.56 | 18 | 12 | 80 | 2.02 | 2811 |
| 500 | 37 | 1.69 | 17 | 10 | 80 | 2.19 | 3645 |
| 750 | 61 | 1.88 | 20 | 9 | 80 | 2.40 | 4912 |
| 1000 | 61 | 2.03 | 26 | 9 | 80 | 2.55 | 6081 |
| Aluminum 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 50 | 1.57 | 1076 |
| 2/0 | 19 | 1.29 | 7 | 14 | 50 | 1.62 | 1157 |
| 3/0 | 19 | 1.34 | 9 | 14 | 80 | 1.73 | 1331 |
| 4/0 | 19 | 1.40 | 11 | 14 | 80 | 1.79 | 1454 |
| 250 | 37 | 1.45 | 13 | 14 | 80 | 1.84 | 1571 |
| 350 | 37 | 1.56 | 18 | 14 | 80 | 1.98 | 1876 |
| 500 | 37 | 1.68 | 25 | 14 | 80 | 2.11 | 2235 |
| 500 | 37 | 1.68 | 16 | 12 | 80 | 2.14 | 2285 |
| 750 | 61 | 1.89 | 24 | 12 | 80 | 2.34 | 2902 |
| 750 | 61 | 1.89 | 15 | 10 | 80 | 2.39 | 2963 |
| 1000 | 61 | 2.04 | 16 | 9 | 80 | 2.56 | 3560 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| in | AWG | mil | in | lb/kft | |||
| Copper 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 16 | 12 | 50 | 1.61 | 1581 |
| 2/0 | 19 | 1.30 | 13 | 10 | 80 | 1.76 | 1914 |
| 3/0 | 19 | 1.35 | 16 | 10 | 80 | 1.81 | 2166 |
| 4/0 | 19 | 1.40 | 16 | 9 | 80 | 1.89 | 2519 |
| 250 | 37 | 1.46 | 25 | 10 | 80 | 1.93 | 2815 |
| 350 | 37 | 1.56 | 22 | 8 | 80 | 2.11 | 3658 |
| 500 | 37 | 1.69 | 31 | 8 | 80 | 2.24 | 4704 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (420 mil) | |||||||
| 1/0 | 19 | 1.25 | 16 | 14 | 50 | 1.57 | 1196 |
| 2/0 | 19 | 1.29 | 20 | 14 | 80 | 1.68 | 1380 |
| 2/0 | 19 | 1.29 | 13 | 12 | 80 | 1.71 | 1424 |
| 3/0 | 19 | 1.34 | 25 | 14 | 80 | 1.73 | 1524 |
| 3/0 | 19 | 1.34 | 16 | 12 | 80 | 1.76 | 1566 |
| 4/0 | 19 | 1.40 | 32 | 14 | 80 | 1.79 | 1707 |
| 4/0 | 19 | 1.40 | 20 | 12 | 80 | 1.82 | 1743 |
| 4/0 | 19 | 1.40 | 13 | 10 | 80 | 1.86 | 1805 |
| 250 | 37 | 1.45 | 25 | 12 | 80 | 1.88 | 1933 |
| 250 | 37 | 1.45 | 16 | 10 | 80 | 1.92 | 1992 |
| 350 | 37 | 1.56 | 32 | 12 | 80 | 2.01 | 2314 |
| 350 | 37 | 1.56 | 20 | 10 | 80 | 2.05 | 2365 |
| 350 | 37 | 1.56 | 16 | 9 | 80 | 2.08 | 2403 |
| 500 | 37 | 1.68 | 29 | 10 | 80 | 2.18 | 2920 |
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities:Refer to beginning of section.
Primary UD TR-XLPE / PVC, Concentric Neutral 5 kV – 46 kV
Features
Low tension stripping compounds.
Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
On request, can be UL Listed as MV105 for use in accordance with Article 328 of the NEC.
On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, Rated 5 – 46 kV.
Specifications
Maximum operating voltage:
• 5 kV – 46 kV, 100 and 133% IL
Maximum conductor operation temperatures:
Wet and dry locations
For TR-XLPE
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
For XLPE
- Normal: 90 °C
- Emergency: 130 °C
- Short Circuit: 250 °C
Engineering Information
| Parameter | Specification |
|---|---|
| 1. Conductor | Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231. |
| On request | strand filled. |
| Sizes | 8 AWG – 1000 kcmil. |
| On request | larger sizes. |
| 2. Conductor Shield | Semi conducting cross-linked polyethylene (XLPE). |
| On request | super clean and super smooth materials. |
| 3. Insulation | Thermoset tree-retardant cross-linked polyethylene (TR-XLPE). |
| On request | cross-linked polyethylene (XLPE). |
| 4. Insulation Shield | Semi conducting cross-linked polyethylene (XLPE). |
| 5. Concentric Neutral | Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced. |
Full or 1/3 Neutral.
| Parameter | Specification |
|---|---|
| On request options | alternate neutral constructions, Water Swellable Powder (WSP), and ripcords. |
| 6. Binder Tape | A suitable polyester tape, as required. |
| 7. Jacket | Overlying (sleeve) black polyvinyl chloride (PVC). |
Configuration Options:
On request: Triplex or Paralleled configurations.
Technical Data
5 kV TR-XLPE Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation in | 1/3Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | mil | in | lb/kft | |||||||||
| Copper 100% Insulation Level (90 mil) | ||||||||||||
| 2 | 7 | 0.50 | 6 | 14 | 60 | 0.83 | 472 | 16 | 14 | 60 | 0.83 | 606 |
| 1 | 19 | 0.54 | 7 | 14 | 60 | 0.87 | 551 | 13 | 12 | 80 | 0.95 | 775 |
| 1/0 | 19 | 0.58 | 9 | 14 | 80 | 0.95 | 697 | 16 | 12 | 80 | 0.99 | 922 |
| 2/0 | 19 | 0.63 | 11 | 14 | 80 | 1.00 | 826 | 13 | 10 | 80 | 1.07 | 1131 |
| 3/0 | 19 | 0.68 | 14 | 14 | 80 | 1.05 | 993 | 16 | 10 | 80 | 1.12 | 1359 |
| 4/0 | 19 | 0.73 | 18 | 14 | 80 | 1.10 | 1204 | 16 | 9 | 80 | 1.20 | 1662 |
| 250 | 37 | 0.79 | 13 | 12 | 80 | 1.19 | 1385 | 25 | 10 | 80 | 1.23 | 1961 |
| 350 | 37 | 0.89 | 18 | 12 | 80 | 1.29 | 1841 | 22 | 8 | 80 | 1.39 | 2656 |
| 500 | 37 | 1.02 | 17 | 10 | 80 | 1.49 | 2578 | 31 | 8 | 80 | 1.54 | 3678 |
| 750 | 61 | 1.21 | 20 | 9 | 110 | 1.77 | 3815 | — | — | — | — | — |
| 1000 | 61 | 1.36 | 26 | 9 | 110 | 1.91 | 4912 | — | — | — | — | — |
| Aluminum 100% Insulation Level (90 mil) | ||||||||||||
| 2 | 7 | 0.50 | 6 | 14 | 60 | 0.83 | 330 | 10 | 14 | 60 | 0.83 | 383 |
| 1 | 19 | 0.54 | 6 | 14 | 80 | 0.91 | 395 | 13 | 14 | 80 | 0.91 | 489 |
| 1/0 | 19 | 0.58 | 6 | 14 | 80 | 0.95 | 431 | 16 | 14 | 80 | 0.95 | 564 |
| 2/0 | 19 | 0.62 | 7 | 14 | 80 | 1.00 | 488 | 13 | 12 | 80 | 1.03 | 676 |
| 3/0 | 19 | 0.67 | 9 | 14 | 80 | 1.05 | 567 | 16 | 12 | 80 | 1.08 | 792 |
| 4/0 | 19 | 0.73 | 11 | 14 | 80 | 1.10 | 657 | 13 | 10 | 80 | 1.18 | 962 |
| 250 | 37 | 0.79 | 13 | 14 | 80 | 1.16 | 741 | 16 | 10 | 80 | 1.24 | 1121 |
| 350 | 37 | 0.89 | 18 | 14 | 80 | 1.26 | 942 | 16 | 9 | 80 | 1.36 | 1400 |
| 500 | 37 | 1.02 | 16 | 12 | 80 | 1.45 | 1261 | 29 | 10 | 80 | 1.49 | 1908 |
| 750 | 61 | 1.22 | 15 | 10 | 110 | 1.76 | 1872 | — | — | — | — | — |
| 1000 | 61 | 1.37 | 16 | 9 | 110 | 1.93 | 2360 | — | — | — | — | — |
8 kV TR-XLPE Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
| Copper 100% Insulation Level (115 mil) | ||||||||||||
| 2 | 7 | 0.55 | 6 | 14 | 60 | 0.88 | 498 | 16 | 14 | 60 | 0.88 | 632 |
| 1 | 19 | 0.59 | 7 | 14 | 80 | 0.96 | 617 | 13 | 12 | 80 | 1.00 | 805 |
| 1/0 | 19 | 0.63 | 9 | 14 | 80 | 1.00 | 728 | 16 | 12 | 80 | 1.04 | 953 |
| 2/0 | 19 | 0.68 | 11 | 14 | 80 | 1.05 | 858 | 13 | 10 | 80 | 1.12 | 1163 |
| 3/0 | 19 | 0.73 | 14 | 14 | 80 | 1.10 | 1027 | 16 | 10 | 80 | 1.17 | 1393 |
| 4/0 | 19 | 0.78 | 18 | 14 | 80 | 1.15 | 1240 | 16 | 9 | 80 | 1.25 | 1697 |
| 250 | 37 | 0.84 | 13 | 12 | 80 | 1.24 | 1423 | — | — | — | — | — |
| 350 | 37 | 0.94 | 18 | 12 | 80 | 1.35 | 1881 | — | — | — | — | — |
| 500 | 37 | 1.07 | 17 | 10 | 80 | 1.54 | 2624 | — | — | — | — | — |
| 750 | 61 | 1.26 | 20 | 9 | 110 | 1.82 | 3870 | — | — | — | — | — |
| 1000 | 61 | 1.41 | 26 | 9 | 110 | 1.97 | 4972 | — | — | — | — | — |
| Aluminum 100% Insulation Level (1 15 mil) | ||||||||||||
| 2 | 7 | 0.55 | 6 | 14 | 80 | 0.92 | 393 | 10 | 14 | 80 | 0.92 | 447 |
| 1 | 19 | 0.59 | 6 | 14 | 80 | 0.96 | 424 | 13 | 14 | 80 | 0.96 | 518 |
| 1/0 | 19 | 0.63 | 6 | 14 | 80 | 1.00 | 461 | 16 | 14 | 80 | 1.00 | 595 |
| 2/0 | 19 | 0.68 | 7 | 14 | 80 | 1.05 | 520 | 13 | 12 | 80 | 1.08 | 708 |
| 3/0 | 19 | 0.73 | 9 | 14 | 80 | 1.10 | 600 | 16 | 12 | 80 | 1.13 | 825 |
| 4/0 | 19 | 0.78 | 11 | 14 | 80 | 1.15 | 693 | 13 | 10 | 80 | 1.23 | 998 |
| 250 | 37 | 0.84 | 13 | 14 | 80 | 1.21 | 778 | 16 | 10 | 80 | 1.29 | 1158 |
| 350 | 37 | 0.94 | 18 | 14 | 80 | 1.31 | 983 | 16 | 9 | 80 | 1.41 | 1440 |
| 500 | 37 | 1.07 | 16 | 12 | 80 | 1.50 | 1307 | 29 | 10 | 80 | 1.54 | 1954 |
| 750 | 61 | 1.27 | 15 | 10 | 110 | 1.81 | 1927 | — | — | — | — | — |
| 1000 | 61 | 1.42 | 16 | 9 | 110 | 1.98 | 2419 | — | — | — | — | — |
15 kV TR-XLPE Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | |||
| Copper 100% Insulation Level (175 mil) | ||||||||||||
| 2 | 1 | 0.68 | 6 | 14 | 80 | 1.05 | 610 | |||||
| 2 | 7 | 0.68 | 6 | 14 | 80 | 1.05 | 610 | 16 | 14 | 80 | 1.05 | 743 |
| 1 | 19 | 0.71 | 7 | 14 | 80 | 1.09 | 694 | 13 | 12 | 80 | 1.12 | 883 |
| 1/0 | 19 | 0.75 | 9 | 14 | 80 | 1.13 | 808 | 16 | 12 | 80 | 1.16 | 1034 |
| 2/0 | 19 | 0.80 | 11 | 14 | 80 | 1.17 | 942 | 13 | 10 | 80 | 1.25 | 1247 |
| 3/0 | 19 | 0.85 | 14 | 14 | 80 | 1.22 | 1115 | 16 | 10 | 80 | 1.30 | 1481 |
| 4/0 | 19 | 0.90 | 18 | 14 | 80 | 1.28 | 1332 | 16 | 9 | 80 | 1.38 | 1790 |
| 250 | 37 | 0.96 | 13 | 12 | 80 | 1.37 | 1519 | 25 | 10 | 80 | 1.41 | 2095 |
| 350 | 37 | 1.06 | 18 | 12 | 80 | 1.49 | 2011 | 22 | 8 | 80 | 1.59 | 2826 |
| 500 | 37 | 1.19 | 17 | 10 | 80 | 1.66 | 2741 | 31 | 8 | 110 | 1.78 | 3947 |
| 750 | 61 | 1.38 | 20 | 9 | 110 | 1.94 | 4008 | — | — | — | — | — |
| 1000 | 61 | 1.53 | 26 | 9 | 110 | 2.12 | 5170 | — | — | — | — | — |
| Aluminum 100% Insulation Level (175 mil) | ||||||||||||
| 2 | 7 | 0.67 | 6 | 14 | 80 | 1.05 | 467 | 10 | 14 | 80 | 1.05 | 520 |
| 1 | 19 | 0.71 | 6 | 14 | 80 | 1.08 | 501 | 13 | 14 | 80 | 1.08 | 595 |
| 1/0 | 19 | 0.75 | 6 | 14 | 80 | 1.12 | 541 | 16 | 14 | 80 | 1.12 | 675 |
| 2/0 | 19 | 0.80 | 7 | 14 | 80 | 1.17 | 603 | 13 | 12 | 80 | 1.20 | 791 |
| 3/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 687 | 16 | 12 | 80 | 1.25 | 912 |
| 4/0 | 19 | 0.90 | 11 | 14 | 80 | 1.27 | 784 | 13 | 10 | 80 | 1.35 | 1089 |
| 250 | 37 | 0.96 | 13 | 14 | 80 | 1.33 | 874 | 16 | 10 | 80 | 1.41 | 1253 |
| 350 | 37 | 1.06 | 18 | 14 | 80 | 1.46 | 1110 | 16 | 9 | 80 | 1.56 | 1568 |
| 500 | 37 | 1.19 | 16 | 12 | 80 | 1.62 | 1422 | 29 | 10 | 80 | 1.66 | 2069 |
| 750 | 61 | 1.40 | 24 | 12 | 110 | 1.89 | 2059 | — | — | — | — | — |
| 750 | 61 | 1.40 | 15 | 10 | 110 | 1.93 | 2065 | — | — | — | — | — |
| 1000 | 61 | 1.54 | 16 | 9 | 110 | 2.13 | 2616 | — | — | — | — | — |
15 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | ||||
| Copper 133% Insulation Level (220 mil) | ||||||||||||
| 2 | 7 | 0.77 | 6 | 14 | 80 | 1.14 | 672 | 16 | 14 | 80 | 1.14 | 805 |
| 1 | 19 | 0.81 | 7 | 14 | 80 | 1.18 | 759 | 13 | 12 | 80 | 1.21 | 947 |
| 1/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 875 | 16 | 12 | 80 | 1.25 | 1100 |
| 2/0 | 19 | 0.89 | 11 | 14 | 80 | 1.26 | 1012 | 13 | 10 | 80 | 1.34 | 1316 |
| 3/0 | 19 | 0.94 | 14 | 14 | 80 | 1.31 | 1187 | 16 | 10 | 80 | 1.39 | 1553 |
| 4/0 | 19 | 1.00 | 18 | 14 | 80 | 1.37 | 1407 | 16 | 9 | 80 | 1.47 | 1865 |
| 250 | 37 | 1.05 | 13 | 12 | 80 | 1.48 | 1622 | 25 | 10 | 80 | 1.52 | 2198 |
| 350 | 37 | 1.16 | 18 | 12 | 80 | 1.58 | 2097 | 22 | 8 | 80 | 1.68 | 2912 |
| 500 | 37 | 1.28 | 17 | 10 | 110 | 1.82 | 2943 | 31 | 8 | 110 | 1.87 | 4046 |
| 750 | 61 | 1.47 | 20 | 9 | 110 | 2.03 | 4118 | — | — | — | — | — |
| 1000 | 61 | 1.62 | 26 | 9 | 110 | 2.21 | 5291 | — | — | — | — | — |
| Aluminum 133% Insulation Level (220 mil) | ||||||||||||
| 2 | 7 | 0.76 | 6 | 14 | 80 | 1.14 | 528 | 10 | 14 | 80 | 1.14 | 582 |
| 1 | 19 | 0.80 | 6 | 14 | 80 | 1.18 | 565 | 13 | 14 | 80 | 1.18 | 658 |
| 1/0 | 19 | 0.84 | 6 | 14 | 80 | 1.22 | 607 | 16 | 14 | 80 | 1.22 | 741 |
| 2/0 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 671 | 13 | 12 | 80 | 1.29 | 859 |
| 3/0 | 19 | 0.94 | 9 | 14 | 80 | 1.31 | 758 | 16 | 12 | 80 | 1.34 | 983 |
| 4/0 | 19 | 0.99 | 11 | 14 | 80 | 1.37 | 858 | 13 | 10 | 80 | 1.44 | 1163 |
| 250 | 37 | 1.05 | 13 | 14 | 80 | 1.44 | 975 | 16 | 10 | 80 | 1.52 | 1355 |
| 350 | 37 | 1.15 | 18 | 14 | 80 | 1.55 | 1195 | 16 | 9 | 80 | 1.65 | 1653 |
| 500 | 37 | 1.28 | 16 | 12 | 110 | 1.77 | 1622 | 29 | 10 | 110 | 1.81 | 2272 |
| 750 | 61 | 1.49 | 15 | 10 | 110 | 2.02 | 2175 | — | — | — | — | — |
| 1000 | 61 | 1.64 | 16 | 9 | 110 | 2.23 | 2737 | — | — | — | — | — |
25 kV TR-XLPE Insulated
| 1/3 Neutral | Full Neutral | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight |
| AWG | mil | in | lb/ft | AWG | mil | in | lb/ft | ||||||||
| Copper 100% Insulation Level (260 mil) | |||||||||||||||
| 1 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 820 | 1 | 19 | 0.89 | 13 | 12 | 80 | 1.29 | 1009 |
| 1/0 | 19 | 0.93 | 9 | 14 | 80 | 1.30 | 939 | 1/0 | 19 | 0.93 | 16 | 12 | 80 | 1.33 | 1164 |
| 2/0 | 19 | 0.97 | 11 | 14 | 80 | 1.34 | 1077 | 2/0 | 19 | 0.97 | 32 | 14 | 80 | 1.34 | 1358 |
| 3/0 | 19 | 1.02 | 14 | 14 | 80 | 1.42 | 1280 | 2/0 | 19 | 0.97 | 20 | 12 | 80 | 1.38 | 1361 |
| 4/0 | 19 | 1.08 | 18 | 14 | 80 | 1.47 | 1504 | 2/0 | 19 | 0.97 | 13 | 10 | 80 | 1.42 | 1382 |
| 250 | 37 | 1.13 | 13 | 12 | 80 | 1.56 | 1698 | 3/0 | 19 | 1.02 | 16 | 10 | 80 | 1.49 | 1646 |
| 350 | 37 | 1.24 | 18 | 12 | 80 | 1.66 | 2178 | 4/0 | 19 | 1.08 | 16 | 9 | 80 | 1.57 | 1961 |
| 500 | 37 | 1.37 | 17 | 10 | 110 | 1.90 | 3035 | 250 | 37 | 1.13 | 25 | 10 | 80 | 1.60 | 2274 |
| 750 | 61 | 1.56 | 20 | 9 | 110 | 2.14 | 4269 | 350 | 37 | 1.24 | 22 | 8 | 110 | 1.82 | 3102 |
| 1000 | 61 | 1.70 | 26 | 9 | 110 | 2.29 | 5403 | 500 | 37 | 1.37 | 31 | 8 | 110 | 1.95 | 4139 |
| Aluminum 100% Insulation Level (260 mil) | |||||||||||||||
| 1 | 19 | 0.88 | 6 | 14 | 80 | 1.26 | 626 | 1 | 19 | 0.88 | 13 | 14 | 80 | 1.26 | 719 |
| 1/0 | 19 | 0.92 | 6 | 14 | 80 | 1.30 | 670 | 1/0 | 19 | 0.92 | 16 | 14 | 80 | 1.30 | 804 |
| 2/0 | 19 | 0.97 | 7 | 14 | 80 | 1.34 | 736 | 2/0 | 19 | 0.97 | 13 | 12 | 80 | 1.37 | 925 |
| 3/0 | 19 | 1.02 | 9 | 14 | 80 | 1.41 | 849 | 3/0 | 19 | 1.02 | 16 | 12 | 80 | 1.45 | 1075 |
| 4/0 | 19 | 1.07 | 11 | 14 | 80 | 1.47 | 953 | 4/0 | 19 | 1.07 | 13 | 10 | 80 | 1.54 | 1258 |
| 250 | 37 | 1.13 | 13 | 14 | 80 | 1.53 | 1050 | 250 | 37 | 1.13 | 16 | 10 | 80 | 1.60 | 1430 |
| 350 | 37 | 1.23 | 18 | 14 | 80 | 1.63 | 1275 | 350 | 37 | 1.23 | 16 | 9 | 110 | 1.79 | 1842 |
| 500 | 37 | 1.36 | 16 | 12 | 110 | 1.85 | 1714 | 500 | 37 | 1.36 | 29 | 10 | 110 | 1.90 | 2363 |
| 750 | 61 | 1.57 | 15 | 10 | 110 | 2.13 | 2325 | — | — | — | — | — | — | — | — |
| 1000 | 61 | 1.72 | 16 | 9 | 110 | 2.31 | 2848 | — | — | — | — | — | — | — | — |
25 kV TR-XLPE Insulated
| 1/3 Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | Number of Wires | Size AWG | Jacket Thickness mm | Approximate Outside Diameter mm | Approximate Net Weight lb/kft |
| Copper 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 9 | 14 | 80 | 1.44 | 1067 |
| 2/0 | 19 | 1.09 | 11 | 14 | 80 | 1.49 | 1210 |
| 3/0 | 19 | 1.14 | 14 | 14 | 80 | 1.54 | 1392 |
| 4/0 | 19 | 1.20 | 18 | 14 | 80 | 1.59 | 1621 |
| 250 | 37 | 1.26 | 13 | 12 | 80 | 1.68 | 1820 |
| 350 | 37 | 1.36 | 18 | 12 | 110 | 1.85 | 2418 |
| 500 | 37 | 1.49 | 17 | 10 | 110 | 2.02 | 3182 |
| 750 | 61 | 1.68 | 20 | 9 | 110 | 2.27 | 4433 |
| 1000 | 61 | 1.83 | 26 | 9 | 110 | 2.42 | 5578 |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 1 | 1.01 | 6 | 14 | 50 | 1.31 | 691 |
| 1/0 | 19 | 1.05 | 6 | 14 | 50 | 1.37 | 744 |
| 2/0 | 19 | 1.09 | 7 | 14 | 50 | 1.42 | 812 |
| 3/0 | 19 | 1.14 | 9 | 14 | 50 | 1.47 | 903 |
| 4/0 | 19 | 1.20 | 11 | 14 | 50 | 1.52 | 1007 |
| 250 | 37 | 1.25 | 13 | 14 | 50 | 1.58 | 1105 |
| 350 | 37 | 1.35 | 18 | 14 | 80 | 1.74 | 1398 |
| 500 | 37 | 1.48 | 25 | 14 | 80 | 1.87 | 1715 |
| 500 | 37 | 1.48 | 16 | 12 | 80 | 1.91 | 1760 |
| 750 | 61 | 1.69 | 24 | 12 | 80 | 2.14 | 2361 |
| 750 | 61 | 1.69 | 15 | 10 | 80 | 2.18 | 2417 |
| 1000 | 61 | 1.84 | 31 | 12 | 80 | 2.29 | 2846 |
| 1000 | 61 | 1.84 | 20 | 10 | 80 | 2.33 | 2924 |
| 1000 | 61 | 1.84 | 16 | 9 | 80 | 2.36 | 2966 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Full Neutral | |||||||
|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation In | Number of Wires | Size AWG | Jacket Thickness mm | Approximate Outside Diameter mm | Approximate Net Weight lb/kft |
| Copper 133% Insulation Level (320 mil) | |||||||
| 1/0 | 19 | 1.05 | 16 | 12 | 80 | 1.48 | 1292 |
| 2/0 | 19 | 1.09 | 13 | 10 | 80 | 1.56 | 1515 |
| 3/0 | 19 | 1.14 | 16 | 10 | 80 | 1.61 | 1758 |
| 4/0 | 19 | 1.20 | 16 | 9 | 110 | 1.76 | 2184 |
| 250 | 37 | 1.26 | 25 | 10 | 110 | 1.79 | 2502 |
| 350 | 37 | 1.36 | 22 | 8 | 110 | 1.94 | 3239 |
| 500 | 37 | 1.49 | 31 | 8 | 110 | 2.07 | 4285 |
| — | — | — | — | — | — | — | — |
| — | — | — | — | — | — | — | — |
| Aluminum 133% Insulation Level (320 mil) | |||||||
| 1/0 | 1 | 1.01 | 16 | 14 | 50 | 1.31 | 811 |
| 1/0 | 19 | 1.05 | 16 | 14 | 50 | 1.37 | 865 |
| 2/0 | 19 | 1.09 | 20 | 14 | 50 | 1.42 | 969 |
| 2/0 | 19 | 1.09 | 13 | 12 | 50 | 1.45 | 1007 |
| 3/0 | 19 | 1.14 | 25 | 14 | 50 | 1.47 | 1096 |
| 3/0 | 19 | 1.14 | 16 | 12 | 50 | 1.50 | 1132 |
| 4/0 | 19 | 1.20 | 32 | 14 | 50 | 1.52 | 1260 |
| 4/0 | 19 | 1.20 | 20 | 12 | 50 | 1.55 | 1290 |
| 4/0 | 19 | 1.20 | 13 | 10 | 50 | 1.60 | 1346 |
| 250 | 37 | 1.25 | 25 | 12 | 50 | 1.61 | 1461 |
| 250 | 37 | 1.25 | 16 | 10 | 80 | 1.72 | 1581 |
| 350 | 37 | 1.35 | 32 | 12 | 80 | 1.78 | 1831 |
| 350 | 37 | 1.35 | 20 | 10 | 80 | 1.82 | 1876 |
| 350 | 37 | 1.35 | 16 | 9 | 80 | 1.84 | 1910 |
| 500 | 37 | 1.48 | 29 | 10 | 80 | 1.95 | 2389 |
| 750 | 61 | 1.69 | 28 | 8 | 80 | 2.24 | 3391 |
| 1000 | 61 | 1.84 | 37 | 8 | 80 | 2.39 | 4188 |
35 kV TR-XLPE Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation In | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | mil | In | lb/kft | AWG | mil | In | lb/kft | |||||
| Copper 100% Insulation Level (345 mil) | ||||||||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 80 | 1.50 | 1114 | 16 | 12 | 80 | 1.53 | 1397 |
| 2/0 | 19 | 1.15 | 11 | 14 | 80 | 1.54 | 1258 | 13 | 10 | 80 | 1.62 | 1652 |
| 3/0 | 19 | 1.20 | 14 | 14 | 80 | 1.59 | 1442 | 16 | 10 | 80 | 1.67 | 1896 |
| 4/0 | 19 | 1.25 | 18 | 14 | 80 | 1.65 | 1673 | 16 | 9 | 110 | 1.81 | 2305 |
| 250 | 37 | 1.31 | 13 | 12 | 110 | 1.80 | 1981 | 25 | 10 | 110 | 1.84 | 2596 |
| 350 | 37 | 1.41 | 18 | 12 | 110 | 1.90 | 2477 | 22 | 8 | 110 | 2.00 | 3371 |
| 500 | 37 | 1.54 | 17 | 10 | 110 | 2.10 | 3294 | 31 | 8 | 110 | 2.16 | 4448 |
| 750 | 61 | 1.73 | 20 | 9 | 110 | 2.32 | 4504 | — | — | — | — | — |
| 1000 | 61 | 1.88 | 26 | 9 | 110 | 2.47 | 5654 | — | — | — | — | — |
| Aluminum 100% Insulation Level (345 mil) | ||||||||||||
| 1/0 | 19 | 1.10 | 6 | 14 | 80 | 1.49 | 842 | 16 | 14 | 80 | 1.49 | 976 |
| 2/0 | 19 | 1.14 | 7 | 14 | 80 | 1.53 | 914 | 13 | 12 | 80 | 1.57 | 1102 |
| 3/0 | 19 | 1.19 | 9 | 14 | 80 | 1.58 | 1010 | 16 | 12 | 80 | 1.62 | 1235 |
| 4/0 | 19 | 1.25 | 11 | 14 | 80 | 1.64 | 1120 | 13 | 10 | 110 | 1.78 | 1533 |
| 250 | 37 | 1.30 | 13 | 14 | 110 | 1.76 | 1330 | 16 | 10 | 110 | 1.84 | 1714 |
| 350 | 37 | 1.40 | 18 | 14 | 110 | 1.86 | 1572 | 16 | 9 | 110 | 1.96 | 2036 |
| 500 | 37 | 1.53 | 16 | 12 | 110 | 2.06 | 1969 | 29 | 10 | 110 | 2.10 | 2619 |
| 750 | 61 | 1.74 | 15 | 10 | 110 | 2.30 | 2560 | — | — | — | — | — |
| 1000 | 61 | 1.89 | 16 | 9 | 110 | 2.48 | 3099 | — | — | — | — | — |
35 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | |||||
| Copper 133% Insulation Level (420 mil) | ||||||||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 80 | 1.65 | 1264 | 16 | 12 | 80 | 1.68 | 1489 |
| 2/0 | 19 | 1.30 | 11 | 14 | 110 | 1.76 | 1517 | 13 | 10 | 110 | 1.83 | 1827 |
| 3/0 | 19 | 1.35 | 14 | 14 | 110 | 1.81 | 1709 | 16 | 10 | 110 | 1.88 | 2080 |
| 4/0 | 19 | 1.40 | 18 | 14 | 110 | 1.86 | 1948 | 16 | 9 | 110 | 1.96 | 2412 |
| 250 | 37 | 1.46 | 13 | 12 | 110 | 1.95 | 2160 | 25 | 10 | 110 | 1.99 | 2738 |
| 350 | 37 | 1.56 | 18 | 12 | 110 | 2.08 | 2716 | 22 | 8 | 110 | 2.18 | 3537 |
| 500 | 37 | 1.69 | 17 | 10 | 110 | 2.26 | 3499 | 31 | 8 | 110 | 2.31 | 4603 |
| 750 | 61 | 1.88 | 20 | 9 | 110 | 2.47 | 4728 | — | — | — | — | — |
| 1000 | 61 | 2.03 | 26 | 9 | 110 | 2.62 | 5892 | — | — | — | — | — |
| Aluminum 133% Insulation Level (420 mil) | ||||||||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 80 | 1.64 | 990 | 16 | 14 | 80 | 1.64 | 1124 |
| 2/0 | 19 | 1.29 | 7 | 14 | 110 | 1.75 | 1173 | 13 | 12 | 110 | 1.78 | 1363 |
| 3/0 | 19 | 1.34 | 9 | 14 | 110 | 1.80 | 1276 | 16 | 12 | 110 | 1.83 | 1504 |
| 4/0 | 19 | 1.40 | 11 | 14 | 110 | 1.86 | 1395 | 13 | 10 | 110 | 1.93 | 1705 |
| 250 | 37 | 1.45 | 13 | 14 | 110 | 1.91 | 1507 | 16 | 10 | 110 | 1.99 | 1891 |
| 350 | 37 | 1.56 | 18 | 14 | 110 | 2.04 | 1807 | 16 | 9 | 110 | 2.15 | 2271 |
| 500 | 37 | 1.68 | 16 | 12 | 110 | 2.21 | 2172 | 29 | 10 | 110 | 2.25 | 2821 |
| 750 | 61 | 1.89 | 15 | 10 | 110 | 2.46 | 2782 | — | — | — | — | — |
| 1000 | 61 | 2.04 | 16 | 9 | 110 | 2.63 | 3335 | — | — | — | — | — |
Primary UD EPR / PVC, Concentric Neutral 15 kV – 46 kV
Features
Low tension stripping compounds.
Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
Strand Filled compound meets compatibility test requirements in accordance with ICEA-T-32-610.
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
On request, can be UL Listed as MV105 for use in accordance with Article 328 of the NEC.
On request, two abrasion resistant ripcords placed longitudinally 180° apart for easy jacket removal.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV
Specifications
Maximum operating voltage:
• 5 kV – 46 kV, 100 and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
| Parameter | Specification |
|---|---|
| 1. Conductor | Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231. |
| On request | strand filled. |
| Sizes | 8 AWG – 1000 kcmil. |
On request, larger sizes.
| Parameter | Specification |
|---|---|
| 2. Conductor Shield | Semi conducting cross-linked polyethylene (XLPE). |
| On request | super clean and super smooth materials. |
| 3. Insulation | Thermoset ethylene propylene rubber (EPR). |
| On request | amorphous EPR. |
| 4. Insulation Shield | Semi conducting cross-linked polyethylene (XLPE). |
| 5. Concentric Neutral | Soft annealed solid copper wires per ASTM B3, helically applied and uniformly spaced. |
Full or 1/3 Neutral.
| Parameter | Specification |
|---|---|
| On request options | alternate neutral constructions, Water Swellable Powder (WSP), and ripcords. |
| 6. Binder Tape | A suitable polyester tape, as required. |
| 7. Jacket | Extruded Overlying (Sleeve) Black polyvinyl chloride (PVC) sunlight resistant. |
Configuration Options:
On request: Triplex or Paralleled configurations.
Technical Data
15 kV EPR Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/KR | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/KR | |||
| Copper 100% Insulation Level (175 mil) | ||||||||||||
| 2 | 7 | 0.68 | 6 | 14 | 80 | 1.05 | 646 | 16 | 14 | 80 | 1.05 | 779 |
| 1 | 19 | 0.71 | 7 | 14 | 80 | 1.09 | 733 | 13 | 12 | 80 | 1.12 | 921 |
| 1/0 | 19 | 0.75 | 9 | 14 | 80 | 1.13 | 850 | 16 | 12 | 80 | 1.16 | 1075 |
| 2/0 | 19 | 0.80 | 11 | 14 | 80 | 1.17 | 987 | 13 | 10 | 80 | 1.25 | 1292 |
| 3/0 | 19 | 0.85 | 14 | 14 | 80 | 1.22 | 1163 | 16 | 10 | 80 | 1.30 | 1530 |
| 4/0 | 19 | 0.90 | 18 | 14 | 80 | 1.28 | 1385 | 16 | 9 | 80 | 1.38 | 1842 |
| 250 | 37 | 0.96 | 13 | 12 | 80 | 1.37 | 1576 | 25 | 10 | 80 | 1.41 | 2151 |
| 350 | 37 | 1.06 | 18 | 12 | 80 | 1.49 | 2075 | 22 | 8 | 80 | 1.59 | 2890 |
| 500 | 37 | 1.19 | 17 | 10 | 80 | 1.66 | 2814 | 31 | 8 | 110 | 1.78 | 4020 |
| 750 | 61 | 1.38 | 20 | 9 | 110 | 1.94 | 4095 | — | — | — | — | — |
| 1000 | 61 | 1.53 | 26 | 9 | 110 | 2.12 | 5268 | — | — | — | — | — |
| Aluminum 100% Insulation Level (175 mil) | ||||||||||||
| 2 | 7 | 0.67 | 6 | 14 | 80 | 1.05 | 503 | 10 | 14 | 80 | 1.05 | 556 |
| 1 | 19 | 0.71 | 6 | 14 | 80 | 1.08 | 540 | 13 | 14 | 80 | 1.08 | 633 |
| 1/0 | 19 | 0.75 | 6 | 14 | 80 | 1.12 | 582 | 16 | 14 | 80 | 1.12 | 716 |
| 2/0 | 19 | 0.80 | 7 | 14 | 80 | 1.17 | 647 | 13 | 12 | 80 | 1.20 | 835 |
| 3/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 735 | 16 | 12 | 80 | 1.25 | 960 |
| 4/0 | 19 | 0.90 | 11 | 14 | 80 | 1.27 | 836 | 13 | 10 | 80 | 1.35 | 1141 |
| 250 | 37 | 0.96 | 13 | 14 | 80 | 1.33 | 930 | 16 | 10 | 80 | 1.41 | 1309 |
| 350 | 37 | 1.06 | 18 | 14 | 80 | 1.46 | 1174 | 16 | 9 | 80 | 1.56 | 1631 |
| 500 | 37 | 1.19 | 16 | 12 | 80 | 1.62 | 1495 | 29 | 10 | 80 | 1.66 | 2142 |
| 750 | 61 | 1.40 | 15 | 10 | 110 | 1.93 | 2153 | — | — | — | — | — |
| 1000 | 61 | 1.54 | 16 | 9 | 110 | 2.13 | 2715 | — | — | — | — | — |
15 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kft | |||
| Copper 133% Insulation Level (220 mil) | ||||||||||||
| 2 | 7 | 0.77 | 6 | 14 | 80 | 1.14 | 721 | 16 | 14 | 80 | 1.14 | 855 |
| 1 | 19 | 0.81 | 7 | 14 | 80 | 1.18 | 812 | 13 | 12 | 80 | 1.21 | 1000 |
| 1/0 | 19 | 0.85 | 9 | 14 | 80 | 1.22 | 932 | 16 | 12 | 80 | 1.25 | 1157 |
| 2/0 | 19 | 0.89 | 11 | 14 | 80 | 1.26 | 1072 | 13 | 10 | 80 | 1.34 | 1377 |
| 3/0 | 19 | 0.94 | 14 | 14 | 80 | 1.31 | 1252 | 16 | 10 | 80 | 1.39 | 1618 |
| 4/0 | 19 | 1.00 | 18 | 14 | 80 | 1.37 | 1478 | 16 | 9 | 80 | 1.47 | 1935 |
| 250 | 37 | 1.05 | 13 | 12 | 80 | 1.48 | 1698 | 25 | 10 | 80 | 1.52 | 2273 |
| 350 | 37 | 1.16 | 18 | 12 | 80 | 1.58 | 2182 | 22 | 8 | 80 | 1.68 | 2997 |
| 500 | 37 | 1.28 | 17 | 10 | 110 | 1.82 | 3039 | 31 | 8 | 110 | 1.87 | 4143 |
| 750 | 61 | 1.47 | 20 | 9 | 110 | 2.03 | 4232 | — | — | — | — | — |
| 1000 | 61 | 1.62 | 26 | 9 | 110 | 2.21 | 5418 | — | — | — | — | — |
| Aluminum 133% Insulation Level (220 mil) | ||||||||||||
| 2 | 7 | 0.76 | 6 | 14 | 80 | 1.14 | 577 | 10 | 14 | 80 | 1.14 | 631 |
| 1 | 19 | 0.80 | 6 | 14 | 80 | 1.18 | 617 | 13 | 14 | 80 | 1.18 | 711 |
| 1/0 | 19 | 0.84 | 6 | 14 | 80 | 1.22 | 663 | 16 | 14 | 80 | 1.22 | 797 |
| 2/0 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 731 | 13 | 12 | 80 | 1.29 | 919 |
| 3/0 | 19 | 0.94 | 9 | 14 | 80 | 1.31 | 823 | 16 | 12 | 80 | 1.34 | 1048 |
| 4/0 | 19 | 0.99 | 11 | 14 | 80 | 1.37 | 928 | 13 | 10 | 80 | 1.44 | 1233 |
| 250 | 37 | 1.05 | 13 | 14 | 80 | 1.44 | 1050 | 16 | 10 | 80 | 1.52 | 1430 |
| 350 | 37 | 1.15 | 18 | 14 | 80 | 1.55 | 1279 | 16 | 9 | 80 | 1.65 | 1737 |
| 500 | 37 | 1.28 | 16 | 12 | 110 | 1.77 | 1718 | 29 | 10 | 110 | 1.81 | 2367 |
| 750 | 61 | 1.49 | 15 | 10 | 110 | 2.02 | 2289 | — | — | — | — | — |
| 1000 | 61 | 1.64 | 16 | 9 | 110 | 2.23 | 2864 | — | — | — | — | — |
25 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in |
1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | mil | in | lb/kft | AWG | mil | in | lb/kft | |||||
| Copper 100% Insulation Level (260 mil) | ||||||||||||
| 1 | 19 | 0.89 | 7 | 14 | 80 | 1.26 | 887 | 13 | 12 | 80 | 1.29 | 1076 |
| 1/0 | 19 | 0.93 | 9 | 14 | 80 | 1.30 | 1010 | 16 | 12 | 80 | 1.33 | 1235 |
| 2/0 | 19 | 0.97 | 11 | 14 | 80 | 1.34 | 1154 | 13 | 10 | 80 | 1.42 | 1458 |
| 3/0 | 19 | 1.02 | 14 | 14 | 80 | 1.42 | 1361 | 16 | 10 | 80 | 1.49 | 1727 |
| 4/0 | 19 | 1.08 | 18 | 14 | 80 | 1.47 | 1591 | 16 | 9 | 80 | 1.57 | 2049 |
| 250 | 37 | 1.13 | 13 | 12 | 80 | 1.56 | 1792 | 25 | 10 | 80 | 1.60 | 2367 |
| 350 | 37 | 1.24 | 18 | 12 | 80 | 1.66 | 2282 | 22 | 8 | 110 | 1.82 | 3207 |
| 500 | 37 | 1.37 | 17 | 10 | 110 | 1.90 | 3154 | 31 | 8 | 110 | 1.95 | 4257 |
| 750 | 61 | 1.56 | 20 | 9 | 110 | 2.14 | 4408 | — | — | — | — | — |
| 1000 | 61 | 1.70 | 26 | 9 | 110 | 2.29 | 5558 | — | — | — | — | — |
| Aluminum 100% Insulation Level (260 mil) | ||||||||||||
| 1 | 19 | 0.88 | 6 | 14 | 80 | 1.26 | 692 | 13 | 14 | 80 | 1.26 | 785 |
| 1/0 | 19 | 0.92 | 6 | 14 | 80 | 1.30 | 741 | 16 | 14 | 80 | 1.30 | 874 |
| 2/0 | 19 | 0.97 | 7 | 14 | 80 | 1.34 | 812 | 13 | 12 | 80 | 1.37 | 1000 |
| 3/0 | 19 | 1.02 | 9 | 14 | 80 | 1.41 | 930 | 16 | 12 | 80 | 1.45 | 1155 |
| 4/0 | 19 | 1.07 | 11 | 14 | 80 | 1.47 | 1040 | 13 | 10 | 80 | 1.54 | 1345 |
| 250 | 37 | 1.13 | 13 | 14 | 80 | 1.53 | 1143 | 16 | 10 | 80 | 1.60 | 1522 |
| 350 | 37 | 1.23 | 18 | 14 | 80 | 1.63 | 1379 | 16 | 9 | 110 | 1.79 | 1945 |
| 500 | 37 | 1.36 | 16 | 12 | 110 | 1.85 | 1831 | 29 | 10 | 110 | 1.90 | 2480 |
| 750 | 61 | 1.57 | 15 | 10 | 110 | 2.13 | 2464 | — | — | — | — | — |
| 1000 | 61 | 1.72 | 16 | 9 | 110 | 2.31 | 3003 | — | — | — | — | — |
25 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kt | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/kt | |||
| Copper 133% Insulation Level (320 mil) | ||||||||||||
| 1 | 19 | 1.01 | 7 | 14 | 80 | 1.38 | 1011 | 13 | 12 | 80 | 1.41 | 1199 |
| 1/0 | 19 | 1.05 | 9 | 14 | 80 | 1.44 | 1163 | 16 | 12 | 80 | 1.48 | 1388 |
| 2/0 | 19 | 1.09 | 11 | 14 | 80 | 1.49 | 1311 | 13 | 10 | 80 | 1.56 | 1616 |
| 3/0 | 19 | 1.14 | 14 | 14 | 80 | 1.54 | 1501 | 16 | 10 | 80 | 1.61 | 1867 |
| 4/0 | 19 | 1.20 | 18 | 14 | 80 | 1.59 | 1737 | 16 | 9 | 110 | 1.76 | 2299 |
| 250 | 37 | 1.26 | 13 | 12 | 80 | 1.68 | 1943 | 25 | 10 | 110 | 1.79 | 2625 |
| 350 | 37 | 1.36 | 18 | 12 | 110 | 1.85 | 2554 | 22 | 8 | 110 | 1.94 | 3376 |
| 500 | 37 | 1.49 | 17 | 10 | 110 | 2.02 | 3336 | 31 | 8 | 110 | 2.07 | 4439 |
| 750 | 61 | 1.68 | 20 | 9 | 110 | 2.27 | 4612 | — | — | — | — | — |
| 1000 | 61 | 1.83 | 26 | 9 | 110 | 2.42 | 5777 | — | — | — | — | — |
| Aluminum 133% Insulation Level (320 mil) | ||||||||||||
| 1/0 | 19 | 1.05 | 6 | 14 | 80 | 1.44 | 891 | 16 | 14 | 80 | 1.44 | 1024 |
| 2/0 | 19 | 1.09 | 7 | 14 | 80 | 1.48 | 967 | 13 | 12 | 80 | 1.52 | 1155 |
| 3/0 | 19 | 1.14 | 9 | 14 | 80 | 1.53 | 1068 | 16 | 12 | 80 | 1.57 | 1293 |
| 4/0 | 19 | 1.20 | 11 | 14 | 80 | 1.59 | 1183 | 13 | 10 | 80 | 1.67 | 1488 |
| 250 | 37 | 1.25 | 13 | 14 | 80 | 1.65 | 1292 | 16 | 10 | 110 | 1.79 | 1780 |
| 350 | 37 | 1.35 | 18 | 14 | 110 | 1.81 | 1648 | 16 | 9 | 110 | 1.91 | 2112 |
| 500 | 37 | 1.48 | 16 | 12 | 110 | 1.97 | 2011 | 29 | 10 | 110 | 2.02 | 2660 |
| 750 | 61 | 1.69 | 15 | 10 | 110 | 2.25 | 2668 | — | — | — | — | — |
| 1000 | 61 | 1.84 | 16 | 9 | 110 | 2.43 | 3222 | — | — | — | — | — |
35 kV EPR Insulated
| Size AWG or kmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | mil | in | lbs/kft | AWG | mil | in | lbs/kft | |||||
| Copper 100% Insulation Level (345 mil) | ||||||||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 80 | 1.50 | 1221 | 16 | 12 | 80 | 1.53 | 1446 |
| 2/0 | 19 | 1.15 | 11 | 14 | 80 | 1.54 | 1371 | 13 | 10 | 80 | 1.62 | 1676 |
| 3/0 | 19 | 1.20 | 14 | 14 | 80 | 1.59 | 1563 | 16 | 10 | 80 | 1.67 | 1929 |
| 4/0 | 19 | 1.25 | 18 | 14 | 80 | 1.65 | 1801 | 16 | 9 | 110 | 1.81 | 2367 |
| 250 | 37 | 1.31 | 13 | 12 | 110 | 1.80 | 2117 | 25 | 10 | 110 | 1.84 | 2695 |
| 350 | 37 | 1.41 | 18 | 12 | 110 | 1.90 | 2629 | 22 | 8 | 110 | 2.00 | 3450 |
| 500 | 37 | 1.54 | 17 | 10 | 110 | 2.10 | 3464 | 31 | 8 | 110 | 2.16 | 4567 |
| 750 | 61 | 1.73 | 20 | 9 | 110 | 2.32 | 4701 | — | — | — | — | — |
| 1000 | 61 | 1.88 | 26 | 9 | 110 | 2.47 | 5872 | — | — | — | — | — |
| Aluminum 100% Insulation Level (345 mil) | ||||||||||||
| 1/0 | 19 | 1.10 | 6 | 14 | 80 | 1.49 | 948 | 16 | 14 | 80 | 1.49 | 1082 |
| 2/0 | 19 | 1.14 | 7 | 14 | 80 | 1.53 | 1026 | 13 | 12 | 80 | 1.57 | 1214 |
| 3/0 | 19 | 1.19 | 9 | 14 | 80 | 1.58 | 1129 | 16 | 12 | 80 | 1.62 | 1354 |
| 4/0 | 19 | 1.25 | 11 | 14 | 80 | 1.64 | 1247 | 13 | 10 | 110 | 1.78 | 1660 |
| 250 | 37 | 1.30 | 13 | 14 | 110 | 1.76 | 1465 | 16 | 10 | 110 | 1.84 | 1849 |
| 350 | 37 | 1.40 | 18 | 14 | 110 | 1.86 | 1722 | 16 | 9 | 110 | 1.96 | 2186 |
| 500 | 37 | 1.53 | 16 | 12 | 110 | 2.06 | 2137 | 29 | 10 | 110 | 2.10 | 2786 |
| 750 | 61 | 1.74 | 15 | 10 | 110 | 2.30 | 2756 | — | — | — | — | — |
| 1000 | 61 | 1.89 | 16 | 9 | 110 | 2.48 | 3317 | — | — | — | — | — |
35 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/ft | Number of Wires | Size AWG | Jacket Thickness mil | Approximate Outside Diameter in | Approximate Net Weight lb/ft | |||
| Copper 133% Insulation Level (420 mil) | ||||||||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 80 | 1.65 | 1407 | 16 | 12 | 80 | 1.68 | 1632 |
| 2/0 | 19 | 1.30 | 11 | 14 | 110 | 1.76 | 1668 | 13 | 10 | 110 | 1.83 | 1978 |
| 3/0 | 19 | 1.35 | 14 | 14 | 110 | 1.81 | 1869 | 16 | 10 | 110 | 1.88 | 2240 |
| 4/0 | 19 | 1.40 | 18 | 14 | 110 | 1.86 | 2118 | 16 | 9 | 110 | 1.96 | 2582 |
| 250 | 37 | 1.46 | 13 | 12 | 110 | 1.95 | 2339 | 25 | 10 | 110 | 1.99 | 2917 |
| 350 | 37 | 1.56 | 18 | 12 | 110 | 2.08 | 2913 | 22 | 8 | 110 | 2.18 | 3734 |
| 500 | 37 | 1.69 | 17 | 10 | 110 | 2.26 | 3719 | 31 | 8 | 110 | 2.31 | 4822 |
| 750 | 61 | 1.88 | 20 | 9 | 110 | 2.47 | 4980 | — | — | — | — | — |
| 1000 | 61 | 2.03 | 26 | 9 | 110 | 2.62 | 6171 | — | — | — | — | — |
| Aluminum 133% Insulation Level (420 mil) | ||||||||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 80 | 1.64 | 1132 | 16 | 14 | 80 | 1.64 | 1266 |
| 2/0 | 19 | 1.29 | 7 | 14 | 110 | 1.75 | 1322 | 13 | 12 | 110 | 1.78 | 1512 |
| 3/0 | 19 | 1.34 | 9 | 14 | 110 | 1.80 | 1434 | 16 | 12 | 110 | 1.83 | 1662 |
| 4/0 | 19 | 1.40 | 11 | 14 | 110 | 1.86 | 1563 | 13 | 10 | 110 | 1.93 | 1872 |
| 250 | 37 | 1.45 | 13 | 14 | 110 | 1.91 | 1684 | 16 | 10 | 110 | 1.99 | 2069 |
| 350 | 37 | 1.56 | 18 | 14 | 110 | 2.04 | 2001 | 16 | 9 | 110 | 2.15 | 2466 |
| 500 | 37 | 1.68 | 16 | 12 | 110 | 2.21 | 2389 | 29 | 10 | 110 | 2.25 | 3038 |
| 750 | 61 | 1.89 | 15 | 10 | 110 | 2.46 | 3034 | — | — | — | — | — |
| 1000 | 61 | 2.04 | 16 | 9 | 110 | 2.63 | 3613 | — | — | — | — | — |
Primary UD PILC Replacement, EPR/PE 15 kV – 35 kV
Features
Reduced overall OD.
True triple extrusion system, for optimum concentricity, and excellent electric field control.
Closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
Sealed conductor passes the Production Water Penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
Heavy duty mechanical and sunlight resistance jacket.
Application
Underground primary distribution circuits where existing duct spacing is limited and reduced cable OD is desired.
May be used in wet or dry locations, installed in underground ducts, or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV.
Specifications
Maximum operating voltage:
• 15 kV – 35 kV, 100% and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
1. Conductor: Uncoated soft annealed copper Class B compacted stranding per ASTM B496.
On request, Filled strand conductor.
| Parameter | Specification |
|---|---|
| Sizes | 4/0 AWG – 1000 kcmil. |
| 2. Conductor Shield | Extruded semiconducting cross-linked polyethylene per ICEA and AEIC. |
| 3. Insulation | High quality, heat, moisture, ozone and corona resistant, thermosetting ethylene propylene rubber (EPR) per ICEA and AEIC. |
| 4. Insulation Shield | Extruded Semiconducting cross-linked polyethylene per ICEA and AEIC. |
| 5. Shield | Flat wires straps of annealed uncoated copper per ICEA, helically applied and uniformly spaced. |
| Note | Specific flat strap constructions and configuration will vary per customer fault current requirements. |
| 6. Jacket | Extruded to fill of Black Linear Low Density Polyethylene (LLDPE) sunlight resistant thermoplastic compound, per ICEA S-97-682. |
On request, XLPE jacket.
15 kV EPR Insulated
| 100% Insulation Level (175 mils) | 133% Insulation Level (220 mils) | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Flat Straps | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | Flat Straps | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | ||
| No. of Wires | Dimensions | No. of Wires | Dimensions | ||||||||
| mil | mil | mil | in | lb/kft | mil | mil | mil | in | lb/kft | ||
| 4/0 | 19 | 12 | 20 x 175 | 50 | 1.08 | 1185 | 12 | 20 x 175 | 50 | 1.17 | 1267 |
| 250 | 37 | 14 | 20 x 175 | 50 | 1.12 | 1353 | 14 | 20 x 175 | 50 | 1.22 | 1439 |
| 350 | 37 | 14 | 20 x 175 | 50 | 1.25 | 1742 | 14 | 20 x 175 | 50 | 1.35 | 1838 |
| 500 | 37 | 14 | 20 X 175 | 50 | 1.37 | 2270 | 14 | 20 x 175 | 50 | 1.47 | 2376 |
| 750 | 61 | 16 | 20 x 175 | 50 | 1.56 | 3176 | 16 | 20 x 175 | 50 | 1.65 | 3295 |
| 1000 | 61 | 16 | 20 x 175 | 50 | 1.71 | 4041 | 16 | 20 x 175 | 50 | 1.83 | 4214 |
25 kV EPR Insulated
| 100% Insulation Level (260 mls) | ||||||
|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Flat Straps | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |
| Number of Wires | Dimensions | |||||
| mil | mil | mil | in | lb/kft | ||
| 4/0 | 19 | 12 | 20 x 175 | 50 | 1.27 | 1368 |
| 250 | 37 | 14 | 20 x 175 | 50 | 1.32 | 1544 |
| 350 | 37 | 14 | 20 x 175 | 50 | 1.43 | 1929 |
| 500 | 37 | 14 | 20 x 175 | 50 | 1.55 | 2475 |
| 750 | 61 | 16 | 20 x 175 | 50 | 1.73 | 3406 |
| 1000 | 61 | 16 | 20 x 175 | 50 | 1.91 | 4338 |
35 kV EPR Insulated
| 100% Insulation Level (345 mIL) | ||||||
|---|---|---|---|---|---|---|
| Size AWG or kcmil | Number of Strands | Flat Straps | Jacket Thickness | Approximate Outside Diameter | Approximate Net Weight | |
| Number of Wires | Dimensions | |||||
| mil | mil | mil | in | lb/kft | ||
| 4/0 | 19 | 12 | 20 x 175 | 50 | 1.45 | 1558 |
| 250 | 37 | 14 | 20 x 175 | 50 | 1.49 | 1741 |
| 350 | 37 | 14 | 20 x 175 | 50 | 1.60 | 2142 |
| 500 | 37 | 14 | 20 x 175 | 50 | 1.72 | 2705 |
| 750 | 61 | 16 | 20 x 175 | 50 | 1.93 | 3707 |
| 1000 | 61 | 16 | 20 x 175 | 50 | 2.08 | 4620 |
Primary UD TR-XLPE Insulated, Concentric Neutral 15 kV – 35 kV
Features
Low tension stripping compounds.
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 kV – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 kV – 46 kV.
Specifications
Maximum operating voltage:
• 5 kV – 46 kV, 100% and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
1. Conductor: Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On request, strand filled.
Sizes: 8 AWG – 1000 kcmil.
On request, larger sizes available.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
On request, super clean and super smooth materials.
| Parameter | Specification |
|---|---|
| 3. Insulation | Thermoset tree-retardant cross-linked polyethylene (TR-XLPE). |
| 4. Insulation Shield | Semi conducting cross-linked polyethylene (XLPE). |
| 5. Concentric Neutral | Tinned coated soft annealed solid copper wires per ASTM B3 and B33, helically applied and uniformly spaced. |
Full or 1/3 Neutral.
On request, a Contrahelical Wire can be applied per customer request.
5 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires in | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (90 mil) | ||||||||||
| 2 | 7 | 0.50 | 6 | 14 | 0.70 | 375 | 16 | 14 | 0.70 | 509 |
| 1 | 19 | 0.54 | 7 | 14 | 0.74 | 449 | 13 | 12 | 0.77 | 632 |
| 1/0 | 19 | 0.58 | 9 | 14 | 0.78 | 552 | 16 | 12 | 0.81 | 772 |
| 2/0 | 19 | 0.63 | 11 | 14 | 0.82 | 674 | 13 | 10 | 0.90 | 967 |
| 3/0 | 19 | 0.68 | 14 | 14 | 0.87 | 833 | 16 | 10 | 0.95 | 1187 |
| 4/0 | 19 | 0.73 | 18 | 14 | 0.93 | 1035 | 16 | 9 | 1.03 | 1476 |
| 250 | 37 | 0.79 | 13 | 12 | 1.02 | 1201 | — | — | — | — |
| 350 | 37 | 0.89 | 18 | 12 | 1.12 | 1639 | — | — | — | — |
| 500 | 37 | 1.02 | 17 | 10 | 1.32 | 2345 | — | — | — | — |
| 750 | 61 | 1.21 | 20 | 9 | 1.53 | 3440 | — | — | — | — |
| 1000 | 61 | 1.36 | 26 | 9 | 1.68 | 4504 | — | — | — | — |
| Aluminum 100% Insulation Level (90 mil) | ||||||||||
| 2 | 1 | 0.48 | 6 | 14 | 0.67 | 221 | 10 | 14 | 0.67 | 275 |
| 2 | 7 | 0.50 | 6 | 14 | 0.70 | 232 | 10 | 14 | 0.70 | 285 |
| 1 | 19 | 0.54 | 6 | 14 | 0.74 | 255 | 13 | 14 | 0.74 | 349 |
| 1/0 | 1 | 0.54 | 6 | 14 | 0.74 | 270 | 16 | 14 | 0.74 | 404 |
| 1/0 | 19 | 0.58 | 6 | 14 | 0.78 | 284 | 16 | 14 | 0.78 | 418 |
| 2/0 | 19 | 0.62 | 7 | 14 | 0.82 | 333 | 13 | 12 | 0.86 | 516 |
| 3/0 | 19 | 0.67 | 9 | 14 | 0.87 | 404 | 16 | 12 | 0.91 | 624 |
| 4/0 | 19 | 0.73 | 11 | 14 | 0.93 | 485 | 13 | 10 | 1.00 | 778 |
| 250 | 37 | 0.79 | 13 | 14 | 0.98 | 559 | 16 | 10 | 1.06 | 927 |
| 350 | 37 | 0.89 | 18 | 14 | 1.09 | 743 | 16 | 9 | 1.19 | 1185 |
| 500 | 37 | 1.02 | 16 | 12 | 1.27 | 1031 | 29 | 10 | 1.31 | 1672 |
| 750 | 61 | 1.22 | 15 | 10 | 1.52 | 1493 | — | — | — | — |
| 1000 | 61 | 1.37 | 16 | 9 | 1.69 | 1941 | — | — | — | — |
8 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (115 mil) | ||||||||||
| 2 | 7 | 0.55 | 6 | 14 | 0.75 | 395 | 16 | 14 | 0.75 | 529 |
| 1 | 19 | 0.59 | 7 | 14 | 0.79 | 470 | 13 | 12 | 0.83 | 653 |
| 1/0 | 19 | 0.63 | 9 | 14 | 0.83 | 575 | 16 | 12 | 0.87 | 794 |
| 2/0 | 19 | 0.68 | 11 | 14 | 0.88 | 698 | 13 | 10 | 0.95 | 990 |
| 3/0 | 19 | 0.73 | 14 | 14 | 0.93 | 858 | 16 | 10 | 1.00 | 1212 |
| 4/0 | 19 | 0.78 | 18 | 14 | 0.98 | 1062 | 16 | 9 | 1.08 | 1503 |
| 250 | 37 | 0.84 | 13 | 12 | 1.07 | 1229 | — | — | — | — |
| 350 | 37 | 0.94 | 18 | 12 | 1.17 | 1671 | — | — | — | — |
| 500 | 37 | 1.07 | 17 | 10 | 1.37 | 2382 | — | — | — | — |
| 750 | 61 | 1.26 | 20 | 9 | 1.58 | 3483 | — | — | — | — |
| 1000 | 61 | 1.41 | 26 | 9 | 1.73 | 4552 | — | — | — | — |
| Aluminum 100% Insulation Level (115 mil) | ||||||||||
| 2 | 1 | 0.53 | 6 | 14 | 0.72 | 240 | 10 | 14 | 0.72 | 293 |
| 2 | 7 | 0.55 | 6 | 14 | 0.75 | 251 | 10 | 14 | 0.75 | 305 |
| 1 | 19 | 0.59 | 6 | 14 | 0.79 | 276 | 13 | 14 | 0.79 | 369 |
| 1/0 | 1 | 0.59 | 6 | 14 | 0.79 | 291 | 16 | 14 | 0.79 | 425 |
| 1/0 | 19 | 0.63 | 6 | 14 | 0.83 | 306 | 16 | 14 | 0.83 | 440 |
| 2/0 | 19 | 0.68 | 7 | 14 | 0.87 | 357 | 13 | 12 | 0.91 | 540 |
| 3/0 | 19 | 0.73 | 9 | 14 | 0.92 | 429 | 16 | 12 | 0.96 | 649 |
| 4/0 | 19 | 0.78 | 11 | 14 | 0.98 | 512 | 13 | 10 | 1.05 | 805 |
| 250 | 37 | 0.84 | 13 | 14 | 1.04 | 588 | 16 | 10 | 1.11 | 955 |
| 350 | 37 | 0.94 | 18 | 14 | 1.14 | 775 | 16 | 9 | 1.24 | 1216 |
| 500 | 37 | 1.07 | 16 | 12 | 1.32 | 1068 | 29 | 10 | 1.36 | 1709 |
| 750 | 61 | 1.27 | 15 | 10 | 1.57 | 1536 | — | — | — | — |
| 1000 | 61 | 1.42 | 16 | 9 | 1.74 | 1988 | — | — | — | — |
15 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (175 mil) | ||||||||||
| 2 | 7 | 0.68 | 6 | 14 | 0.88 | 449 | 16 | 14 | 0.88 | 583 |
| 1 | 19 | 0.71 | 7 | 14 | 0.91 | 527 | 13 | 12 | 0.95 | 710 |
| 1/0 | 19 | 0.75 | 9 | 14 | 0.95 | 635 | 16 | 12 | 0.99 | 855 |
| 2/0 | 19 | 0.80 | 11 | 14 | 1.00 | 761 | 13 | 10 | 1.07 | 1054 |
| 3/0 | 19 | 0.85 | 14 | 14 | 1.05 | 926 | 16 | 10 | 1.12 | 1279 |
| 4/0 | 19 | 0.90 | 18 | 14 | 1.10 | 1133 | 16 | 9 | 1.20 | 1575 |
| 250 | 37 | 0.96 | 13 | 12 | 1.19 | 1305 | — | — | — | — |
| 350 | 37 | 1.06 | 18 | 12 | 1.32 | 1776 | — | — | — | — |
| 500 | 37 | 1.19 | 17 | 10 | 1.49 | 2478 | — | — | — | — |
| 750 | 61 | 1.38 | 20 | 9 | 1.71 | 3593 | — | — | — | — |
| 1000 | 61 | 1.53 | 26 | 9 | 1.89 | 4715 | — | — | — | — |
| 1000 | 61 | 1.53 | 26 | 9 | 2.12 | 5170 | — | — | — | — |
| Aluminum 100% Insulation Level (175 mil) | ||||||||||
| 2 | 1 | 0.65 | 6 | 14 | 0.85 | 291 | 10 | 14 | 0.85 | 345 |
| 2 | 7 | 0.67 | 6 | 14 | 0.87 | 304 | 10 | 14 | 0.87 | 358 |
| 1 | 19 | 0.71 | 6 | 14 | 0.91 | 332 | 13 | 14 | 0.91 | 426 |
| 1/0 | 1 | 0.72 | 6 | 14 | 0.91 | 347 | 16 | 14 | 0.91 | 482 |
| 1/0 | 19 | 0.75 | 6 | 14 | 0.95 | 365 | 16 | 14 | 0.95 | 499 |
| 2/0 | 19 | 0.80 | 7 | 14 | 0.99 | 419 | 13 | 12 | 1.03 | 602 |
| 3/0 | 19 | 0.85 | 9 | 14 | 1.04 | 495 | 16 | 12 | 1.08 | 715 |
| 4/0 | 19 | 0.90 | 11 | 14 | 1.10 | 582 | 13 | 10 | 1.18 | 875 |
| 250 | 37 | 0.96 | 13 | 14 | 1.16 | 663 | 16 | 10 | 1.23 | 1030 |
| 350 | 37 | 1.06 | 18 | 14 | 1.28 | 878 | 16 | 9 | 1.38 | 1320 |
| 500 | 37 | 1.19 | 16 | 12 | 1.44 | 1162 | 29 | 10 | 1.49 | 1804 |
| 750 | 61 | 1.40 | 15 | 10 | 1.69 | 1647 | — | — | — | — |
| 1000 | 61 | 1.54 | 16 | 9 | 1.90 | 2150 | — | — | — | — |
15 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| AWG | in | lb/kft | AWG | in | lb/kft | |||||
| Copper 133% Insulation Level (220 mil) | ||||||||||
| 2 | 7 | 0.77 | 6 | 14 | 0.97 | 496 | 16 | 14 | 0.97 | 630 |
| 1 | 19 | 0.81 | 7 | 14 | 1.01 | 576 | 13 | 12 | 1.04 | 759 |
| 1/0 | 19 | 0.85 | 9 | 14 | 1.05 | 686 | 16 | 12 | 1.08 | 906 |
| 2/0 | 19 | 0.89 | 11 | 14 | 1.09 | 815 | 13 | 10 | 1.17 | 1108 |
| 3/0 | 19 | 0.94 | 14 | 14 | 1.14 | 982 | 16 | 10 | 1.22 | 1336 |
| 4/0 | 19 | 1.00 | 18 | 14 | 1.20 | 1193 | 16 | 9 | 1.30 | 1635 |
| 250 | 37 | 1.05 | 13 | 12 | 1.31 | 1390 | — | — | — | — |
| 350 | 37 | 1.16 | 18 | 12 | 1.41 | 1847 | — | — | — | — |
| 500 | 37 | 1.28 | 17 | 10 | 1.58 | 2556 | — | — | — | — |
| 750 | 61 | 1.47 | 20 | 9 | 1.80 | 3682 | — | — | — | — |
| 1000 | 61 | 1.62 | 26 | 9 | 1.98 | 4815 | — | — | — | — |
| Aluminum 133% Insulation Level (220 mil) | ||||||||||
| 2 | 1 | 0.74 | 6 | 14 | 0.94 | 336 | 10 | 14 | 0.94 | 389 |
| 2 | 7 | 0.76 | 6 | 14 | 0.96 | 350 | 10 | 14 | 0.96 | 404 |
| 1 | 19 | 0.80 | 6 | 14 | 1.00 | 380 | 13 | 14 | 1.00 | 474 |
| 1/0 | 1 | 0.81 | 6 | 14 | 1.00 | 396 | 16 | 14 | 1.00 | 530 |
| 1/0 | 19 | 0.84 | 6 | 14 | 1.04 | 415 | 16 | 14 | 1.04 | 550 |
| 2/0 | 19 | 0.89 | 7 | 14 | 1.08 | 472 | 13 | 12 | 1.12 | 655 |
| 3/0 | 19 | 0.94 | 9 | 14 | 1.13 | 551 | 16 | 12 | 1.17 | 771 |
| 4/0 | 19 | 0.99 | 11 | 14 | 1.19 | 641 | 13 | 10 | 1.27 | 934 |
| 250 | 37 | 1.05 | 13 | 14 | 1.27 | 745 | 16 | 10 | 1.35 | 1113 |
| 350 | 37 | 1.15 | 18 | 14 | 1.37 | 948 | 16 | 9 | 1.47 | 1389 |
| 500 | 37 | 1.28 | 16 | 12 | 1.53 | 1239 | 29 | 10 | 1.58 | 1881 |
| 750 | 61 | 1.49 | 15 | 10 | 1.78 | 1735 | — | — | — | — |
| 1000 | 61 | 1.64 | 16 | 9 | 1.99 | 2250 | — | — | — | — |
25 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (260 mil) | ||||||||||
| 1 | 19 | 0.89 | 7 | 14 | 1.09 | 624 | 13 | 12 | 1.12 | 807 |
| 1/0 | 19 | 0.93 | 9 | 14 | 1.13 | 736 | 16 | 12 | 1.16 | 956 |
| 2/0 | 19 | 0.97 | 11 | 14 | 1.17 | 867 | 13 | 10 | 1.25 | 1160 |
| 3/0 | 19 | 1.02 | 14 | 14 | 1.24 | 1057 | 16 | 10 | 1.32 | 1411 |
| 4/0 | 19 | 1.08 | 18 | 14 | 1.30 | 1272 | 16 | 9 | 1.40 | 1714 |
| 250 | 37 | 1.13 | 13 | 12 | 1.39 | 1452 | — | — | — | — |
| 350 | 37 | 1.24 | 18 | 12 | 1.49 | 1914 | — | — | — | — |
| 500 | 37 | 1.37 | 17 | 10 | 1.66 | 2630 | — | — | — | — |
| 750 | 61 | 1.56 | 20 | 9 | 1.91 | 3808 | — | — | — | — |
| 1000 | 61 | 1.70 | 26 | 9 | 2.06 | 4908 | — | — | — | — |
| Aluminum 100% Insulation Level (260 mil) | ||||||||||
| 1 | 19 | 0.88 | 6 | 14 | 1.08 | 427 | 13 | 14 | 1.08 | 521 |
| 1/0 | 1 | 0.89 | 6 | 14 | 1.08 | 443 | 16 | 14 | 1.08 | 577 |
| 1/0 | 19 | 0.92 | 6 | 14 | 1.12 | 465 | 16 | 14 | 1.12 | 599 |
| 2/0 | 19 | 0.97 | 7 | 14 | 1.17 | 524 | 13 | 12 | 1.20 | 707 |
| 3/0 | 19 | 1.02 | 9 | 14 | 1.24 | 624 | 16 | 12 | 1.27 | 845 |
| 4/0 | 19 | 1.07 | 11 | 14 | 1.29 | 719 | 13 | 10 | 1.37 | 1012 |
| 250 | 37 | 1.13 | 13 | 14 | 1.35 | 806 | 16 | 10 | 1.43 | 1174 |
| 350 | 37 | 1.23 | 18 | 14 | 1.45 | 1014 | 16 | 9 | 1.55 | 1455 |
| 500 | 37 | 1.36 | 16 | 12 | 1.62 | 1312 | 29 | 10 | 1.66 | 1954 |
| 750 | 61 | 1.57 | 15 | 10 | 1.89 | 1859 | — | — | — | — |
| 1000 | 61 | 1.72 | 16 | 9 | 2.07 | 2342 | — | — | — | — |
25 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation in | 1/3 Neutral | Full Neutral | ||||||
| Number of Wires | Size AWG | Approximate Outside Diameter in | Approximate Net Weight lb/kft | Number of Wires | Size AWG | Approximate Outside Diameter in | Approximate Net Weight lb/kft | |||
| Copper 133% Insulation Level (320 mil) | ||||||||||
| 1 | 19 | 1.01 | 7 | 14 | 1.22 | 710 | 13 | 12 | 1.24 | 887 |
| 1/0 | 19 | 1.05 | 9 | 14 | 1.28 | 846 | 16 | 12 | 1.31 | 1060 |
| 2/0 | 19 | 1.09 | 11 | 14 | 1.32 | 982 | 13 | 10 | 1.39 | 1268 |
| 3/0 | 19 | 1.14 | 14 | 14 | 1.37 | 1156 | 16 | 10 | 1.44 | 1503 |
| 4/0 | 19 | 1.20 | 18 | 14 | 1.43 | 1376 | 16 | 9 | 1.52 | 1810 |
| 250 | 37 | 1.26 | 13 | 12 | 1.52 | 1560 | — | — | — | — |
| 350 | 37 | 1.36 | 18 | 12 | 1.62 | 2030 | — | — | — | — |
| 500 | 37 | 1.49 | 17 | 10 | 1.79 | 2756 | — | — | — | — |
| 750 | 61 | 1.68 | 20 | 9 | 2.04 | 3953 | — | — | — | — |
| 1000 | 61 | 1.83 | 26 | 9 | 2.19 | 5065 | — | — | — | — |
| Aluminum 133% Insulation Level (320 mil) | ||||||||||
| 1 | 19 | 1.01 | 6 | 14 | 1.20 | 506 | 13 | 14 | 1.20 | 599 |
| 1/0 | 1 | 1.01 | 6 | 14 | 1.21 | 522 | 16 | 14 | 1.21 | 656 |
| 1/0 | 19 | 1.05 | 6 | 14 | 1.27 | 566 | 16 | 14 | 1.27 | 700 |
| 2/0 | 19 | 1.09 | 7 | 14 | 1.31 | 629 | 13 | 12 | 1.34 | 812 |
| 3/0 | 19 | 1.14 | 9 | 14 | 1.36 | 715 | 16 | 12 | 1.39 | 935 |
| 4/0 | 19 | 1.20 | 11 | 14 | 1.42 | 814 | 13 | 10 | 1.49 | 1107 |
| 250 | 37 | 1.25 | 13 | 14 | 1.47 | 906 | 16 | 10 | 1.55 | 1273 |
| 350 | 37 | 1.35 | 18 | 14 | 1.57 | 1121 | 16 | 9 | 1.67 | 1563 |
| 500 | 37 | 1.48 | 16 | 12 | 1.74 | 1429 | 29 | 10 | 1.78 | 2070 |
| 750 | 61 | 1.69 | 15 | 10 | 2.01 | 1995 | — | — | — | — |
| 1000 | 61 | 1.84 | 16 | 9 | 2.19 | 2489 | — | — | — | — |
35 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (345 mil) | ||||||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 1.33 | 884 | 16 | 12 | 1.36 | 1098 |
| 2/0 | 19 | 1.15 | 11 | 14 | 1.37 | 1021 | 13 | 10 | 1.44 | 1307 |
| 3/0 | 19 | 1.20 | 14 | 14 | 1.42 | 1198 | 16 | 10 | 1.49 | 1545 |
| 4/0 | 19 | 1.25 | 18 | 14 | 1.48 | 1419 | 16 | 9 | 1.57 | 1853 |
| 250 | 37 | 1.31 | 13 | 12 | 1.57 | 1605 | — | — | — | — |
| 350 | 37 | 1.41 | 18 | 12 | 1.67 | 2079 | — | — | — | — |
| 500 | 37 | 1.54 | 17 | 10 | 1.87 | 2850 | — | — | — | — |
| 750 | 61 | 1.73 | 20 | 9 | 2.09 | 4013 | — | — | — | — |
| 1000 | 61 | 1.88 | 26 | 9 | 2.24 | 5129 | — | — | — | — |
| Aluminum 100% Insulation Level (345 mil) | ||||||||||
| 1/0 | 1 | 1.06 | 6 | 14 | 1.28 | 578 | 16 | 14 | 1.28 | 712 |
| 1/0 | 19 | 1.10 | 6 | 14 | 1.32 | 604 | 16 | 14 | 1.32 | 738 |
| 2/0 | 19 | 1.14 | 7 | 14 | 1.36 | 668 | 13 | 12 | 1.39 | 851 |
| 3/0 | 19 | 1.19 | 9 | 14 | 1.41 | 756 | 16 | 12 | 1.44 | 976 |
| 4/0 | 19 | 1.25 | 11 | 14 | 1.47 | 856 | 13 | 10 | 1.54 | 1149 |
| 250 | 37 | 1.30 | 13 | 14 | 1.52 | 950 | 16 | 10 | 1.60 | 1317 |
| 350 | 37 | 1.40 | 18 | 14 | 1.62 | 1169 | 16 | 9 | 1.73 | 1610 |
| 500 | 37 | 1.53 | 16 | 12 | 1.82 | 1521 | 29 | 10 | 1.86 | 2162 |
| 750 | 61 | 1.74 | 15 | 10 | 2.07 | 2054 | — | — | — | — |
| 1000 | 61 | 1.89 | 16 | 9 | 2.24 | 2553 | — | — | — | — |
35 kV TR-XLPE Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 133% Insulation Level (420 mil) | ||||||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 1.48 | 1002 | 16 | 12 | 1.51 | 1222 |
| 2/0 | 19 | 1.30 | 11 | 14 | 1.52 | 1144 | 13 | 10 | 1.60 | 1436 |
| 3/0 | 19 | 1.35 | 14 | 14 | 1.57 | 1324 | 16 | 10 | 1.65 | 1678 |
| 4/0 | 19 | 1.40 | 18 | 14 | 1.63 | 1551 | 16 | 9 | 1.73 | 1992 |
| 250 | 37 | 1.46 | 13 | 12 | 1.72 | 1742 | — | — | — | — |
| 350 | 37 | 1.56 | 18 | 12 | 1.85 | 2267 | — | — | — | — |
| 500 | 37 | 1.69 | 17 | 10 | 2.02 | 3012 | — | — | — | — |
| 750 | 61 | 1.88 | 20 | 9 | 2.24 | 4192 | — | — | — | — |
| 1000 | 61 | 2.03 | 26 | 9 | 2.39 | 5323 | — | — | — | — |
| Aluminum 133% Insulation Level (420 mil) | ||||||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 1.47 | 726 | 16 | 14 | 1.47 | 860 |
| 2/0 | 19 | 1.29 | 7 | 14 | 1.51 | 795 | 13 | 12 | 1.54 | 978 |
| 3/0 | 19 | 1.34 | 9 | 14 | 1.56 | 887 | 16 | 12 | 1.59 | 1107 |
| 4/0 | 19 | 1.40 | 11 | 14 | 1.62 | 993 | 13 | 10 | 1.69 | 1285 |
| 250 | 37 | 1.45 | 13 | 14 | 1.67 | 1092 | 16 | 10 | 1.75 | 1459 |
| 350 | 37 | 1.56 | 18 | 14 | 1.81 | 1361 | 16 | 9 | 1.91 | 1802 |
| 500 | 37 | 1.68 | 16 | 12 | 1.97 | 1688 | 29 | 10 | 2.01 | 2329 |
| 750 | 61 | 1.89 | 15 | 10 | 2.22 | 2241 | — | — | — | — |
| 1000 | 61 | 2.04 | 16 | 9 | 2.39 | 2754 | — | — | — | — |
Primary UD EPR Insulated, Concentric Neutral 15 kV – 35 kV
Features
Low tension stripping compounds.
Sealed conductor passes the production water penetration tests per ICEA-T-31-610 at 15 psi for 60 minutes.
True triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion of insulation and shields.
Application
Underground primary residential and commercial distribution circuits.
May be used in wet or dry locations, installed in underground ducts or direct burial.
Standards
ICEA S-94-649: Standard for Concentric Neutral Rated Cables 5 – 46 kV.
AEIC CS8: Specifications for Extruded Dielectric, Shielded Power Cable, rated 5 – 46 kV.
Specifications
Maximum operating voltage:
• 5 kV – 46 kV, 100 and 133% IL
Maximum conductor operation temperatures:
- Wet and dry locations
- Normal: 105 °C
- Emergency: 140 °C
- Short Circuit: 250 °C
Engineering Information
1. Conductor: Soft annealed uncoated copper Class B compressed or unilay compressed per ASTM B8 or hard drawn aluminum Class B compressed or unilay compressed stranding per ASTM B231.
On request, strand filled.
Sizes: 8 AWG – 1000 kcmil.
On request, larger sizes.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
On request, super-clean and super-smooth materials.
3. Insulation: Thermoset ethylene propylene rubber (EPR).
On request, amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Concentric Neutral: Tinned coated soft annealed solid copper wires per ASTM B3 and B33, helically applied and uniformly spaced.
Full or 1/3 Neutral.
On request, a Contra-helical Wire can be applied.
Technical Data
15 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (175 mils) | ||||||||||
| 2 | 7 | 0.68 | 6 | 14 | 0.88 | 485 | 16 | 14 | 0.88 | 619 |
| 1 | 19 | 0.71 | 7 | 14 | 0.91 | 566 | 13 | 12 | 0.95 | 749 |
| 1/0 | 19 | 0.75 | 9 | 14 | 0.95 | 676 | 16 | 12 | 0.99 | 896 |
| 2/0 | 19 | 0.80 | 11 | 14 | 1.00 | 806 | 13 | 10 | 1.07 | 1099 |
| 3/0 | 19 | 0.85 | 14 | 14 | 1.05 | 974 | 16 | 10 | 1.12 | 1328 |
| 4/0 | 19 | 0.90 | 18 | 14 | 1.10 | 1186 | 16 | 9 | 1.20 | 1627 |
| 250 | 37 | 0.96 | 13 | 12 | 1.19 | 1362 | — | — | — | — |
| 350 | 37 | 1.06 | 18 | 12 | 1.32 | 1840 | — | — | — | — |
| 500 | 37 | 1.19 | 17 | 10 | 1.49 | 2551 | — | — | — | — |
| 750 | 61 | 1.38 | 20 | 9 | 1.71 | 3681 | — | — | — | — |
| 1000 | 61 | 1.53 | 26 | 9 | 1.89 | 4813 | — | — | — | — |
| Aluminum 100% Insulation Level (175 mils) | ||||||||||
| 2 | 1 | 0.65 | 6 | 14 | 0.85 | 325 | 10 | 14 | 0.85 | 379 |
| 2 | 7 | 0.67 | 6 | 14 | 0.87 | 340 | 10 | 14 | 0.87 | 393 |
| 1 | 19 | 0.71 | 6 | 14 | 0.91 | 370 | 13 | 14 | 0.91 | 464 |
| 1/0 | 1 | 0.72 | 6 | 14 | 0.91 | 386 | 16 | 14 | 0.91 | 520 |
| 1/0 | 19 | 0.75 | 6 | 14 | 0.95 | 406 | 16 | 14 | 0.95 | 540 |
| 2/0 | 19 | 0.80 | 7 | 14 | 0.99 | 464 | 13 | 12 | 1.03 | 647 |
| 3/0 | 19 | 0.85 | 9 | 14 | 1.04 | 543 | 16 | 12 | 1.08 | 763 |
| 4/0 | 19 | 0.90 | 11 | 14 | 1.10 | 634 | 13 | 10 | 1.18 | 927 |
| 250 | 37 | 0.96 | 13 | 14 | 1.16 | 719 | 16 | 10 | 1.23 | 1086 |
| 350 | 37 | 1.06 | 18 | 14 | 1.28 | 942 | 16 | 9 | 1.38 | 1383 |
| 500 | 37 | 1.19 | 16 | 12 | 1.44 | 1235 | 29 | 10 | 1.49 | 1876 |
| 750 | 61 | 1.40 | 15 | 10 | 1.69 | 1734 | — | — | — | — |
| 1000 | 61 | 1.54 | 16 | 9 | 1.90 | 2248 | — | — | — | — |
15 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 133% Insulation Level (220 mils) | ||||||||||
| 2 | 7 | 0.77 | 6 | 14 | 0.97 | 545 | 16 | 14 | 0.97 | 679 |
| 1 | 19 | 0.81 | 7 | 14 | 1.01 | 629 | 13 | 12 | 1.04 | 812 |
| 1/0 | 19 | 0.85 | 9 | 14 | 1.05 | 743 | 16 | 12 | 1.08 | 963 |
| 2/0 | 19 | 0.89 | 11 | 14 | 1.09 | 876 | 13 | 10 | 1.17 | 1168 |
| 3/0 | 19 | 0.94 | 14 | 14 | 1.14 | 1047 | 16 | 10 | 1.22 | 1401 |
| 4/0 | 19 | 1.00 | 18 | 14 | 1.20 | 1264 | 16 | 9 | 1.30 | 1705 |
| 250 | 37 | 1.05 | 13 | 12 | 1.31 | 1465 | — | — | — | — |
| 350 | 37 | 1.16 | 18 | 12 | 1.41 | 1932 | — | — | — | — |
| 500 | 37 | 1.28 | 17 | 10 | 1.58 | 2652 | — | — | — | — |
| 750 | 61 | 1.47 | 20 | 9 | 1.80 | 3796 | — | — | — | — |
| 1000 | 61 | 1.62 | 26 | 9 | 1.98 | 4942 | — | — | — | — |
| Aluminum 133% Insulation Level (220 mils) | ||||||||||
| 2 | 1 | 0.74 | 6 | 14 | 0.94 | 382 | 10 | 14 | 0.94 | 436 |
| 2 | 7 | 0.76 | 6 | 14 | 0.96 | 399 | 10 | 14 | 0.96 | 453 |
| 1 | 19 | 0.80 | 6 | 14 | 1.00 | 432 | 13 | 14 | 1.00 | 526 |
| 1/0 | 1 | 0.81 | 6 | 14 | 1.00 | 448 | 16 | 14 | 1.00 | 583 |
| 1/0 | 19 | 0.84 | 6 | 14 | 1.04 | 471 | 16 | 14 | 1.04 | 606 |
| 2/0 | 19 | 0.89 | 7 | 14 | 1.08 | 532 | 13 | 12 | 1.12 | 715 |
| 3/0 | 19 | 0.94 | 9 | 14 | 1.13 | 615 | 16 | 12 | 1.17 | 835 |
| 4/0 | 19 | 0.99 | 11 | 14 | 1.19 | 711 | 13 | 10 | 1.27 | 1004 |
| 250 | 37 | 1.05 | 13 | 14 | 1.27 | 820 | 16 | 10 | 1.35 | 1187 |
| 350 | 37 | 1.15 | 18 | 14 | 1.37 | 1032 | 16 | 9 | 1.47 | 1473 |
| 500 | 37 | 1.28 | 16 | 12 | 1.53 | 1335 | 29 | 10 | 1.58 | 1976 |
| 750 | 61 | 1.49 | 15 | 10 | 1.78 | 1849 | — | — | — | — |
| 1000 | 61 | 1.64 | 16 | 9 | 1.99 | 2377 | — | — | — | — |
25 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lbs/kft | AWG | in | lbs/kft | ||||
| Copper 100% Insulation Level (260 mils) | ||||||||||
| 1 | 19 | 0.89 | 7 | 14 | 1.09 | 691 | 13 | 12 | 1.12 | 874 |
| 1/0 | 19 | 0.93 | 9 | 14 | 1.13 | 807 | 16 | 12 | 1.16 | 1027 |
| 2/0 | 19 | 0.97 | 11 | 14 | 1.17 | 943 | 13 | 10 | 1.25 | 1236 |
| 3/0 | 19 | 1.02 | 14 | 14 | 1.24 | 1139 | 16 | 10 | 1.32 | 1493 |
| 4/0 | 19 | 1.08 | 18 | 14 | 1.30 | 1360 | 16 | 9 | 1.40 | 1801 |
| 250 | 37 | 1.13 | 13 | 12 | 1.39 | 1545 | — | — | — | — |
| 350 | 37 | 1.24 | 18 | 12 | 1.49 | 2019 | — | — | — | — |
| 500 | 37 | 1.37 | 17 | 10 | 1.66 | 2748 | — | — | — | — |
| 750 | 61 | 1.56 | 20 | 9 | 1.91 | 3947 | — | — | — | — |
| 1000 | 61 | 1.70 | 26 | 9 | 2.06 | 5063 | — | — | — | — |
| Aluminum 100% Insulation Level (260 mils) | ||||||||||
| 1 | 19 | 0.88 | 6 | 14 | 1.08 | 493 | 13 | 14 | 1.08 | 587 |
| 1/0 | 1 | 0.89 | 6 | 14 | 1.08 | 510 | 16 | 14 | 1.08 | 644 |
| 1/0 | 19 | 0.92 | 6 | 14 | 1.12 | 535 | 16 | 14 | 1.12 | 669 |
| 2/0 | 19 | 0.97 | 7 | 14 | 1.17 | 599 | 13 | 12 | 1.20 | 782 |
| 3/0 | 19 | 1.02 | 9 | 14 | 1.24 | 705 | 16 | 12 | 1.27 | 925 |
| 4/0 | 19 | 1.07 | 11 | 14 | 1.29 | 805 | 13 | 10 | 1.37 | 1098 |
| 250 | 37 | 1.13 | 13 | 14 | 1.35 | 899 | 16 | 10 | 1.43 | 1266 |
| 350 | 37 | 1.23 | 18 | 14 | 1.45 | 1118 | 16 | 9 | 1.55 | 1559 |
| 500 | 37 | 1.36 | 16 | 12 | 1.62 | 1429 | 29 | 10 | 1.66 | 2071 |
| 750 | 61 | 1.57 | 15 | 10 | 1.89 | 1998 | — | — | — | — |
| 1000 | 61 | 1.72 | 16 | 9 | 2.07 | 2497 | — | — | — | — |
25 kV EPR Insulated
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kdt | AWG | in | lb/kit | ||||
| Copper 133% Insulation Level (320 mils) | ||||||||||
| 1 | 19 | 1.01 | 7 | 14 | 1.21 | 795 | 13 | 12 | 1.24 | 977 |
| 1/0 | 19 | 1.05 | 9 | 14 | 1.27 | 936 | 16 | 12 | 1.31 | 1155 |
| 2/0 | 19 | 1.09 | 11 | 14 | 1.32 | 1077 | 13 | 10 | 1.39 | 1369 |
| 3/0 | 19 | 1.14 | 14 | 14 | 1.37 | 1258 | 16 | 10 | 1.44 | 1612 |
| 4/0 | 19 | 1.20 | 18 | 14 | 1.42 | 1485 | 16 | 9 | 1.52 | 1926 |
| 250 | 37 | 1.26 | 13 | 12 | 1.51 | 1676 | — | — | — | — |
| 350 | 37 | 1.36 | 18 | 12 | 1.62 | 2160 | — | — | — | — |
| 500 | 37 | 1.49 | 17 | 10 | 1.79 | 2902 | — | — | — | — |
| 750 | 61 | 1.68 | 20 | 9 | 2.03 | 4123 | — | — | — | — |
| 1000 | 61 | 1.83 | 26 | 9 | 2.18 | 5254 | — | — | — | — |
| Aluminum 133% Insulation Level (320 mils) | ||||||||||
| 1/0 | 19 | 1.05 | 6 | 14 | 1.27 | 661 | 16 | 14 | 1.27 | 795 |
| 2/0 | 19 | 1.09 | 7 | 14 | 1.31 | 730 | 13 | 12 | 1.34 | 913 |
| 3/0 | 19 | 1.14 | 9 | 14 | 1.36 | 822 | 16 | 12 | 1.39 | 1042 |
| 4/0 | 19 | 1.20 | 11 | 14 | 1.42 | 928 | 13 | 10 | 1.49 | 1221 |
| 250 | 37 | 1.25 | 13 | 14 | 1.47 | 1027 | 16 | 10 | 1.55 | 1395 |
| 350 | 37 | 1.35 | 18 | 14 | 1.57 | 1256 | 16 | 9 | 1.67 | 1698 |
| 500 | 37 | 1.48 | 16 | 12 | 1.74 | 1581 | 29 | 10 | 1.78 | 2223 |
| 750 | 61 | 1.69 | 15 | 10 | 2.01 | 2174 | — | — | — | — |
| 1000 | 61 | 1.84 | 16 | 9 | 2.19 | 2688 | — | — | — | — |
35 kV ERP Insulation
| Size AWG or kcmil | Number of Strands | Nominal OD Over Insulation | 1/3 Neutral | Full Neutral | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | Number of Wires | Size | Approximate Outside Diameter | Approximate Net Weight | |||
| in | AWG | in | lb/kft | AWG | in | lb/kft | ||||
| Copper 100% Insulation Level (345 mils) | ||||||||||
| 1/0 | 19 | 1.10 | 9 | 14 | 1.32 | 985 | 16 | 12 | 1.36 | 1205 |
| 2/0 | 19 | 1.15 | 11 | 14 | 1.37 | 1128 | 13 | 10 | 1.44 | 1421 |
| 3/0 | 19 | 1.20 | 14 | 14 | 1.42 | 1311 | 16 | 10 | 1.49 | 1665 |
| 4/0 | 19 | 1.25 | 18 | 14 | 1.47 | 1540 | 16 | 9 | 1.57 | 1982 |
| 250 | 37 | 1.31 | 13 | 12 | 1.56 | 1734 | — | — | — | — |
| 350 | 37 | 1.41 | 18 | 12 | 1.67 | 2222 | — | — | — | — |
| 500 | 37 | 1.54 | 17 | 10 | 1.87 | 3012 | — | — | — | — |
| 750 | 61 | 1.73 | 20 | 9 | 2.08 | 4200 | — | — | — | — |
| 1000 | 61 | 1.88 | 26 | 9 | 2.23 | 5338 | — | — | — | — |
| Aluminum 100% Insulation Level (345 mils) | ||||||||||
| 1/0 | 1 | 1.06 | 6 | 14 | 1.28 | 678 | 16 | 14 | 1.28 | 812 |
| 1/0 | 19 | 1.10 | 6 | 14 | 1.32 | 709 | 16 | 14 | 1.32 | 844 |
| 2/0 | 19 | 1.14 | 7 | 14 | 1.36 | 780 | 13 | 12 | 1.39 | 963 |
| 3/0 | 19 | 1.19 | 9 | 14 | 1.41 | 875 | 16 | 12 | 1.44 | 1095 |
| 4/0 | 19 | 1.25 | 11 | 14 | 1.47 | 983 | 13 | 10 | 1.54 | 1276 |
| 250 | 37 | 1.30 | 13 | 14 | 1.52 | 1085 | 16 | 10 | 1.60 | 1452 |
| 350 | 37 | 1.40 | 18 | 14 | 1.62 | 1318 | 16 | 9 | 1.73 | 1759 |
| 500 | 37 | 1.53 | 16 | 12 | 1.82 | 1688 | 29 | 10 | 1.86 | 2329 |
| 750 | 61 | 1.74 | 15 | 10 | 2.07 | 2251 | — | — | — | — |
| 1000 | 61 | 1.89 | 16 | 9 | 2.24 | 2771 | — | — | — | — |
| Copper 133% Insulation Level (420 mils) | ||||||||||
| 1/0 | 19 | 1.25 | 9 | 14 | 1.48 | 1146 | 16 | 12 | 1.51 | 1366 |
| 2/0 | 19 | 1.30 | 11 | 14 | 1.52 | 1295 | 13 | 10 | 1.60 | 1587 |
| 3/0 | 19 | 1.35 | 14 | 14 | 1.57 | 1484 | 16 | 10 | 1.65 | 1838 |
| 4/0 | 19 | 1.40 | 18 | 14 | 1.63 | 1721 | 16 | 9 | 1.73 | 2162 |
| 250 | 37 | 1.46 | 13 | 12 | 1.72 | 1921 | — | — | — | — |
| 350 | 37 | 1.56 | 18 | 12 | 1.85 | 2464 | — | — | — | — |
| 500 | 37 | 1.69 | 17 | 10 | 2.02 | 3232 | — | — | — | — |
| 750 | 61 | 1.88 | 20 | 9 | 2.24 | 4445 | — | — | — | — |
| 1000 | 61 | 2.03 | 26 | 9 | 2.39 | 5601 | — | — | — | — |
| Aluminum 133% Insulation Level (420 mils) | ||||||||||
| 1/0 | 19 | 1.25 | 6 | 14 | 1.47 | 868 | 16 | 14 | 1.47 | 1002 |
| 2/0 | 19 | 1.29 | 7 | 14 | 1.51 | 944 | 13 | 12 | 1.54 | 1127 |
| 3/0 | 19 | 1.34 | 9 | 14 | 1.56 | 1045 | 16 | 12 | 1.59 | 1265 |
| 4/0 | 19 | 1.40 | 11 | 14 | 1.62 | 1160 | 13 | 10 | 1.69 | 1453 |
| 250 | 37 | 1.45 | 13 | 14 | 1.67 | 1269 | 16 | 10 | 1.75 | 1636 |
| 350 | 37 | 1.56 | 18 | 14 | 1.81 | 1556 | 16 | 9 | 1.91 | 1997 |
| 500 | 37 | 1.68 | 16 | 12 | 1.97 | 1905 | 29 | 10 | 2.01 | 2546 |
| 750 | 61 | 1.89 | 15 | 10 | 2.22 | 2493 | — | — | — | — |
| 1000 | 61 | 2.04 | 16 | 9 | 2.39 | 3032 | — | — | — | — |
Certificate Display
Type and routine tests are issued from our own testing centre under the ISO 9001 quality system — test reports and certificates accompany every shipment.
Factory Tour
Why Choose Us
Packing & Shipping
- Wooden, steel or steel-wood drums; drum length to customer requirement
- Drum marking per customer / utility specification
- Both drum ends sealed and protected for sea freight
Ready for Your Next Cable Project?
Send us your specifications, cable schedule or RFQ — our engineering team replies with a technical proposal and price within one working day.
- Emailinfo@qzcablegroup.com
- WhatsApp / WeChat+86 173 3570 4553
- Contact personChloe · Export Department
- Factory addressWest Industrial Park, Zhulin Town, Gongyi City, Henan Province, China
Related products
Medium Voltage Cables to BS 6622BS 7835
Medium Voltage Cables to BS 6622/BS 7835
XLPE — Insulated Power Cables
XLPE INSULATED ELECTRICAL ARMOURED and NON-ARMOURED POWER CABLE
Flame retardant and fire resistant cable
An important distinction exists between fire resistant cables and flame retardant cables, even though both of them are subjected to various fire performance tests in order to earn their respective classification. In brief, flame retardant cables are designed to resist the spread of fire into a new…
LSZH — Sheathed Cables